Construction Materials Testing Services
II FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 10
11 5356 Oakland Lake Circle Permit No 1806-0803, Fort Pierce, St. Lucie County., FL
As re�juested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction. materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
WorF, Order No. L Date Type of Report
9$274-1 08/01/2018 In -Place Density Test Report w/Activity Record
We I��pe this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the udersianed.
Sincerely, `=
Universal Engirp4ring Sciences;'lnc.
Certificate A'=A ;thori ation,_Nlo
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
i8d - cam}
FILE COP`
nail: cbugg@nvrinc.com; elibrihi@nvrinc.com; jomcalli@nvrinc.com; rofingar@nvdnc.com; sign/seal MAIL to ryan homes at 1777 Willows Square, Vero
, FL 32966
Revised May 2015
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering •Environmental Sciences
Geophysical'Services kMaterialsTesting'i`Threshold Inspection.
Building Code Administration; Compliance Inspection & Plan Review,
820 lirevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F:
UES Project No: 0310.1700251.0019
UES DOCS No:
UES Report No: 99274-1 ARC 080118
On -Site Time (hrs): 1.00
Lab Time (hrs): 0.00
Travel Time (hrs): 1.00
Total Time (hrs): 2.00
321.638.0978
Activity Record
Clie"t: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Oakland Lake Subdivision Lot 10
5356 Oakland Lake Circle Permit No 1806-0803, Fort Pierce, St. Lucie County, FL
of Activity: Wednesday, 01 August, 2018
nician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
eart, work testing for the House pad.
Whi on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad jAll test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The'lContractor was notified of the test results or a copy was left for their records.
L UES DOCS No � 0310.1700251.0019
UNIVERSA
ENGINEERING. SCI.ENCES UES Report No: 99274-1 DT080118
Consultants Ini Geotechnical Engineering • EnvironmentaiSciences
Geophysical,Services • Materials Testing:-i Threshold Inspection
Building Code Administration, .Comp liance Inspection.& Plan Review
820 BrTard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
Clie Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Proj ct: Oakland Lake Subdivision Lot 10
5356 Oakland Lake Circle Permit No 1806-0803, Fort Pierce, St. Lucie County, FL
Tested: House pad
Typ' of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 08/01/2018
7 Lab: ASTM D1557 Modified Proctor
ician: Cliff Cherrnay
cements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
onlv and do not address the condition of the underlvinq soils below the tested depths.
Test
No. I Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1 ,I
N/W Test
0-1 ft
12.00
21143
113.6
11.8
99
A
2 I
WE Test
0-1 ft
12.00
21143
114.4
11.7
99
A
3
S/E Test
0-1 ft
12.00
21143
112.0
12.2
97
A
4
S/W Test
0-1 ft
12.00
21143
114.1
13.2
99
A
0)�J Ref. Datum: 0 = Top of Final Grade
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21143
115.0
12.0
test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements'
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
i
UES Project No: 0310.1700251.0019
UNIVERSAL UES ROCS- No:
UES Report No..
99274-1 ARC 080118
ENGINEERING SCIENCES On -Site Time (hrs):1.00
Consultants In: Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00 SCANNED
Geophysical Services • Materials Testing - Threshold Inspection Travel Time (hrs): 1.00 BY
Building Code Administration, Compliance Inspection & Plan Review Total Time (hrs):' 2.00 St. Lucie county
82013��vard Avenue, Rockledge, FL 32965 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Clien I Ryan Homes y
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Proje t: Oakland Lake Subdivision Lot 10
5356 Oakland Lake Circle Permit No 48fl6;_ 8Q 0;36;gort Pierce, St. Lucie County, FL
F
.Date I f Activity: Wednesday, 01 August, 2018
Technician: Cliff Cherrnay
As re �ested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earth irk testing for the House pad.
While n site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. A I test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The ntractor was notified of the test results or a copy was left for their records.
DES Project No.: 2 9UNIVERSAL Date Typed: August 08,2018.
ENGINEERING SCIENCES
Consultants In: Geotechnical.Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Bre,i rd Avenue, Rockledge, FL 32955• - P: 321.638.0808 - F: 321.638.0978
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project . Oakland Lake Subdivision Lot 10
5356 Oakland Lake Circle Permit No 1806-0803, Fort Pierce, St. Lucie, County, FL
AS req sted, Universal Engineering Sciences, Inc. (UES) representatives) performed construction materials testing and/or
field insl' ection services on the above project. Testing results and/or inspection observations are reported on the attached
sheetsIThe contents of this package are summarized below:
Scope of Work
Work Order
No.
I Date
I Type of Report
992
4-1
1 08/01/2018
In -Place Density Test Report w/Activity Record
We ho
a this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the un
rsigned.
Sincerely,
Universal Engineering Sciences, Inc.
1li1lj�rl Certificate of Authorization No.00000549
,��'"������ Richard E.
ti y rs
.
Hoaglin, P.E.
2018.08.08
t tC.� 4, 17 6 �
--16:28:32
r
' -04'00'
L7
5w�4
(.;.,.., Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
Attach
ents (1) '
This item has been electronically signed and sealed by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
a
icc E
il: cbugg@nvdnc.com; elibrihi@nvdnc.com; jomcaili@nvrinc.com; rofingar@nvrinc.com; sign/seal MAIL to ryan homes at 1777 Willows Square, Vero
Beach, IL
32966
Revised May 2016
UNIVERSALUUES ES DOCS Noo: 0310.1700251.0019
ENGINEERING SCIENCES UES Report No: 99274-1 DT 080118
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
Q820Bre rd Avenue, Rockledge, FL 32965 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Projec : Oakland Lake Subdivision Lot 10
5356 Oakland Lake Circle Permit No 1806-0803, Fort Pierce, St. Lucie County, FL
Area sted: House pad
Type o Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 08/01/2018
Lab: ASTM D1557 Modified Proctor
Techn cian: Cliff Cherrnay
Requi I'ements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlying soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
N
Test
0-1 ft
12.00
21143
113.6
11.8
99
A
2
N
E Test
0-1 ft
12.00
21143
114.4
11.7
99
A
3
S,jE
Test
0-1 ft
12.00
21143
112.0
12.2
97
A
4
SI
Test
0-1 ft
1 12.00
1 21143
114.1
13.2
99
A
(1) Of. Datum: 0 = Top of Final Grade (3) Comments Key
(2) Maximum Optimum A. Compaction meets min. requirements
Proctor Dry Moisture B. Compaction does not meet min. requirements
# Density Content C. Moisture does not meet requirements
J 21143 115.0 12.0 D. Recompaction required
E. Recomoacted. Retested. Meets Reauirements