UES Project August 142018 20
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing •Threshold Inspection I �QQ — QfJO
Building Code Administration, Compliance Inspection & Plan Review
820 13revard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PA-.._
RECEIVED
Clie t: Ryan Homes
1450 Centrepark Blvd Suite 340 AUG 2 4 2018
West Palm Beach, FL 33401
Pro ect: Oakland Lake Subdivision Lot 09 ST. Lucie County, Permitting
5360 Oakland Lake Circle Permit No 1807-0003, Fort Pierce, St. Lucie County, FL
As equested, Universal Engineering Sciences, Inc. (LIES) representative(s) performed construction materials testing and/or
feel inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Wdrk Order No. I Date IType of Report
' 99526-1 1 08/08/2018 In -Place Density Test Report w/Activity Record
We, hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the, undersigned.
it
Sincerely, a::'
Universa'°Ui;1ginzering Science , .
Certifica' of P1d ` ion Rt8-8 0549
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
Email: cbugg@nvrinc.com; elibrihi@nvrinc.com; iomcalli@nvrinc.com; rofingar@nvrinc.com; sign/seal MAIL to ryan homes at 1777 Willows Square, Vero
:h, FL 32966
(r
Ui=a'r roject No: 0310.1700251.0020
UNIVERSAL UES ROCS No:
UES Report No: 99526-1 ARC 080818
idENGINEERING SCIENCES On -Site Time (hrs):1.00
Consultants In:Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing • Threshold Inspection Travel Time (hrs): 0.25
Building Code Administration, Compliance Inspection & Plan Review Total Time (hrs): 1.25
Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
ect: Oakland Lake Subdivision Lot 09
5360 Oakland Lake Circle Permit No 1807-0003, Fort Pierce, St. Lucie County, FL
of Activity: Wednesday, 08 August, 2018
Technician: Cliff Ch
requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
thwork testing for the House lot.
ile on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the project
ipaction requirements of 95% of the maximum dry density per ASTM D-1557.
Contractor was notified of the test results or a copy was left for their records.
UNIVERSAL UUES ES DOCS Noo: 0310.1700251.0020
ENGINEERING SCIENCES UES Report No: 99526-1 DT080818
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 6revard Avenue, Rockledge, FL 32966 - P: 321.638.0808 - F: 321.638.0978
ClIn-Place Density Test Report
i:�'
I nt: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Pri'ect:Oakland Lake Subdivision Lot 09
J 5360 Oakland Lake Circle Permit No 1807-0003, Fort Pierce, St. Lucie County, FL
Area Tested: House lot
''I
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 08/08/2018
11 Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
RIIlquirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlyinq soils below the tested depths.
Test
Np.
Location of.Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
N/W Test
0-1 ft
12.00
21143
113.4
11.8
99
A
WE Test
0-1 ft
12.00
21143
114.0
12.2
99
A
S/E Test
0-1 ft
12.00
21143
112.3
11.7
98
A
S/W Test
0-1 ft
12.00
21143
114.1
11.5
99
A
Ref. Datum: 0 = Top of Final Grade
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21143
115.0
12.0
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTM procedures.
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
I
DES Project oject No.: 0310.1700251.0020
UNIAi"'ERSAL
Date Typed: August 14,2018
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE R8CZ1VEj)
Client: Ryan Homes Pe AUG. 2 3.201g
1450 Centrepark Blvd Suite 340 rmittin
West Palm Beach, FL 33401 St. Lc,9Depart,
eo g ent
ty
Project: Oakland Lake Subdivision Lot 09
5360 Oakland Lake Circle Permit No'K6&-&Q.QftFort Pierce, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (LIES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No. I Date I Type of Report
99526-1 1 08/08/2018 In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
•,,....4• ,� ter.
' NO
. 48796
.STATE OF
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 00000549
Richard E.
Hoaglin, P.E.
� 2018.08.14
16:12:40
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and sealed by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
ICC Email: cbugg@nvrinc.com; elibrihi@nvrinc.com; jomcalli@nvrinc.com; rofingar@nvrinc.com; sign/seal MAIL to ryan homes at 1777 Willows Square, Vero
Beach, FL 32966
�
UES�,roject No: 0310.1700251.0020
UES DOCS No:
UNIVERSAL UES Report No: 99526-1 ARC 080818
ELuNGINEERING SCIENCES On -Site Time (hrs): 1 .00
Consultants In: Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services 9 Materials Testing • Threshold Inspection Travel Time (hrs): 0.25
: 1.25hrs Time
Building Code Administration, Compliance Inspection &Plan Review Total (hrs):
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 09
5360 Oakland Lake Circle Permit No 1807-0003, Fort Pierce, St. Lucie County, FL
Date of Activity: Wednesday, 08 August, 2018
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House lot.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
lot. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the project
compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
0 r.
UNIVERSAL UU ES Project No:
ES DOCS No: 0310.1700251.0020
ENGINEERING SCIENCES
UES Report No: 99526-1 DT 080818
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
8201 revard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
Clint: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Pr ject: Oakland Lake Subdivision Lot 09
5360 Oakland Lake Circle Permit No 1807-0003, Fort Pierce, St. Lucie County, FL
Ar• a Tested: House lot
of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 08/08/2018
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
rements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underivino soils below the tested debths_
Te It
No
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1 I
NM Test
0-1 ft
12.00
21143
113.4
11.8
99
A
2
N/E Test
0-1 ft
12.00
21143
114.0
12.2
99
A
31'
S/E Test
0-1 ft
12.00
21143
112.3
11.7
98
A
4'I
SM Test
0-1 ft
12.00
21143
114.1
11.5
99
A
(1), Ref. Datum: 0 = Top of Final Grade
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21143
115.0
12.0
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
test was performed without deviation from ASTM procedures.
report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.