ST. LUCIE FIRE DISTRICT
FIRE PREVENTION BUREAU
BUILDING PLAN REVIEW
JURISDICTION: St. Lucie County
OCCUPANCY: P.G.A. Golf. Storage Building
CONTRACTOR:Crist Construction
ARCHITECT: R/ Reinhard
BUILDING OWNER: Tyringham Ridgg
BUILDING LOCATION: 9601 Legends Dr.
OCCUPANCY TYPE: Storage
GROSS SQ FT: 2400 sq ft.
OCCUPANCY LOAD: ****
CONSTRUCTION: NFPA # 220: (II)-(000)
TELEPHONE (561)-462-2312
FAX NO. (561)462-2323
F.P.B. NO: 6629
BUILDING DEPT NO: 97040029
PHONE NO: 461-9555
PHONE NO: 567-7461
REVIEW DATE: 4/7/97
NUMBER OF STORIES: one
AUTOMATIC SP'KLRS: No.
NET S Q FT: 2400
BASED ON:****
SBCCI: (IV) Unprotected
New Construction: X Shell Only Tenant Improvement: Renovation:
Addition: A/S System: Contractor:
Fire Alarm: Contractor: Storage tank:
' All revisions must be in compliance before the final inspection.
The Fire Marshal requires 24 hr. notice on all inspections.
I, Building Departments schedules all inspections by the Fire Marshal.
Required Revisions: 1. Every building or structure used for storage and every section
thereof considered separately shall have at leased two separate means of egress as
remotely located from each other as practicable.
Exception: In ordinary hazard storage occupancies, a single means of egress is
permitted from any story or section, provided that the exit can be reached within 50
feet.
2 If hazardous storage will be evident then two remote exits will be required.
3. Any door in a means of egress shall be side -hinged or pivoted -swing type.
and may be a man door installed in the overhead door.
4. Provide two 3A - 40 BC rated fire extinguishers, and mount near the exit doors.
5. Provide a illuminated exit sign above the exit doors.
6. If the building is used other than daylight hours an emergency lighting system will be
required with a 90 minute battery back up. Because emergency lighting is required the exit
II signs shall be provided with a 90 minute battery back up system also.
Reviewed by: Date: 4-7-97