Loading...
HomeMy WebLinkAbout96090099- BUILDING PLAN REVIEW4 SCANNED ST. LUCIE COUNTY -FT PIERCE FIRE DISTRI&TLU BYCie ty BUILDING PLAN REVIEW P. O. BOX 3030 Ft. Pierce, FL 34948-3030 Telephone: 561-462-2312 FAX: 661-462-2326 JURISDICTION: St Lucie County FPB #: 6577 PROJECT NAME: Reserve Country Club_ BLDG DEPT #: 96080093 C NTRACTOR: Parent Constlo PHONE #: 561-331-6802 A,,, CHITECT: Schlift & Brenner PHONE #: 561-562-1716 BUILDING OWNER: Tgringham Ridge Inc_ REVIEW DATE: 8-13-96 BiUILDING LOCATION: 9000 Country Club Dr # OF STORIES: 1 O�PCUPANCY TYPE: Assembly 'C" AUTO SPKLS: Yes NoTX G,�OSS SQ FOOTAGE: Existing NET SQ FT: 2194 OCCUPANT LOAD: 146 BASED ON: 15 sq ft per person net OCONSTRUCTION TYPE: NFPA #220 _Existing SBCCI V_ (un) N W CONSTRUCTION _X_TENANT IMPROV RENOVATION ADDITION SHELL ONLY i 4LL REVISIONS LISTED MUST BE IN COMPLIANCE BEFORE THE FINAL INSPECTION. The Fire Marshal requires 24 hour notice on all inspections. The Building Department schedules. all final inspections. ,�. Provide additional emergency lighting for all rooms illuminating means of egress. Provide panic hardware for Doors 3 �; and #2 exiting from Casual Dining Room. Provide panic hardware for the existing Main Dining Room which leads directly to the building exterior. NOTE: The occupant load of the building has increased from 83 persons to' 146 persons. Any door in a means of egress serving an occupant load excess of 100 persons may be provided with a latch or lock only if it is panic hardware. 4. A 40BC rated fire extinguisher is required for the kitchen. A 2A-10BC rated extinguisher is required for each 75' of travel for all other areas including the Tennis Pro Shop. REVIEWED BY: 61 DATE: S. /g/::940 Sheet f of ol