HomeMy WebLinkAboutPLAN REVIEW FORMSAINT LUCIE COUNTY FIRE DISTRICT
G�COUN7)%
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
ar' x
Telephone:772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
•Building Dept. SLC FMO Permit # B-1 B-192
,Project Name Farrell Advantage Storage Building A BLDG Permit # 1712-0015
Address 605 Kitterman Road city PSL
Contractor Welsh Construction
Address 3845 West EAU Gallie Blvd City Melbourne
State FL Zip 32934 Telephone (321) 757-7383
Architect/Engineer Frank GReif Telephone (631)271-4432
Occupancy Type Storage Construction Type 116 Square Feet 10,125
Occupant Load * 21 per pains Number of Stories i Access Box Required Access Key Switch
AFSPermit Required FA Permit Required FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electroniccopy must be received prior to permitting.
a. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned spate..
B. Plans and construction are subject to corrections in field to maintain code compliance.
9. Automatic fan shutdown Is required for HVAC system/s that exceed 2,000 drn design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection'Systems require a separate review and. permit.
THE FLORIDA FIRE PREVENTION CODE, 2015 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.Frovide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detector(s)
;hall be tied into the fire alarm system.
2. The Installation or Alteration of Fire Sprinkler, Fire Alarm Systems require a separate review and permit.
Page F of 1 Reviewed by Tony )erger Date T-06-2018