Loading...
HomeMy WebLinkAboutPLAN REVIEW FORMSAINT LUCIE COUNTY FIRE DISTRICT OUN� �O PLAN REVIEW FORM 5160 N.W. Milner Drive ;6 Port Saint Lucie, FL 34983 ° x� x Telephone: 772-621-3322 ipFOl,\� Fax: 772-621-3604 Web Address: www.slcfd.com Bubng Dept. SLC FMO Permit # 1B-18-195 Project Name Farrell Advantage Storage Building D ; BLDG Permit # 1712-0020 AddreTs 605 Kitterman Road f City PSL Contractor Welsh Construction Address 3845 West EAU Gallie Blvd City Melbourne State yFL 'Lip 32934 Telephone (321)757-7383 Architect/Engineer 'Fral nk G Relf Telephone (631) 271-4432 Occupancy Type Storage Construction Type IIB Square Feet 6675 Occupant Load "� �14per pains Number of Stories �— Access Box Required Access Key Switch AFS Permit lReq®uired FA Permit RegUlred FFP Permit 1 General Notes 1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only. 2. All revisions, including the electronic copy must be received prior to permitting. 3. The Fire Marshal requires 24 hour notice on all inspections. 4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office. 5. Failed inspections require payment of fee prior to rescheduling of further inspections. 6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans. 7. Fire alarm panels shall be located indoors within air conditioned space. 8. Plans and construction are subject to corrections in the field to maintain code compliance. 9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. 10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit. THE FLORIDA FIRE PREVENTION CODE, 2015 EDITION IS CURRENTLY ENFORCED. BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING A CERTIFICATE OF OCCUPANCY. See General Notes Above and Required Revisions Below ,�Automatic.fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.Provide a remote test and iafspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detector(s) shall be tied into the fire alarm system. Q. The Installation or Alteration of Fire Sprinkler, Fire Alarm Systems require a separate review and permit. Page 1 of 1 Reviewed by Tony Jerger �� Date 7-06-2018