DATE: 7/11/18 JOB ORDER #: 18-2863
CLIENT: All Area Roofing
ADDRESS: 3921 S. US Highway 1 Fort Pierce, FL 34982
PROJECT: Daum Residence Sloped Tile Roof Deck
ADDRESS: 9519 Shadow Lane Fort Pierce, FL
2017 FBC/ASCE-7 DESIGN PRESSURE CALCULATIONS
Project Information:
Mean Roof Height = 10'
Length = 87'
Width = 73'
Parapet Wall: N/A
Design Calculations:
Exposure: C Basic/Ultimate Wind Speed: V„1t=170 mph
Category: II Nominal Wind Speed: V.d=V,it*40.6
Slope: 5/12 (asd = allowable strength design)
Residential KZ = 0.85, Kzt =1.0, Kd = 0.85
Velocity Pressure: q = 0.00256*K,-KztKdV2
Velocity Pressure (,,It): q=0.00256(0.85)(1.0)(0.85)(170)2] = 53.45 psf
Velocity Pressure (.d): q=0.00256(0.85)(1.0)(0.85)(170*40.6)2] = 32.07 psf
Width of Pressure Coefficient: 0.1(73) = 7.3'
0.4(10') = 4.0' } use: 4'0"
Effective Wind Area: <10ft2
For hip roofs with a roof slope of 25 degrees or less, zone three (3) shall be treated as
zone two (2).
External Pressure Coefficient:
1) GCP1 = -0.9
2) GCP2 = -1.7
3) GCP3 = -2.6
Internal Pressure Coefficient:
1) GCPi = 0.18
FILE Copy
Vf Q
Quality , A�I.Jm trance
w
Page 2, 7/11/18, Job Order #18-2&._,
-All Area Roofing
Daum Residence - Sloped Tile Roof Deck
9519 Shadow Lane; Fort Pierce, FL:
Design Pressures Based on Vasd:
1) Field
P1 = 32.07*[(-0.9)
— (0.18)]
_ -34.6 psf
2) Perimeter
P2 = 32.07*[(-1.7)
— (0.18)]
_ -60.3 psf
3) Corners
P3 = 32.07*[(-2.6)
— (0.18)]
_ -89.2 psf
Attachment Reouirements Per RAS 127 (Entegra Plantation Flat Tile):
FLO A
Tile System: Moment Based
Aerodynamic Multiplier: 0.289 ft3 (Direct Deck Application - Table 1
Restoring moment due to gravity: Mg = 7.52 ft-lbf (Table 2)
Attachment resistance expressed as a moment: Mf= 51 ft-lbf Polyset AH-160 Foam Set
(Table 4, Single Medium Paddy 30g)
1) Field :
Mri =
(34.6*0.289)
= 7.52 ft. lb =
2.5 ft. lb. < 51 ft. lb = PASS
2) Perimeter :
Mr2 =
(60.3*0.289)
— 7.52 ft. lb =
9.9 ft. lb. < 51 ft. lb = PASS
3) Corners :
Mr3 =
(89.2*0.289)
— 7.52 ft. lb =18.3
ft. lb. < 51 ft. lb = PASS
System is acceptable as approved with single medium paddy (30g) placement of the
Polyset AH-160 Foam Ahesive by ICP Ahdesives and Sealants based on the requirements
of Florida Product Approval # FL7804-R10.
Notes: Corners and perimeter area dimension shall not be less than a = 4'0"
Contractor to verify 'that the fastening patterns meet manufacturer's
requirements for issuance of a warranty (as applicable).
All work shall be in compliance with the local building code product
control notice of acceptance and manufacturer specifications and Florida
Building Code 2017 Edition.
Wind load calculations based on ASCE-7, 2017 FBC, and information
provided by client. Client is responsible for verifying existing/proposed
conditions/decks as it pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative) or a building department inspector to verify compliance
with specifications.
Sincerely,
ZC No. 48202
Mark A. Mess; P.E.
Florida Engir* ' & cTVWjr(W Inc;`�
Florida Reg.-�.%20?�