Door Replacement
3206 S Lakeview Circle (Apt 104)
Fort Pierce, FL 34949
Whom It May Concern:
lur office has calculated the required design pressure in accordance with ASCE 7-10 for
replacement of the doors at the above referenced address.
speed: V„lt: 165mph, Vasa: 128 mph
;ure: D
sure Type: Enclosed
Size: Sliding Glass Doors 139" wide X 96" high
pity of Doors: 1
ion: Rear of Unit / Zone 5 (Worst Case)
red Design Pressure (Zone 5): +51.1/ -68.2 PSF Worst Case
to be installed shall be equal to, or exceed the required design pressures as listed
All installations shall be in accordance with FBC 2017 and manufacturer's
ttion instructions.
Door: PGT Sliding Glass Door 2500 (Non -Impact)
NOA# 18-0207.05 (+65 /-73.8PSF)
Existing Shutters to remain as Impact Protection.
you for your attention to this matter.