HomeMy WebLinkAboutEVALUATION REPORTSCANNED BY DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES SECTION: 0616 00—SHEATHING DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION SECTION: 07 2S 00—WATER-RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: 07 27 00—AIR.BARRIERS REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 EVALUATION SUBJECT: ZIP SYSTEM® WALL SHEATHING 1CC IN 1CC PMG USTED Look for the trusted marks of Conformity! "2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPQ Award in Excellence" i A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not °"�ibd specifically addressed, -nor are they to be construed as an endorsement of the subject of the report or a recommendation for. its use. There is no warranty by ICC Evaluation Service, LLC,. expressP or implied, as to any finding or other matter in this report, or as to any product covered by the report. conmaG Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. !b IMES Evaluation Report www.icc-es.ora 1 (800) 423-6687 1 (562) 699-0543 DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES Section: 06 16 00--Sheathing DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 25 00—Water-resistive BarrierslWeather Barriers Section: 07 27 00—Air Barriers REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 (800)933-9220 www.huberwood.com EVALUATION SUBJECT: ZIP SYSTEM" WALL SHEATHING 1.0 EVALUATION SCOPE Compliance with the following codes: is 2015, 2012 and 2009 International Building Code® (IBC) a 2015, 2012 and 2009 International Residential Code® (IRC) ■ 2015, 2012 and 2009 International Energy Conseniation Code® (IECC) Properties evaluated: x Weather resistance 18 Air leakage 2.0 USES ZIP System® Wall Sheathing panels are used as combination wall sheathing, air barrier, and water -resistive barrier. This report recognizes the use of ZIP System® Sheathing, when installed with ZIP SystemTM flexible flashing seam tape, in walls of Type V construction (IBC) and dwellings under the IRC, and as an alternate to the water -resistive barrier required in Chapter 14 of the IBC and Chapter 7 of the IRC, and to the air barrier required by Sections R402.4 and C402.5.1 of the 2015 IECC (Sections R402.4 and C402.4.1 of the 2012 IECC; Sections 402.4.1 and 502.4.3 of the 2009 IECC). ESR-1474 Reissued October 2016 This report is subject to renewal October 2018. A Subsidiary of the International Code Council® 3.0 DESCRIPTION 3.1 Sheathing Panel: The ZIP System® Wall Sheathing panel is an OSB wood structural panel having a laminated exterior facer_ The Exposure 1 OSB complies with US DOC PS 2 for wood structural panels. The exterior facer is a medium -density, phenolic -impregnated, polymer -modified sheet material qualifying as a Grade D water -resistive barrier (required by Section 2510.6 of the 2012 and 2009 IBC). The panels are nominally 4 feet wide by 8, 9, 10, 11 or 12 feet long and have a square -finished -edge or machined -edge profile. When tested in accordance with ASTM E96 (water method), the polymer -modified sheet overlay has a minimum vapor permeance of 12 perms [68.6 X 10.11 kg/(Pa-s-m2)]. Equivalent Water Vapor Transmission rate (WVT) of the polymer -modified sheet overlay is 83.4 g/(24h-m2) when tested at 73.4°F (23°C). The water -resistive barrier and air barrier properties of the ZIP Systeme Wall Sheathing Panels are not affected when the panels are manufactured to comply as facing materials for SIPS in accordance with Section R610.3.2 and Table R610.3.2 of the 2015 IRC (Section R613.3.2 and Table R613.3.2 of the 2012 and 2009 IRC). 3.2 Seam Tape: The ZIP SystemTM seam tape is a self -adhering membrane tape consisting of acrylic adhesive laminated to a polyolefin backing. The tape is 0.012 inch (0.30 mm) thick with a minimum width of 3 /a inches (95.2 mm), and comes in rolls of various lengths. 4.0 INSTALLATION 4.1 General: Installation of ZIP System® Wall Sheathing panels must comply with the applicable code, this report and the manufacturer's published installation instructions. The manufacturer's published installation instructions must be available at the jobsite during installation. 4.2 Application: 4.2.1 General: The ZIP System Wall Sheathing panels must be attached to wall framing in accordance with the applicable code for wood structural panels, and in compliance with their panel span rating. The panels must be installed with the polymer -modified sheet overlay facing the exterior. In accordance with the manufacturer's published installation instructions, it is recommended that the square edges of the panels be installed with a gap ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specfcally addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendatton for its use There is no xarranry by [CC Evoluouon Service, LX express or implied, as to any finding or other matter in this report, or as io any product covered by the report. ®� �— Copyright 0 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 6 ESR-1474 I Most Widely Accepted and Trusted Page 2 of 6 between adjacent panels and between panels and dissimilar materials. All ZIP System° Wall Sheathing panel seams must be sufficiently sealed with ZIP System seam tape. All overlay surfaces must be dry and free of sawdust and dirt prior to application of the ZIP System seam tape. The ZIP SystemTM seam tape must extend a minimum of 1 inch (25.4 mm) past the panel edge T-joint intersections and must be centered within 1/2 inch (117 mm) over the middle of panel seams. The tape must be pressed firmly to adhere to the surfaces and seal the seams. Wrinkles in the ZIP SystemT" seam tape are acceptable unless they create a leak path to the panel seam. 4.2.2 Flashing: Flashing complying with the applicable code must be installed at the perimeter of door and window assemblies, penetrations and terminations of exterior wall assemblies, exterior wall intersections with roofs, chimneys, porches, decks, balconies, and similar projections, and at built-in gutters and similar locations where moisture could enter the wall. An adhesive -backed flashing tape recognized in a current ICC-ES evaluation report must be installed to seal all ZIP System Wall Sheathing flashing joints. Penetration items must be sealed to the panels. The adhesive -backed flashing tape must comply with the ICC-ES Acceptance Criteria for Flexible Flashing Materials (AC148) and must be installed in accordance with the manufacturer's published installation instructions. See Figures 1 through 7 of this report for typical flashing, water -resistive barrier and air barrier assembly installation details. 4.2.3 Air Barrier Assembly: ZIP System Wall Sheathing fastened to maximum 24-inch-on-center (610 mm), wood wall framing, using minimum 6d nails spaced at 6 inches (152 mm) around panel edges and at 12 inches (305 mm) in the field, leaving a 1/8-inch (3.18 mm) gap between panels, forms an air barrier assembly when the gaps between panels and the perimeter of penetrations are sealed with ZIP SystemTM seam tape as required by Section 4.2.1. The assembly has demonstrated a maximum air leakage of 0.0072 cfm/fe (0.037 U(s•m2)1 infiltration and 0.0023 cfm/ft2 (0.012 U(s•m)] exfiltration at a pressure differential of 1.57 psf (75 Pa) when tested in accordance with ASTM E2357. 5.0 CONDITIONS OF USE The ZIP System Wall Sheathing panel and tape system described in this report complies with, or is a suitable alternative to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 This evaluation reoort and the manufacturer's published installation instructions, when required by the code official, must be submitted at the time of permit application. 5.2 The ZIP System® Wall Sheathing panels must be manufactured, identified and installed in accordance with this report and the manufacturer's published installation instructions. In the event of a conflict between the instructions and this report, this report must govern. 5.3 The ZIP System® Wall Sheathing panels must be covered with a code -complying exterior wall covering, or one that is recognized in a current ICC-ES evaluation report. 5.4 The OSS sheathing must comply with US DOC PS-2. 5.5 Fire -resistance -rated construction is outside the scope of this report. 6.0 EVIDENCE SUBMITTED 6.1 Data in accordance with the ICC-ES Acceptance Criteria for Water -resistive Membranes Factory - bonded to Wood -based Structural Sheathing, Used as Water -resistive Barriers (AC310), dated May 2008 (editorially revised August 2015). 6.2 Air leakage data in accordance with ASTM E2357. 7.0 IDENTIFICATION Each ZIP System Wall Sheathing panel described in this report must bear a label that includes the manufacturer's name (Huber Engineered Woods LLC), the product name, nominal panel thickness, the evaluation report number (ESR-1474), and the words "Mill 229, Crystal Hill, Virginia"; "Mill 228, Easton, Maine"; "Mill 227, Commerce, Georgia"; or 'Mill 290, Broken Bow, Oklahoma." The OSB sheathing must also bear a label demonstrating compliance with US DOC PS 2 from an approved inspection agency. The ZIP SystemT'" seam tape roll must be labeled with the ZIP System logo and the evaluation report number ESR-1474 (see Figure 8). i GVTEM T=E lCH-PRES9M P0.YLVEMANE FM CR NI}T)pW SLL GWIKIMC- RECCY11 MED tl ff BY FLuiii>!G RWCH F.0 WG SILL SECTION HEADER SECTION FIGURE 1-TYPICAL CROSS SECTIONS OF FLANGED WINDOW i ESR-1474 I Most Widely Accepted and Trusted Page 4 of 6 SILL SECTION HEADER SECTION WINGCW JAMB Zip SYSTEM' LIP%E,--'.E-BACKED WALL SHEATHINNG NG TAPE ou TSIDE CAUL (INO RCUCH CPEIING !HS)pE LOW-FRE55UP_c POUN' THr'NE FOAM JAMB SECTION FIGURE 2—TYPICAL CROSS SECTIONS & INSTALLED BRICK MOLD WINDOW ESR-1474 I Most Widely Accepted and Trusted Page 5 of 6 ZIP SYSTEM TM WALL SHEATHING WALL FRAMING - ADHESIVE -BACKED FLASHING TAPE -METAL'FLASHING FLASHING FASTENER ADHESIVE -BACKED FLASHING TAPE j� ROOF UNDER LAYMENT (FELT) / ROOF SHEATHING ROOF JOIST FIGURE 3—ROOF-WALL INTERSECTION (OPTION 1) LLL iFY1IC --- Mliff[,a�•M to =T tIJ01 C9MV.a0 �•` mCRtt IIIdG WZ YD VCR'��d��YTi9�Zt •.•.-,\ \` - _=.,_.MNZC`�[ ` ¶ - P1;Jr71 • .. • , 1 IRA mac•-^t+�rsq —_ f ^�,...fi:: �. i� I• •)f' � 'jT•` �. `.'`^�'.T"ci '�_ • _ .` owl FIGURE 5—TYPICAL WALL -SILL INTERSECTION AND FLASHING DETAILS FOR BRICK SIDING ZIP SYSTEM' '' WALL SHEATHING WALL FRAMNG ADHESIVE -BACKED FLASHING TAPE FLASHING FASTENER COUNTER FLASHING BASE FLASHING FLASHING FASTENER ` ADHESIVE -BACKED FLASHING TAPE (/ ROOF UNDERLAY. NT (FELT) ROOF SHEATHING ROOF JOIST FIGURE 4—ROOF-WALL INTERSECTION (OPTION 2) FIGURE S—TYPICAL WALL -SILL INTERS2CTION AND FLASHING DETAILS FOR LAPPED SIDING ESR-1474 I Most Widely Accepted and Trusted Page 6 of 6 Adhesive -Backed Flashing Tape FIGURE 7—INSTALLATION AT PENETRATION OPENING (NON -FIRE -RESISTANCE RATED) FIGURE 8—LABELING FOR THE ZIP SYSTEM SEAM TAPE ROLL IMES Evaluation Report ESR-1474 FEC Supplement Reissued October 2016 This report is subject to renewal October 2018. www.icc-es.orct 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council' DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES Section: 06 16 00-Sheathing DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 25 00—Water-Resistive BarriersM/eather Barriers Section: 07 27 00—Air Barriers REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 (800) 933-9220 www.huberwood.com EVALUATION SUBJECT: ZIP SYSTEM' WALL SHEATHING 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that ZIP System® Wail Sheathing panels, recognized in ICC-ES master evaluation report ESR-1474, have also been evaluated for compliance with the codes noted below. Applicable code editions: ® 2014 Florida Building Code —Building ® 2014 Florida Building Code —Residential 2.0 CONCLUSIONS The ZIP System Wail Sheathing panels, described in Sections 2.0 through 7.0 of the master evaluation report ESR-1474, comply with the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential, provided the design and installation are in accordance with the International Building Code® provisions noted in the master report. Use of the ZIP System° Wall Sheathing panels for compliance with the High -Velocity Hurricane Zone provisions of the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential has not been evaluated, and is outside the scope of this evaluation report. For products falling under Florida Rule 9N-3, verification that the report holder's quality -assurance program is audited by a quality -assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official, when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, reissued October 2016. ICC-ES Evaluation Reports are nor to he construed as representing aesthetics or any other artrtbuies not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendanon jbr its me, There is no a arranty by ICC Evaluation Service, LLC, esprrsr or Implied as to any finding or other matter in this report, or as to any product covered by the report. Copyright® 20161CC Evaluation Service, LLC. All rights reserved. Page 1 of 7 ICC-ES Environmental Report VAR-1012 Reissued September 2015 This report is subject to renewal September 2017. www.icc-es.org/ep 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council' DIVISION: 06 00 00--WOOD, PLASTICS AND COMPOSITES Section: 06 12 00—Structural Panels Section: 06 16 00—Sheathing DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 21 00—Thermal Insulation Section: 07 25 00—Water-Resistive Barriers/Weather Barriers Section: 07 27 00—Air Barriers REPORT HOLDER: HUBER ENGINEERED WOODS, LLC 10925 DAVID TAYLOR DRIVE CHARLOTTE, NORTH CAROLINA 28262 (800)933-9220 www.huberwood.com EVALUATION SUBJECT: ADVANTECHO (AT -SERIES) SHEATHING SPAN; ADVANTECH" (AT -SERIES) FLOOR SPAN; ZIP SYSTEM" ROOF SHEATHING; ZIP SYSTEMO WALL SHEATHING; ZIP SYSTEM" RSHEATHING (INSULATING SHEATHING) 1.0 EVALUATION SCOPE Compliance with the following evaluation criteria: • ICC-ES Environmental Criteria for Determination of Bio- based Material Content (EC102), dated March 2012. • ICC-ES Evaluation Guideline for Determination of Source of Recovery, Extraction, Harvest and Manufacture for Materials or Products (EC114), dated March 2012 • ICC-ES Environmental Criteria for Determination of Formaldehyde Emissions of Composite Wood and Engineered Wood Products (EC108), dated March 2012. • ICC-ES Environmental Criteria for Determination of Certified Wood and Certified Wood Content in Products (EC109), dated March 2012. Compliance eligibility with the applicable sections of the following green building rating systems, standards and codes: • 2012 International Green Construction Code (IgCC) (see Table 2 for details) • 2013 Califomia Green Building Standards Code (CALGreen), Title 24, Part 11 (see Table 3 for details) • National Green Building Standard (ICC 700-2008) (see Table 4 for details) • National Green Building Standard (ICC 700-2012) (see Table 5 for details) • LEED for Homes 2008 (see Table 6 for details) • LEED v4 for Homes Design and Construction (see Table 7 for details) • LEED 2009 for New Construction and Major Renovations (see Table 8 for details) LEED 2009 for Schools New Construction and Major Renovations (see Table 9 for details) • LEED v4 for Building Design and Construction (BD+C) (See Table 10 for details) • ANSI/GBI 01-2010 — Green Building Assessment Protocol for Commercial Buildings (see Table 11 for details) 2.0 USES AdvanTechO (AT -Series) Sheathing Span, AdvanTechO (AT -Series) Floor Span, ZIP System Roof Sheathing and ZIP System" Wall Sheathing are used for a variety of interior and exterior framing and sheathing applications. ZIP System" R-Sheathing panels are used as combination wall sheathing and continuous insulation in conventional wood -framed wall construction. 3.0 DESCRIPTION AdvanTecho (AT -Series) Sheathing Span and AdvanTech"� (AT -Series) Floor Span wood structural panels are Exposure 1 oriented strand board (OSS) panels manufactured with strands from a single wood species or a combination of wood species blended with an exterior -type adhesive system to comply with U.S. DOC PS-2 and the applicable ICC-ES report as indicated in Table 1. ZIP Systemo Roof Sheathing and ZIP Systemo Wall Sheathing wood structural panels are OSB panels with laminated, resin -impregnated, polymer -modified sheet material manufactured to comply with U.S. DOC PS-2 and the applicable ICC-ES reports as indicated in Table 1. The panels are installed with ZIP System" self -adhering membrane tape. The tape is outside the scope of this evaluation report. ZIP Systemo R-Sheathing is an insulated sheathing made by combining 71le-inch-thick ZIP System® Wall ICC-ES Yerificerion of Attributes Reports an; issued under the ICOES 'JAR Environmental Program. These reports arc not to be construed as representing aesthetics or any other attributes not specifically addressed, nor arc they to be construed as an endorsement of the subject of the mpurt or a mcommendation for its use There is no uarronly by [CC Eivinarlon Service, LLC, express or implied. as to any finding ur other matter in this report, or as to any product covered by the report. Copyright,9 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 6 VAR-1012 I Most Widely Accepted and Trusted Page 2 of 6 Sheathing as described in ESR-1474 with a layer of maximum 1-inch-thick (25.4 mm) rigid foam plastic insulation laminated to the interior face with PVA adhesive. Refer to ESR-3373 for additional product description. 4.0 CONDITIONS 4.1 Code Compliance: AdvanTech® (AT -Series) Sheathin% Span, AdvanTech° (AT -Series) Floor Span, ZIP System Roof Sheathing, ZIP Systemo Wall Sheathing and ZIP System R-Sheathing have been evaluated for compliance with the requirements of the international Codes as listed in Table 1 of this report. 4.2 Green Rating Systems, Standards and Code Eligibility: The information presented in Tables 2 through 11 of this report provides a matrix of areas of evaluation and corresponding limitations and/or additional project -specific requirements, and offer benefit to individuals who are assessing eligibility for credits or points. 5.2 ICC-ES EC114. [Evaluation applies to IgCC Section 505.2.5; CALGreen Section A5.405.1; ICC 700-2008 Section 608.1; ICC 700-2012 Sections 609.1, 11.609.1 & 12.1(A).609.1; LEED Homes MR 2.2(c); LEED v4 Homes MRc3; LEED NC MR 5; LEED Schools MR 5; LEED v4 BD+C MRc3; ANSI/GBI 01- 2010 Section 10.1.4.1]. 5.3 ICC-ES EC108 [Evaluation applies to IgCC Section 806.1; ICC 700-2008 Section 901.4(6); ICC 700-2012 Sections 901.4(6) & 11.901.4(6); LEED NC EQ 4.4; LEED Schools EQ 4.4; LEED v4 BD+C EQc2]. 5.4 ICC-ES EC109 [Evaluation applies to ICC 700-2008 Section 606.2; ICC 700-2012 Sections 606.2(2), 11.606.2(2) & 12.1(A).606.2; ANSI/GBI 01-2010 Section 10.3.2.1]. 5.5 The final interpretation of the specific requirements of the 5.6 respective green building rating system, standard and/or code rests with the developer of that specific rating system or standard or the Authority Having Jurisdiction, as applicable. Compliance with items noted as "Verified Attribute" is subject to any conditions noted in the tables. Decisions on compliance with those items noted as "Eligible for Points" in Tables 2 through 11 rests with the user of this report, and those items are subject to the conditions noted. The user is advised of the project -specific provisions that may be contingent upon meeting specific conditions, and the verification of those conditions is outside the scope of this report. Rating systems. or standards often provide supplemental information as guidance. 5.0 BASIS OF EVALUATION The information in this report, including the "Verified Attribute," is based upon the following supporting documentation: 5.1 ICC-ES EC102 [Evaluation applies to IgCC Section 505.2.4; CALGreen Sections A4.405.4 & A5.405.2; ICC 700-2008 Section 606.1(2); ICC 700-2012 Sections 606.1, 11.606.1 & 12.1(A).606.1; ANSI/GBI 01-2010 Section 10.1.2.2j. Documentation establishing and documenting all major sources of primary manufacturing energy [Evaluation applies to ICC 700-2008 Section 606.3; ICC 700-2012 Sections 606.3 & 11.606.31. ICC-ES ESR-1474 documenting that ZIP System Wall Sheathing is equivalent to a code -prescribed water - resistive barrier [Evaluation applies to CALGreen Section 5.407.1; ICC 700-2008 Section 602.9; ICC 700-2012 Section 602,1.8]. 5.7 Refer to ICC-ES ESR-1474 for evaluation of the ZIP System Wall Sheathing as an air barrier assembly (Evaluation applies to IgCC Section 605.1.2.1.1; ICC 700-2008 Section 703.2.1; ICC 700-2012 Sections 701.4.3.2, 11.701.4.3.2 & 12.1.701.4.3.1; LEED Homes EA 3; LEED v4 Homes EAc7]. 6.0 IDENTIFICATION AdvanTech® (AT -Series) Sheathing Span, AdvanTech$ (AT -Series) Floor Span, ZIP System Roof Sheathing, ZIP Systeme Wall Sheathing and ZIP System° R-Sheathing products are identified with a stamp noting the manufacturer's name (Huber Engineered Woods, LLC) and address, the product name the manufacturing location, the ICC-ES evaluation report number (if applicable), and the name or logo of the inspection or grading agency. The report subjects are also identified on the product and/or packaging with the VAR Environmental Report number (VAR-1012) and the ICC-ES SAVE Mark, as applicable. TABLE 1—REFERENCE STANDARD OR EVALUATION REPORT NUMBER FOR HUBER ENGINEERED WOODS LLC PRODUCTS PRODUCT REPORT NUMBER/ REFERENCE STANDARD AdvanTech" (AT -Series) Sheathing Span AdvanTech® (AT -Series) Floor Span ESR-1785 ZIP System° Roof Sheathing ESR-1473 & ESR-2227 ZIP Systems Wall Sheathing ESR-1474 & ESR-2227 ZIP System" R-Sheathing E R- 373 VAR-1012 I Most Widely Accepted and Trusted Page 3 of 6 TAo1 oe n tuonnr_u .. Scetlon lnlanl Candftlo—Alex Ea Qualify AdyanToeh Advon7rrJr ZIPSystrm Rmf LPSyekm wan -S Systrm Number! Pdntr st whing Ftecring AShemhing Sh"thin0 Shratlling TABLE 2—SUMMARY OF AREAS OF ELEG1131UTY WITH 2O12 INTERNATIONAL GREEN CONSTRUCTION CODE Su`52a Mt:s pcCas WA A! Huber •' o d pica-: are Gua::fid as b-b Med � • • • • Os Piod: shall be rewrerd, t—bates. vvaad d u-uraduw r tbn 3 6M mi '�Fw (wo bn) rad oa of tie bog'g sae Wher_ orry a pavan at a mate,.f cr pM•Jd v —red, tod add S.^an ft : d we500 R3a IBM '—L any 505.25 IrC15er y. atdas fJA that pcA:ee:ra':ler'ndudM.VAmrerw:rmafe :nnaput-d by raferura;?e O O O O to tie WYAirg s4e stall or deae by mu•apysg the'' that me ::°frw � —Uro Cy 0 raov:m are trarapMee by �;va!u v ms ty 025 S add.rq'rat m:rroer!a the r!a ditama tramported oy meanmi other tmm waterer rar 6C5.1.21.1 Ak Wr„•r rslaaadon NIA Instaa the system 1—ordana nfthe mamafadurera 3Y.al�a:kn'rstnu3a•a IMES !vaN.aticn reWn_eft-14TA I'-.S „"'! yrr rye. e • SC6./ F—&-hide emmwre N!A C xccd sWninl panes cempj w!'t US 70C PS 2 (Sea Take 1 of Na report aM ar- exempt from kmat'ehyee em ;ms test V • • • • 01 TABLE 3—SUMMARY OF AREAS OF ELEGIBILITY WITH 2O13 CALIFORNIA GREEN BUILDING STANDARDS CODE ASA C4 I R Ven1y boa! pM = Nat are atndd, P— and ra wured wahm E:edve Cafddrttia v SOC Riles I 8C5 kr.:1 of are rob aaa O O C OA4,40 '5 AS 2 B's�aed. atenap M �!:rxr —d FrxLoM m ,w!Pe: ie laaoa..q. • • t • Os A4 4CS 4(3) M 4CS.d(5) R--Ve eplfl`3 Maler`.a4from r ri—role aOurG>•J ;s--dt a erginered'—A). • • • • Os AS, 40521 Ce• l..d'Nccd urdr. l—by Cab!Omu Bvdug Stardar--7 Commmkns WA VA A!A WA WA SdCi1 walff—wtarlt eltd..-3] ,rtiy fkrdatary Haler pod.da;—ldea K.{tf-tC..-"-,atl were- —1 erv62pe ���<:��++ 1"J.r e...z L", 1 1 _.3� O O a Su.s Canpesae •-M prcdud endu:am eh- Prods: do rot appy le:he—P de wood tdn' i` 7. T -1 -Y T -'r l4 e A•F;: y' n °'r. S.SG45 pad-•.W M TABLE 4—SUMMARY OF AREAS OF ELEGIBILITY WITH THE NATIONAL GREEN BUILDING STANDARD (ICC 700.2008) 6C2.9 K'ater+essdra barter Mandatory !tav7 a »au-reeaaveblrt!er wdlcr drainage pan system 60t r.d ester., veneer - _ anUor rq • • Tws types of dceaaed mezrias ate md, each for To eam 6 pdkua pnadLcta meat be al!1ad 1%of IHa zm.dnxsn malda! =t AN' iM 1(2) more :tan 1% of the projecro prejedd Mike p 6 another ao-bsed product at iKef eattra! cost Mn ee used 1 or 3 Palntr are • • • • 01 materalmst "Mile!. for greater it., 0.5%. 6C6 2(i) Twd "Zew woM-wsd pad- are Lug for rr.;rer ekmenta of the R3drg, such as a3 wa:s 3 To oam 3 peln's a —rd .-e, -d—oo psdcd m�R aia :e csed as ami ne Odra IX(epf Climenll • • ■ • 01 Twe xMd-w.basd prw, r= are :-Jd for To 4 606 212) maar e—ta of are n Fd'N such a1 al walls, 4 cam pbattr a SezM x�uftd wCd pMud mitt sip be sd 3s a .^ejcr corns p rxf e!enlertt' ■ ■ • • 01 Matera'a ale mad !u majcrcompcnerta et the buildirg that are manufad-d usirg a mn:mum at &76 3 33%of pe—q—.'ladunrg pats enter 2 tadi To earn 6 poims the poduda mt,-t be and lot at;east 3 map cvnper..vts d the dervd win rcnewatle aeurr=s, mstx��cre mste 4 mas wzvf. s. 2 PNy may be ear, ed w ... atd for tall, ma ar Y 1 xrnprr:ert. D • • • O 1 xum, a renew.:. —'gy meGr9 • • Wfirrd aV bL" _. • TN' -- i- n does not apply to Nb pM <t Note Foct•ctn are bend after Tab'a 11 VAR•1012 ( Most Widely Accepted and Trusted Pape 4 of 6 TART PS 7 TLiR191 IMW 44 f(^nnafnr m.J1 S.W. Pnalblo AQv-T- Advan— LP Spin. AP SyaYm ZIPS :ern Numhar S¢tldn Imam Pdnla Ccndidene of L`ed to OUWify Shunning Floating Roof Watt pShoadting Slmthln9 6haathtnp TABLE 4-SUMMARY OF AREAS OF ELEGIBILITY WITH THE NATIONAL GREEN BUILDING STANDARD (ICC 70D-2008) (Continued) 60A 1 maMdaH 2, am . earn 2 jot b — raax5 boar pare acplratea, produ row , gnot:unary c1 -dgerb t0 erarr natu2 •corn 560 mi1e4 805 lo, of on tifnt O O O I.Iii; cn and ar seaCrq a Ir=S mci axldanca wnh as the, ldbwlrq, as `. r'4" "_.'. ° ^'. ^. - - ...• - - •.•_ - •- 703 2t rre_ afion aM ak xallrq 3 '"�a� - I I 5 max 0) trot-pany vent!dt:m ptAamd is {a. !2)rcN.d-ta+ly verfica"sa+peAcrr�]:� - Sbustxa1 p1r cod used Mr Ater, wart arlUer real- eheathN ¢mpaea •Mh 00C PS 1 arur a DOC PS - 2 088 used Mr Amr, •-aWL .=Or reef eheenr1ng so14(t) mmpiin wth COC PS 2 Pane%are made wnh 11"amry Tan the; a —Mm of 85% d CSS cr ptyemd �n Inc culid •m caner of • • • • RaG1L't6r6ieWd adhcaN. and Iha t:a^_tmaak Huber corium ■ id,cates th0 oahesNd are Exp we 1 cc &tenor IrA—d) ad Eaposura t (OS81 go, 416) —odfrar6rg prdLcb. wrlct an Irb.�:Ce S:radarJl wced i A maurtian of 65% of prdlxl In 01e bulk' aV are CrnL'fiod Hubc prdces. • • • • •s TABLE S—SUMMARY OF AREAS OF EL£GIBILITY WITH THE NATIONAL GREEN BUILDING STANDARD (ICC 700-2012) - 6021d Walu-rtsstive bamtr N]rGlxf 1r m.1.—ter-resctve gamer artUR Nanapt pan ayvem bchrd arener veneer -...--.•_ _ _.-._ -„ ..-. _ .. aMJcr aiding._._ j • • Mo.1(2) Two .ypm of bicbesed =lest s are ud, each for To gam 6 pomm prdrx� mr_st be at least 1%el the srtstnaabn maldal cat M 11 6cis l(b) m m Tan 1%cl!he pr.>)ec[S Rc)eyM biL'irq 6 another liobaced pmdaq at ;%c1 marhi cost mtct Wend. 1 or 3 PcirxS ara • • • • Os 121U).6®1 —!ar!alxct ava9atle far reaterbnan0.5A 6C8 20) mwe a Pd wad -bald Rc, i we 1-d for To earn 3 p .h a s_�ccrd cadl d —A Rcdua n w also be usd as amino, I 11.6XI 20) ilwr eiprlwna of Tire bcidrg, wort aoal brm 3 t'�rtrt: • • • • 01 121 A1,6M I aline or rttia k fi66 2(2) are BA 7e1 vqd-0asd Rgr To W m 4 pchlts a Se—d z•R.Te•9 vrad prod-C m:C• a:te be Lsd as a mac, tt ru«salad -x cement of the RW�ng, cJCh as ad'wa9a, a • ■ • • Oa 12S A 606 2 IAI 6061 .".ecn w rtdi msrt;t .V a:enah are tad Mr major exngrera of tr 6C83 blik ng are .mafbfaeLTe4 u,:rg am r,:— of 33% of tntgy demd 2 earf: it tan 6 PeirS bte Fvodcm,ms: to wd fcr al:wst 7,ra,u ¢mperemx alms 11 fitd 3 primary:rsanu!aouriy Rocca from rplewatla mhrfLa, cot-bLLeeda waste 6— ailig. 2 pw1� may to eamd •xrxn �s.ed fv eaT ma;ar anpoeen: • • ■ • Os sourer, or re —Nd energy aC:b Td earn 2 pi fts vedN nuttnal is padwed. grows naturaNy, w ccalra nM..gy wan;n SCo MAes(605'sml of lhe)db sire T trarorZnd by tt—k or 1xO mlos(2414 , 6C9.1 Reg 1 matda:s 2 each Im) t •rarspnnd far al kart 30%of n,, Mtal dSarco b/ ralf crwaMr P.•odwls W 10 ma ara aslemGC! dr Redurad from muit:pla r— mooltale qua ify 1 the v cigmd O O O --;e (Of —;214 ar vaMmeJ of fnt d'=— bd roar ma:grab bout be_n It—. xnd men the di: — trtelia ' To1.J 32 ifAlna:blh ir. at, —,I g is1tye1Em. asrdarca'I.`Jh V. the fdbw�'fg, as �.,.�'-..- �' � �. •• . "� ••,_-�..,-___ t 1.7014.32 ireulaLcn ]rd a'a srai'rq 3 appfl,. I C O 12 t 7C1.J 3,1 15 mza IIS tRrd-)ao1Y venAaaar perforated Fts, 121 rli UIZM-card venfloaCen poll—ol 3 Rt Stvdunl plywd lined Mr Aeon. wa11, atWor roof sne-nrrd rg wp7e »tm CCC PS 1 ara CCC PS 901.4{7) 2 OSB 4•ed Mr Hoer, wart anBot roc/ sl:eat71!rg i o men Ul'9 a m;n;mum of dS% cI OE3 a yywxA In tha G.sd'+1g gust xnaist of 11 301.4(t) am)ii, wab DOC PS 2. Panels are made v.+t s1a.•datcry HLber • • • O O 12.7901 Ail) mc'slro-rtaixar..aEn.4d Sd+e imdemark pcdu . "al- s Lne adhesives am Eaisewe I or Eaferor Idyw.d) S Eapa:✓a 1 (088) 90,40) 7:en-emitirp Rodr:Cs, wtidh 6i UfCLdt s41•CLrai t ] Rdq Ir i! ;; a Cu'a`.^.g are Te ArniF..M HetaR d,=, • 0s150t.4(6 �-'M'5 pa ahaort ts .. 1 = Tnb pravtdbn dtq net aepN to this pra'�et Note Footwes are looted after Tabs 11 VAR-1012 I Most Widely Accepted and Trusted Page 6 of 6 Tea) ;:A 7 TURnI IrW 11 yr-fi- ml Sae.n Poeelo)e Adv-Teeet Adean— LPQW bm 2)P wyetem LP SYefnm Sartbn Intent Pdnb Cand'dlons of lure trr GuaMy for Pelnb Simathirtq Fk-g l I RSheathing .Number ShRoofl g Sheadiing TABLE 8-SUMMARY OF AREAS OF ELEGIBILITY WITH USGSC'S LEED FOR HOMES 2008 6A7 Nr:n:Juan 7max To eam2cr7po:.:s meet me air leakage requ'de.menb eMxn -.+? O O In Tatie 17 of ine ved3 -a aNe. MR 21 FSC me.led Topol-4 0 5 nett To eam 0.5 mmpwam - Fsc c gi&d tropical •koor} ] 1 ] d 8ma pam per Emianr.•.enL !,y pefe2Ne Fmdu¢v .'u rz!. wail 8 0 5 each ed;valtu: To "Ip�i- ma prwu Umt are exnaed, pro-med and —1-red MR22(4 fCgte, terkrd exte^e! bemngd l-w'g 0max '.A0 rrules(805 Win) of r .. !a amfq um of 90%(by -.Igm cr.I-eof me C mmcoreM.' TABLE 7-SUMMARY OF AREAS OF ELEGIBILITY WITH USGBC'S LEED V4 HOMES EAC7 Nr M6tz:on To eam 1 a 2 pofiro bamd on air leakage <n de!-r of 2y leeerq ano O vsr'fKaf:ort MR FSC -0--d npi.1A Prereq-A. A?. rwoC x rortropctl cr certifM r FSC a l:SGBGapproved equrva:entt ] 2 ] . f Qpeon ' a eam po+ma ue ry lnal al! — a... pomseed a rar a rec - _ w.N'n 1CO rr ea (150 icm) al the srte for a m)nanum of S:!S (try Meigl:l orvdume) o! O O- MRe7 Emkwn nhl)Y prefemde padude br rod, wail d 0.5 each r x • kdeil r d ex•.erior fmmktg d eheatNrg f , 8max Opea12: Use A padueb cefaEed by FSC a t)SGBC-ap r-m equivalent.] 2 2 2 2 O] EO� Lax emelrtg materab t i o eam 1 po W use uood mmpmde pcdues me- ,d madded wea- • • ■ I • •s , dam r:r� TABLE e-SUMNIARY OF AREAS OF ELEGIBILITY WITH USGSC'S LEED 2009 FOR NEW CONSTRUCTION AND MAJOR RENOVATION MR 5.1 Regia®fmaterub (',O%of ¢ment) I Tc e-.. I Feint 1ne produce that are eanew, procaaed and m'aruhaaed rritni 5g0 mi!es;805 km) d the eee for a"i"rr met 1C%(by -I)dlaal. !dais .1ue. To earn 2 pc:Ma _ae a minimum of 2D%! O O O O MR 5 2 Regarat fralenae f20%of mmrnt) 2 O O O C -% MR 7 Ce O ..w I To eam 1 pam L a mMm4m -,% (boned on -1) a! V X16oasm 2 2 2 2 7 mate'abin¢ues="m to FSCf uoemara2 E04.4 Low em"-teC b 1 'cr eam 1 Pam use wood -P.4e -w podu¢s eortain'mg 'deed rn. • • • • Os fcmuidehyda rnkc. TABLE 9L-SUMMARY OF AREAS OF ELEGIBILITY WITH USGBC'S LEED 2009 FOR SCHOOLS NEW CONSTRUCTION AND MAJOR RENOVATION MR 51 I10%d mrlent) 1 To nm 1 poktuserrowocm Lw are e--seed,p--d am mvva=ed•M!: SM !mice (805 ja j of the s1a for a car;—. of 1C:i (try metl of ldsl materiis W. To nm 2 pc:nb use a m.Mmum of 2:%' O O C MR52 Regina1 meer.%(20%cl mmem) 2 w .2_ . - MR 7 Cercdod tl 1 )e eam Pant u]e a jeaeed cn mf) of eased m. rr t 2 ] ] 2 EO 4.4 Te eam 1 pdm use wood m.Tpaee notd xodn =Mahi'ng ;-added urea • • • O Os for-lk h -Lo TABLE 10—SUMMARY OF AREAS OF ELEGIBILITYWITH USGBC'S LEED v4 BUILDING DESIGN AND CONSTRUCTION (BD4C) MRe7 $wtalg of rnv ma:edab-¢NfkatfandneW wxd I O)>:at2-.i)eewoo6basM matenallpmutJcert:flm by FSC aUSGBGacppletl 2 2 02 od nuGs' eeuvai•rd] Prpduea meeCpg T.e rcqurcanenn at MRd Op4on 2 f^aY e r, .NRc7 Sc4fe of )ax mrma)s -deuce lomtdn N WA aedil hased pt sou: ce'orahcn eI md'an, anuheuro ]af r a+el ant) taxed e e s ST 'n an leat'on re'at."re to -ee Adel 4:i2 c -. lECc22 Lax emnng mataAr.4 WA E'A?andw.be: pcdue2 do r4l appy to the¢mxeee-W posuadeG:ibA s, as � N �' 7•.kn. m ,�•p � zt =�gdm-Pama a=Vedf-_d atTbae = Thz prwCsgn donna apply to tnn -dLe Note Focow. s are:-LJ o'er Tale 1'L VAR-1012 1 &lost'Ndely Accepted and Trusted Passe 6 of 6 TART FS 9 TWPnitrl4 1t fCnnflnnait. Sactlan imm�t 7-- Cenaldans d Uso b Ou.lify for Peon • A--och Atr.anTach LP SyaWm Roof ZIP Sysflm Wall ZIP Soto. N am° h Sheathing Fl aarin9 SheathingSMathlnB -Sheathing TABLE 11—SUMMARY OF AREAS OF ELEGIBILITY WITH ANSUGBI 01-2010- GREEN BUILDING ASSESSMENT PROTOCOL FOR COMMERCIAL BUILDINGS 10122 aimaxd produm - w4.r9 aese.^. Cilo 7 — A3 Hut w wad product are q—fied as bctased • • • • OS To earn =wits tse poa':m that arc crrataod. peceased and marttacrea Mfvr ' ` ,,,r 10 1 a.1 Regi«-al vala wo - bubaq aasembl'es S max 5Cv":nAa ib75 7c'f) ot!1:e 9.Se !« a rr7r rv+ or 5:^i lty r.esti u voiu^..e of the o - O o o yP 'iS� , 19321 CM"rd..od 6rt•aR 6_...__.10%am 60%or:Cate.l upo0.Waed produces--d In a:e wm,.gare ttattl purr e,9ed . • • • • Oa 0 =E SIN.brpours • = Ver:'M aatlb.te Trh Ps-alen doe not Z;pty to trig pod= Fxtrrt,w ICml.ton a fegLd"ddthe manutad—any Vendor Chain or CWCdy!enal requlred m quald/f«Ta poi.! 'F..t mn'carbn raedi for LEED 2M re — FSC esHUNc1y and to, LFS0 A:esourwe ether FSC or USG8Carpmed aquWem. Conrad USGEC for a 1,9 of apr—d equivalent program tCGeSCrecr�impc,w.of—C=rrcd!crestpw.da —er Cle,peck rruucnenn are c ryorderaweApneat f�� area c not be —%-d a itn to pmvei«y of 9-0e 0 a a'n LEED (Tacle A) e-aus:he CaVemia Air Re-- Emm (CARS) dos rotre elate erVreerad •tread produd emw aas cVIoUlllf Wf- an.Y to Me N—C baaed sheatn4 9 P.11 l .(!he p.-l. `Reglonai bash on oryeC I..Zi. vw4M by Huoer upon toques;. WA • Net ...able .. w DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES SECTION: 0616 00—SHEATHING DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION SECTION: 07 30 05—ROOFING FELT AND UNDERLAYMENT REPORT HOLDER: HUBER ENGINEERED WOODS' LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 EVALUATION SUBJECT: ZIP SYSTEM® AND ZIP SYSTEM+TM ROOF SHEATHING IN IN ICC cg) � ag� C PMG LISTED Look for the trusted marks of Conformity! '2014 Recipient of Prestigious Western States Seismic Policy Council WSSPC Award in Excellence" °^� l— i i A Subsidiary of CONCOURM ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a implied, or recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, expressP lied, as to anyfinding or other matter in this report, or as to any product covered by the report. acm Copyright © 2015 ICC Evaluation Service, LLC. All rights reserved. IMES Evaluation Report ESR-1473* Reissued September 2015 This report is subject to renewal September 2017. www.1cc-es.orta 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 06 00 00—WOOD, PLASTICS, AND COMPOSITES Section: 06 16 00—Sheathing DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 30 05—Roofing Felt and Underlayment REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 (800)933-9220 www.huberwood.com EVALUATION SUBJECT: ZIP SYSTEM" AND ZIP SYSTEM+TTM ROOF SHEATHING 1.0 EVALUATION SCOPE Compliance with the following codes: 0 2015, 2012 and 2009 International Building Code° (IBC) * 2015, 2012 and 2009 Intemational Residential Code (IRC) * 2013 Abu Dhabi International Building Code (ADIBC)t 'The ADIBC is based on the 2009 18C. 2009 iBC code sections referenced in this report are the same sections in the ADIBC. Properties evaluated: ■ Structural —wind uplift resistance ® Nonclassified roof covering m Classified roof covering a Weather resistance 2.0 USES ZIP System® and ZIP System+T111 are used as combination roof underlayment. 3.0 DESCRIPTION roof sheathing panels sheathing and roof The ZIP Systemo and ZIP System+T" roof Sheathing panels are wood structural panels having a laminated facer. The ZIP System+TM panels are manufactured using a different resin than the Zip System® panels.. The panels are installed with a proprietary seam tape, which allows the systems to be used as an alternate to the underlayment required in Chapter 15 of the IBC and Chapter 9 of the IRC. The OSB substrate complies with U.S. DOC PS-2 for wood structural panels and is overlaid on one side with a medium -density, phenol -impregnated, polymer -modified sheet material. The standard -size panels are nominally 4 feet by 8 feet. Oversize panels, wider than 4 feet (1219 mm) or longer than 8 feet (2438 mm), or both, are also produced. The panels are available with either a square -finished -edge profile a tongue -and -groove edge profile or a machined edge profile. The proprietary seam tape is a self -adhering sheet -type membrane consisting of acrylic adhesive laminated to a polyolefin backing, and the face of the tape is labeled with ESR-1473. The tape is 0.012 inch thick (0.30 mm) with a minimum width of 3 inches (76.2 mm), and comes in rolls of varying length. 4.0 INSTALLATION 4.1 General: Installation of ZIP System® and ZIP System+T'" roof sheathing must comply with the applicable code, this report and the manufacturer's published installation instructions. The installation instructions are to be available at the jobsite at all times during installation. The instructions within this report must govern if there are any conflicts between the manufacturer's published instructions and this report. 4.2 Application: The ZIP System® and ZIP System+TM roof sheathing panels must be installed with the longer dimension perpendicular to the roof framing and fastened to the roof framing in accordance with the applicable code for wood structural panels. The panels must be installed in accordance with the panel span rating as shown on the panels. All corners are to be securely fastened. Tongue - and -groove and machined edge panels are designed to provide the correct gap size at the panel edges during installation. Squared -edged panels must be spaced apart a minimum of '/a inch (3.18 mm) at the time of installation. End joints of adjacent panel runs must be staggered. The panel must be installed with the laminated phenol - impregnated polymer -modified sheet material facing to the exterior. All ZIP System's and ZIP System+T*+ roof sheathing seams must be sealed with the Zip System® tape. All overlay surfaces must be free of any significant presence of debris, particles or sawdust prior to installation of the ZIP System tape. Overlay surfaces must be void of any free water prior to application of the ZIP System® tape. The ZIP System tape edges must be sealed and the tape is to be centered within +/-'/2 inch t12.7 mm) of all panel edge seam centers. All ZIP System and ZIP System+TM 'Revised November 2015 ICC-ES Evaluation Reports are not to be construed as represeming aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement ojihe subject ofthe report or a recommendatlonfor its use. There is no warranty by ICC Evolumion Service, LLC, express or implied, as l/.1 i�h79 to any finding or other matter in this report, or as to any product covered by the report. m� ==-- Copyright m 2015 ]CC Evaluation Service, LLC. All rights reserved. Pago 1 of 2 ESR-1473 I Most WrdetyAccepted and Trusted Page 2 of 2 roof sheathing surface defects, openings, cracks, etc., that completely penetrate the overlay and substrate, and caused by handling or construction work, must be covered with the ZIP Systems tape. The ZIP Systems tape must extend a minimum of 1 inch (25.4 mm) past the panel edge T-joint intersections. The ZIP Systems tape must be adhered to the ZIP System' and ZIP System+TM roof sheathing. Wrinkles in the ZIP System seam tape are acceptable unless they create a leak path to the panel seam. 4.3 Roof Assemblies 4.3.1 Classified Roof Coverings 4.3.1.1 Class A: Underlayment is not required for a minimum 'h-inch thick Zip System+-"' roof sheathing with Class A asphalt glass fiber mat shingles. 4.3.1.2 Class B: Underlayment is not required for a minimum 7/,6-inch thick Zip Systems roof sheathing with Class A asphalt glass fiber mat shingles. 4.3.2 Nonclassified Roof Coverings: The ZIP System° and ZIP System+T'" roof sheathing panels are limited to installation on buildings permitted to have nonclassified roof coverings using code -complying asphalt -fiberglass shingles, metal shingles, metal panels, wood shakes, wood shingles, built-up roofing, slate and slate -type shingles, and clay and concrete tile roof coverings. Roof coverings may be applied directly to the taped ZIP Systems and ZIP System+TM roof panels unless multi -layer underlayments are required, 4.4 Wind Uplift Resistance: Wind uplift design loads and ZIP Systems and ZIP System+TW roof wood structural panel allowable uplift resistance shall be determined in accordance with Sections 1609 and 2304.8.2 of the 2015 IBC or 2304.7.2 of the 2012 and 2009 IBC and Section R301.2.1 of the IRC. Roof coverings must be fastened to the sheathing with mechanical fasteners sufficient to resist the design uplift load. 5.0 CONDITIONS OF USE The ZIP System' and ZIP System+TM roof sheathing panels -.described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 This evaluation report and the manufacturer's published installation instructions, when required by the code official, must be submitted at the time of permit application. 5.2 The ZIP Systems and ZIP System+"" roof sheathing panels must be manufactured, identified and installed in accordance with this report and the manufacturer's published installation instructions. 5.3 The ZIP Systems and ZIP System+TM+ root sheathing panels are limited to code -approved structural use for wood structural panels with either a 24118, 32/16 or 40/20 span rating. 5.4 In jurisdictions enforcing the IBC, the roof covering system incorporating the panels is limited to installations in the following construction types: • Type III-B and Type V-B • Type III -A or Type V-A under the conditions specified in footnote d of IBC Table 601 • Type III -A or Type V-A under the conditions specified in footnote b of IBC Table 601, for occupancies other than Group F-1, H, M and S-1 In jurisdictions enforcing the IRC, the roof covering system incorporating the panels may be installed on structures constructed in accordance with the IRC, 5.5 Enclosed attics and rafter spaces must be ventilated in accordance with the applicable code, except where unvented conditioned attic assemblies are permitted by 2015 and 2012 IRC Section R806.5 or 2009 IRC Section R806.4. 5.6 An ice barrier must be provided as required by Section 1507.2.8.2 of the IBC and Section R905.2.7 of the 2015 IRC and Section R905.2.7.1 of the 2012 and 2009 IRC. 5.7 Installation is limited to roofs having a slope of 2:12 (16.67% slope) or greater. 5.8 ZIP Systems and ZIP System+T'" roof sheathing panels are manufactured by Huber Engineered Woods, LLC, in Crystal Hill, Virginia; Commerce, Georgia; Broken Bow, Oklahoma; and Easton, Maine, under a quality -control program with inspections by ICC-ES. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Wood Structural Panel Roof Sheathing Factory - laminated with an Alternative Roof Underlayment (AC266), dated May 2008 (editorially updated October 2015). 7.0 IDENTIFICATION Each ZIP System and ZIP System+T" roof sheathing panel covered by this report must bear a label that includes the manufacturer's name (Huber Engineered Woods, LLC) and address; the product name; the evaluation report number (ESR-1473); and the grade, performance category and bond classification. The panel mill label and span rating, grade, performance category and bond classification label must be visible on the bottom face of panels, opposite the laminated facer. The ZIP Systems tape roll is labeled with the product name and the evaluation report number (ESR-1473). IMES Evaluation Report ESR-1473 FSC Supplement Reissued September 2015 This report is subject to renewal September 2017. www.icc-es.org 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 06 00 00—WOOD, PLASTICS, AND COMPOSITES Section: 06 16 00—Sheathing DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 30 05—Roofing Felt and Underlayment REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 (800) 933-9220 www.huberwood.com EVALUATION SUBJECT: ZIP SYSTEM® AND ZIP SYSTEM+Tm ROOF SHEATHING 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that ZIP System® and Zip System+T"" roof sheathing, recognized in ICC-ES master evaluation report ESR-1473, has also been evaluated for compliance with the codes noted below. Applicable code editions: * 2014 Florida Building Code —Building * 2014 Florida Building Code —Residential 2.0 CONCLUSIONS The ZIP System® and ZIP System+Tm roof sheathing, described in Sections 2.0 through 7.0 of the master evaluation report ESR-1473, complies with the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential, provided the design and installation are in accordance with the international Building Code® provisions noted in the master report, and with the condition that wind uplifting design loads must be determined in accordance with Section 1609 of the Florida Building Code —Building and Section R301.2.1 of the Florida Building Code —Residential. Use of the ZIP System° and ZIP System+T"' roof sheathing for compliance with the High -Velocity Hurricane Zone provisions of the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential has not been evaluated and is outside the scope of the evaluation report. For products falling under Florida Rule 9N-3, verification that the report holder's quality -assurance program is audited by a quality -assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official, when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, reissued September 2015 and revised November 2015 ICC-ES Evaluation Reports are not to be construed at representing aesthetics or any other attributes not speciftcally addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warrantyby ICC Evaluation Service, LLC, espress or implied as to any finding or other matter in this report, or ar to any produci covered by the report. EM copyright 2015 ICC Evaluation Service, LLC. Al rights reserved. Page 1 of 1 Florida Building Code Online Page 1 of 1 s't'%'y' :'tea *`�•.�" '�' "`vrs� R=.o=}.;x.�J i'i� 1 r�,.v ��, �' � � u � ,1+. ` � � �%v� t...;�„ s `.,uer�.t[oGetat;craroeea edvkdiet wia rattrA t.Degn SOS Home Log In I User Registration Hot Topics Submit Surchanlie Slats Bt Facts Publications FBC Staff BCJS Site Map Links Search I Product Approval t {�:r e USER: Public User Search Criteria Refine Search Code Version 2014 FL# 17147 Application Type ALL Product Manufacturer ALL Category ALL Subcategory ALL Application Status ALL Compliance Method ALL Quality Assurance Entity ALL Quality Assurance Entity Contract Expired ALL Product Model, Number or Name ALL Product Description ALL Approved for use in HVHZ ALL Approved for use outside HVHZ ALL Impact Resistant ALL Design Pressure ALL Other ALL Cl—reh Raeu ltc - Ann1lr�+inns EL# 7_Y22 (Manufacturer Validated ft Status 1FL 7147_ Revision Huber Engineered Woods LLC ICC Evaluation Service, Approved EU Category: Structural Components LLC. History Subcategory: Products Introduced as a Result of New (205) 599-9800 Technology Contact Us:: 2401 a air Starr R. Tm;I-S — r -ra a2ago Pe te R The State of Florida Is an AA/eEo employer. Copve3otk 2007.2013 State of Flo,'& ;: .JYJLy ey1• M0 :: A•mcdbiliy N.�Statnmenr Under Florida law, email addresses are public records. U you do rot wart your rMll addr5s released in response to a public -records request, do not sand electronic ma!I to this entity, instead, contact the of&e by phone or by traditienaf mall. Uyou ha•ra any questions, please contact 850.487,1395. 'Pursuant to Sectlon 455.275(1), Florida Statutes, effective October 1, 2012, licensees Ilcarsed under Chapter 455, F.S. must provide the Department with an email address If they have one. The Smalls provided may be used tar official communimtion with the licensee. However mall addresses are public record. 111 you do not wish to supply a Personal address, please provide the Departrent with an email address whim can be made available to the public. To determine if you are a licensee under Chapter 455, F.S., please tilck here . Product Approval pppprcce oval Apts: 99 RE 12 Credit Card Sate a' https://wwrv.floridabuilding.org/pr/Pr�_appjst.aspx 4/ 12/2017