HomeMy WebLinkAboutLETTER-RESPONSES TO COMMENTSArchitectonic Inc SCANNED SY St. Lucie County Building Department Planning & Development Serv�iUNIG COUnty Building & Code Regulation Division 2300 Virginia Avenue Ft. Pierce, FL 34982 October 10, 2018 RE: Debbie Brenner/18504 Tranquility Base Lane Permit # 1801-0366 To Whom It My Concern: RECEIVED OCT 1'2 2018 Penpitting 9®Partment St. lWe CQuntb Please accept the following responses to the comments dated 10/8/2018 from your agency. Response shown on plans corresponding (if required) to these comments are noted. *Please show compliance with 412.5.2 egress. A hanger shall provide two means of FBC 2017 6th Edition. Response: SEE REVISED SHEET 1 *The electrical NEC code referenced is out dated code cycle. Designs must comply too NEC Edition 2014. Please review plans and make corrections. Response: SEE REVISED SHEET 1 *Please provide framing detail for the egress doors. Chapter 1, Section 10 Subsection 107.1 of the 2017 FBC 6th Edition. Response SEE REVISED SHEET 1 *Please provide framing detail for the Roll Up Door. Chapter 1, Section 107 Subsection 107.1 of the 2017 FBC 6dth Edition. Response: SEE REVISED SHEET 1 *Please provide Anchor Bolt lengths as per DWG # MB-1.10. Response: SEE REVISED SHEET 1 *Please provide transfer of Anchor Bolt Force to the concrete as per DWG # MB-1.10 Response: SEE REVISED SHEET 1 Please show compliance with 412.5.3 Smoke Alarms. Smoke Alarms shall be provided within the Hanger in ccordance with the 2017 FBC 6th Edition Section 907-2.212017 FBC 61h Edition. esponse: SEE REVISED SHEET 1 'e - ...:: UJ ha SeRP Architec h'ic Inc..: V� R .. TE a Tel: 772 460 7751 www.architectonicinc.com j fort i orida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1