HomeMy WebLinkAboutLETTER-REVIEW-COMMENTSSCANNED BY J ����®��� 6095 Parkland Boulevard ® Cleveland, Ohio 44124 THEM,NY www.theaustin.com PH 440.544.2600 FX 440.544.2690 July 31, 2008 Mr. Greg Smyth St. Lucie County Plumbing Inspector 2300 Virginia Ave Ft. Pierce, FI. 34982 RE: Florida Power & Light PSL — Maintenance Building Austin's W.O. #07-10129 Review Comment #10, dated 07/25/2008 Dear Mr. Greg Smyth, This letter addresses the Review Comment #10 dated 07/25/2008 for the _ ie Maintenance Building. 10. Number of plumbing fixtures are not equal for worn and FBC Section P403.3. Section P403.3 of the code states: 'The required a set, ories, and showers or bathtubs shall be distributed equally between xe as d on the percentage of each sex anticipated in the occupant load. The occ nt e composed of 50% of each sex, unless statistical data approved by the cod ✓ci i dicate a different distribution of the sexes. " The number of fixtures required, and provided, are as listed below: • 20 water closets are required; 22 water closets are provided: 9 are in Women's Toilet Room and 13 are in Men's Toilet Rooms. • 15 lavatories are required; 25 are provided: 9 are in the Women's Toilet Room and 16 are in the Men's Toilet Rooms. The intent of this letter is to document that the distribution of sexes at the St. Lucie Nuclear Power Plant is not 50% and that the project meets the requirements of the Florida Building Code, Section P403.3. This building is located inside the protected area of the FPL St. Lucie Nuclear Power Plant and access into the protected area is restricted. This building is designed to house FPL personnel assigned to the St. Lucie facility. The Human Resources Department at FPL St. Lucie has verified that the distribution of FPL employees with badges at St. Lucie Plant is 89% male and 11% female. Therefore we have an occupant load that is not 50% of each sex. Sincerely, TH '�1STIN COMPANY gers anager of Engineering C ON S U LTA N T 5 o D E S I G N E R S o E N G I N E E R S o C O N S T R U C T O R S