HomeMy WebLinkAboutLOAD DESCRIPTIONSi
. Florid Power & Light
St. Lu6ie, PSL Bldg -FL.
W.7-10129
BY
St. Lucie COMW
4/11/08
D/B/A THE AUSfIN COMPANY
CERT. OF AUTHORIZATION #26945
MAIN SWBD- "MDP"
Tac#
(11oad description
Volt
Ph
HP
AMP
CONN.
KVA
CONN.
AMP.
Load
Factor
Load kVA
Load
Amps
Remarks
Main SWBD-"MDP"
DC : OWER SUPPLY
460
3
40.3
33.5
40.3
0.74
24.8
29.8
See Note 1
T 'OSFORMER-T-1
4601
3
1
135.3
1 112.5
135.3
1 0.77
86.6
104.2
See Note 2
PANEL-PP3A
460
3
1
108.1
89.9
108.1
1.00
89.9
108.1
See Note 3
PA EL-PP1A
460
3
230.1
191.3
230.1
1.00
191.3
230.1
See Note 3
CH LLER #1
460
3
180.4
150.0
180.4
1.00
150.0
180.4
See Note 3
CHILLER #2
460
3
180.4
150.0
180.4
1.00
150.0
180.4
See Note 3
PA ;EL- V2
460
3
117.9
98.0
117.9
1.00
98.0
117.9
See Note 3
PANj;EL V3W
460
3
46.9
1 39.0
46.9
1 1.00
39.0
46.9
See Note 3
EL
VATOR 30HP MOTOR
460
3
30
39.7
33.0
39.7
1.00
33.0
39.7
See Note 3
PANEL-LP1W
460
3
59.3
49.3
59.3
1.00
49.3
59.3
See Note 3
PA
EL-LP1E
460
3
76.3
63.4
76.3
1.00
63.4
76.3
See Note 3
PANEL-PP2A
460
3
401.7
334.0
401.7
0.78
1 261.7
314.8
See Note 2
PANEL-PP1M
1460
1 3
1 355.5
295.5
1 355.5
0.93
1 274.2
335.5
1 See Note 3
To`
al
1639
1 1972
1511
1823
Switchboard is 2000A
NOTES: .
�41
I
1. EMHP,
50-130 has a 44A input rating at 440V, 3-phase, or 33.53 kVA. The Connected Load is 14.4 KVA
which r
sults in a 24.8 WA input, a 0.74 Load Factor.
2. LoadrE
resents 10 kVA of all of the XFMR 180 VA loads plus 50% of the remaining 180 VA loads plus all non-180 VA loads.
3. This is
connected load.
rs\0129\Elec\MDP Revised 4-14-08 .xis MDP 1 of 7
Florid) Power Light
St. L cie, PSL-bldg,FL
W.O. 7-10129
D/B/A THE AUSfIN COMPANY
CERT. OF AUTHORIZATION #26945
PANEL
"PP3A"
Tac #
Load description
Volt
Ph
HP
AMP
CONN.
KVA
CONN.
AMP.
Load
Factor
Load
KVA
LoadRemarks
Amps
P
fiVEL "PP3A"
AH
I -3
460
3
30
39.7
33
40
1
33
40
AH
-4
460
3
30
39.7
33
40
1
33
40
COOLING
TOWER CELL CT-1A
460
3
10
13.4
11
13
1
11
13
10HP Fan
COOLING
TOWER CELL CT-1B
460
3
10
13.4
11
13
1
11
13
10HP Fan
EX
. FAN EF-5
460
3
0.75
1.9
1 2
2
1
2
2
1
1
1
1
1 -1-1-1
1
L1
Su
TOTAL LOAD at Panel
90
108
90
108
PANEL
SIZE 400A
rkorders\0129\Elec\MDP Revised 4-14-08 .xls PP3A 2 of 7
D/B/A THE AUSTIN COMPANY
CERT. OF AUTHORIZATION #26945
Florid) Powe'
Light
St. Ll I I PSL-bldg,FL
W.O.Q7-10129
PA'EL"PP1A"
Tac#
Load description
Volt
Ph
HP
AMP
CONN.
KVA
CONN.
AMP.
Load
Factor
Load
KVA
Load
Amps
Remarks
PANEL
"PP1A"
CHILLER
PUMP - P-1
460
3
15
20.4
17
20
1
17
20
CHI,LLER
PUMP - P-2
460
3
15
20.4
17
20
1
17
20
MT
LAB AC UNIT AC-1
460
3
15
21.7
18
22
1
18
22
CO
5, LING TWR PUMP P-3
460
3
15
20.4
17
20
1
17
20
CO
LING TWR PUMP P-4
460
3
15
20.4
17
20
1
17
20
MC
NORAIL HOIST
460
3
5
8.4
7
8
1
7
8
EX
IAUST FAN EF-9
460
3
3/4
1.5
1
2
1
1
2
1 R
LLUP DOOR - SHP
460
3
5
8.4
7
8
1
7
8
W
ER HEATER - DWH-1
460
3
54.1
45
54
1
45
54
W ER HEATER - DWH-2
460
3
54.1
45
54
1
45
54
S
b TOTAL LOAD at
191
230
191
230
P
NEL SIZE 600A
29\Elec\MDP Revised 4-14-08 .xis PP1A 3 of 7
Florid 11 Power Light
St. L cie, PSL-bldg,FL
11
W.O. 17-10129
D/B/A THE AUS IN COMPANY
CERT. OF AUTHORIZATION426945
PANEL
"PP2A"
Tac#
Load description
Volt
Ph
HP
AMP
CONN.
CONN.
AMP.
Load
Factor
Load
KVA
LoadKVA
Am s
Remarks
PANEL
"PP2A"
T
,NSFORMER T-2
460
3
180.4
150
180
0.84
126
152
See Note 1
DA
CONDITIONER
iAWAVE POWER
DITIONER
460
3
90.2
75
90
0.35
26
32
See Note 2
AH'
-1
460
3
15
20.4
17
20
1
17
20
AH
D -1 REHEAT
460
3
90.2
75
90
1
75
90
AH
-2
146701
3
1 15
1 20.4
1 17
20
1
17
20
S
b TOTAL LOAD at
334
402
262
315
P6NEL
SIZE 600A
NOTES:
1. Load r
presents 10 kVA of all of the XFMR 180 VA loads plus 50% of the remaining 180 VA loads
plus all non-180 VA loads,
2. The Da, awave has an approximate efficiency of 89%. The 23.45 kVA actual load equates to a 26.21 kVA input load.
29\Elec\MDP Revised 4-14-08 .xls PP2A 4 of 7
i
Florid Power Light
St. L cie, PSL-bldg,FL
W.O. 7-10129
D/B/A THE AUSTIN COMPANY
CERT. OF AUTHORIZATION #26945
Tac #
PANEL "PP1 M
Lo 'd description
Volt
Ph
HP
AMP
CONN.
KVA
CONN.
AMP.
Load
Factor
Load
KVA
Load
Amps
Remarks
PA' EL "PP1 M"
PO ER OUTLET -100A
460
3
60.1
50
60
1
50.0
60
POWER OUTLET - 60A
460
3
0.0
0
0.0
0
Owner has only
three pieces of
equipment that can
plug into these
receptacles.
POWER OUTLET - 60A
460
` 3
30.1
25
30
1
25.0
30
PO , ER OUTLET - 60A
PO ;; ER OUTLET - 60A
PO � ER OUTLET - 60A
460
460
460
3
3
3
0.0
0.0
0.0
0
0
0
0.0
0.0
0.0
0
0
0
PO,, ER OUTLET - 60A
460
3
30.1
25
30
1
25.0
30
PO ER OUTLET - 60A
460
3
0.0
0
0.0
0
POWER OUTLET - 60A
460
3
30.1
25
30
1
25.0
30
T , NSFORMER T-3
460
1
31.3
15
31
0.43
6.5
13
Actual Conn. Load
2 I
OLL-UP DOORS @ 5HP
460
3
15.6
13
16
1
13.0
16
5
''OLL-UP DOORS @ 5HP
460
3
37.9
32
38
1
31.5
38
M
NORAIL HOIST AND Door
460
3
1 5
14.4
1 12
14
1
12.0
14
J1 I CRANE
460
3
5
7.2
6
7
1 1
6.0
7
E . FAN EF-7
460
3
7.5
10.8
9
11
1
9.0
11
Et. FAN EF-8
460
3
7.5
10.8
9
11
1
9.0
11
T I NSFORMER T-4
460
3
90.2
75
90
0.83
62.3
75
Actual Conn. Load
;I
Sib
TOTAL LOAD at
296
369
274.2
336
P
NEL SIZE: 600A
129\Elec\MDP Revised 4-14-08 .xls PP1M 5 of 7
i
I
D/B/A THE AU!
RPP1L,
180VA
on- 180V
Total
1st 1 Total
CERT. Of AUfHDI
Tac
# ! Load
Panel
CONN.
CONN.
Load Load
descripti
Conn
Remarks
KVA
WA.
Factor KVA
on
kVA
PANEL
"RPP1"
28.3
0.0
28.3
10.0
19.2
10 WA
RPIWA
included
here
RP1wB
0.0
10.5
10.5
10.5
RPMM
12.2
10.8
23.0
16.9
RP1EA
27.2
0.0
27.2
13.6
RP1EB
11.0
5.2
16.2
10.7
RPEM
8.6
1 9.6
18.2
13.9
FACP
0.0
1.9
1.9
1.9
'I
87.3
1 38.0
125.3
0.69
86.7
*Loa
represents 10 WA of all of the XFMR 180 VA loads plus 50% of the remaining 180 VA loads
CF
I
i
I
I
I
I
i
i
)TIN COMPANY
UZATIOR,#26945
plus all non-180 VA loads.
D/B/A THE AUSTIN COMPANY
CERT. OF AUTHORIZATION #26945
PANEL
180VA
on- 18OVI
Total
1st 1
Total
"RPP2"
kVA
Tac #
Load
CONN.
CONN.
Panel
Load
Load
descripti
KVA
kVA.
Conn
Factor
KVA
Remarks
on
kVA
JPANEL
"RPP2"
11.3
1.4
12.7
10.0
12.1
10 kVA
RP2WA
included
here
RP2WB
18.9
1.3
20.2
10.8
RP3WA
36.9
1.4
38.3
19.9
RP3WB
30.2
3.5
33.7
18.6
RP2EA
28.4
0.0
28.4
14.2
p�
RP2EB
13.1
4.2
17.3
10.8
RP3EA
35.3
3.6
38.9
21.3
RP3EB
29.2
4.4
33.6
19.0
203.3
19.8
223.1
0.57
126.5
*Load
10 WA of all of the XFMR 180 VA loads plus 50% of the remaining 180 VA loads plus all non-180 VA loads.