HomeMy WebLinkAboutICC-ES-EVALUATION REPORT-ES Evaluation Report ESR-2074 FBC Supplement
SCANNED Issued July 1, 2013
This report is subject to renewal February 1, 2015.
w�nnruv.icc-es.org 1 (800) 423-6587 1 (562) 699 0643 A Subsidiary of the International Code Council®
I: 08 00 00—OPENINGS
08 95 43—Vents/Foundation Flood Ve�`Iis
HOLDER:
\RTVENT PRODUCTS, INC.
ANDBRO DRIVE, UNIT 1
RAN, NEW JERSEY 08071
') "1-8368
TION SUBJECT:
VENT" AUTOMATIC FOUNDATION FLOOD (VENTS: FLOODVENT- MODEL #1540.520; FLOODVENTTm STACKING
#1540-521; SMARTVENTTm MODEL #1540-610; SMARTVENt- STACKING MODEL #1540-511; WOOD WALL FLOOD
#1540-570; WOOD WALL FLOOD OVERHEAb DOOR MODEL #1540.574; FLOODVENT7m OVERHEAD DOOR MODEL
t4; SMARTVENTTm OVERHEAD DOOR MODEL #1540-614
REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that Smart Vent® Automatic Foundation Flood Vents, recognized
in ICC-ES master report ESR-2074, have also been evaluated for compliance with the codes noted below.
code editions:
■ 2010 Florida Building Code —Building (FBC)
■ 2010 Florida Building Code —Residential (FRC)
CONCLUSIONS
The Smart Vent® Automatic Foundation Flood Vents, described in Sections 2.0 through 7.0 of the master evaluation report
ESR-2074, comply with the FBC and the FRC, provided the design and installation are in accordance with the International
Building Code® provisions noted in the master report.
Use of the Smart Vent® Automatic Foundation Flood Vents has also been found to be in compliance with the High -Velocity
Hurricane Zone provisions of the FBC and the FRC for structures not subject to FBC Section 2326.3.1 or FRC Section
4409.13.3.1, as applicable.
For products falling under Florida Rule 9N-3, verification that the report holder's quality assurance program is audited by a
quality assurance entity approved bycthe Florida Building Commission for the type of inspections being conducted is the
responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by
the Commission).
supplement expires concurrently with the master report, reissued December 1, 2012, revised July 2013.
C-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed nor are they to be construed
an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
any finding or other matter in this report, or as to any product covered by the report. NO
�m
O 2013 Page 1 of 1
-ES Evaluation Report
ESR-2074*
Reissued December 1, 2012
This report is subject to renewal February 1, 2015.
vjMAcc-es:ora 1 (800) 423-6687 1 (562) 699-0543 A Subsidiary of the International Code Council°
I: 08 00 00—OPENINGS
08 95 43—Vents/Foundation Flood Vents
HOLDER:
\RTVENT PRODUCTS, INC.
ANDBRO DRIVE, UNIT 1
61AN, NEW JERSEY 08071
1 441-8368
ALUATION SUBJECT:
VENT' AUTOMATIC FOUNDATION FLOOD VENTS:
tENTTM MODEL #1640-520; FLOODVENTTm
MG MODEL #1540-521; SMARTVENTTm MODEL
10; SMARTVENTTm STACKING MODEL #1540-511;
WALL FLOOD MODEL #1540-570; WOOD WALL
OVERHEAD DOOR MODEL #1640-574;
/ENTTm OVERHEAD DOOR MODEL #1540.624;
fENTTM OVERHEAD DOOR MODEL #1640-514
U0 EVALUATION SCOPE
with the following codes:
■ 2009 and 2006 International Building Code® (IBC)
* 2009 and 2006 International Residential Code® (IRC)
evaluated:
■ Physical operation
■ Water flow
USES
ie Smart Vent® units are automatic foundation flood
nts (AFFVs) employed to equalize hydrostatic pressure
i nonfire-resistance-rated foundation walls, rolling -type
erhead, doors and building walls subject to rising or
ling flood waters. The Smart Vent® units are intended for
e where flood hazard areas have been established in
cordance with IBC Section 1612.3 or IRC Section
Q22.1. Certain models also allow natural ventilation in
cordance with Section 1203 of the IBC or Section 408.1
the IRC.
DESCRIPTION
1 General:
subjected to pressure from rising water, the Smart
AFFVs disengage, then pivot open to allow flow in
direction to equalize water level and hydrostatic
pressure from one side of the foundation to the other. The
AFFV pivoting door is normally held in the closed position
by a buoyant release device. When subjected to rising '
water, the buoyant release device causes the unit to
unlatch, allowing the plate to rotate out of the way and
allow flow. The water level stabilizes, equalizing the lateral
forces. Each unit is fabricated from stainless steel. The
SmartVENTTM Stacking Model #1540-511 and
FloodVENTTm Stacking Model #1540-521 units each
contain two vertically arranged openings per unit.
3.2 Engineered Opening:
The AFFVs comply with the design principle noted in
Section 2.6.2.2 of ASCE/SEI 24 for a maximum rate of rise
and fall of 5.0 feet per hour (0.423 mm/s). In order to
comply with the engineered opening requirement of
ASCE/SEI 24, •Smart Vent AFFVs must be installed in
accordance with Section 4.0.
3.3 Model Sizes:
The FloodVENTTM Model #1540-520, SmartVENTTM'Model
#1540-510, FloodVENTTM Overhead Door Model
#1540-524, and SmartVENTTM Overhead Door Model
#1540-514 units measure 153/4 inches wide by 73/4 inches
high (400 by 196.9 mm). The Wood Wall Flood Model
#1540-570 and Wood Wall Flood Overhead Door Model
#1540-574 units measure 14 inches wide by 83/4 inches
high (355.6 by 222.25 mm). The SmartVENTTM Stacking
Model #1540-511 and FloodVENTTM Stacking Model
#1540-521 units measure 16 inches wide by 16 inches
high (406.4 by 406.4 mm):
3.4 Ventilation:
The SmartVENT® Model #1540-510 and SmartVENT®
Overhead Door Model #1540-514 both have screen covers
with 1/4-inch-by-1/4-inch (6.35 by 6.35 mm) openings,
yielding 51 square inches (32 903 mm2) of net free area
to supply natural ventilation. The SmartVENTTM Stacking
Model #1540-511 consists of two Model #1540-510.
units in one assembly, and provides '102 square inches
(65 806 mm2) of net free area to supply natural ventilation.
Other AFFVs recognized in this report do not offer natural
ventilation.
4.0 INSTALLATION
SmartVENT' and FloodVENT rm are designed to be
installed into walls or overhead doors of existing or new
construction from the exterior side. Installation of the vents
must be in accordance with the manufacturer's
instructions, the applicable code and this report. The
mounting straps allow mounting in wood, masonry and
*Revised July 2013
iS Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
o finding or other matter in this report, or as to arty product covered by the report.cmuG u
,mo
right © 2013 Page 1 of 2
Most Widely Accepted and Trusted
i
2of2
ncrete walls up to 12 inches (305 mm) thick. In order to
mply with the engineered opening design principle noted
Section 2.6.2.2 of ASCE/SEI 24, the Smart Vent® AFFVs
ist be installed as follows:
With a minimum of two openings on different sides of
each enclosed area.
With a minimum of one AFFV for every 200 square
feet (18.6 m) of enclosed area, except that the
SmartVENTTm Stacking Model #1540-511 and
FloodVENTT"' Stacking Model #1540-521 must be
installed with a minimum of one AFFV for every
400 square feet (37.2 M) of enclosed area.
Below the base flood elevation.
With the bottom of the AFFV located a maximum of
12 inches (305.4 mm) above grade.
CONDITIONS OF USE
e Smart Vent® AFFVs described in this report comply
:h, or are suitable alternatives to what is specified in,
)se codes listed in Section 1.0 of this report, subject to
following conditions:
A
5.1 The Smart Vent® AFFVs must be installed in
accordance with this report, the applicable code and
the manufacturer's installation instructions. In the
event of a conflict, the instructions in this report
govern.
6.2 The Smart Vent® AFFVs must not be used in the
place of "breakaway walls" in coastal high hazard
areas, but are permitted for use in conjunction with
breakaway walls in other areas.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria
for Automatic Foundation Flood Vents (AC364), dated
October 2007.
7.0 IDENTIFICATION
The Smart VENT models recognized in this report must
be identified by a label bearing the manufacturer's name
(Smartvent Products, Inc.), the model number, and the
evaluation report number (ESR-2074).