EVALUATION REPORT
GAF
1 Campus Drive
Parsippany, NJ 07054
(800)766-3411
EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT#13
OXFORD, CT 06478
(203)262-9245
Evaluation Report 01506.01.08-1122
FL10124-1120
Date of Issuance:01/03/2008
Revision 22: 09/20/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 61h Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: GAF Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein and FBC 1507.2.7.1 / R905.2.6.1.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. TrinityJERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity) ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 09/20/2017. This does not serve as an electronically signed
document.
CERTIFICATION OF INDEPENDENCE:
1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity] ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
nr�t
All
(T_fRINITYJERD'�l ,
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Asphalt Shingles
Compliance Statement: GAF Asphalt Roof Shingles, as produced by GAF, have demonstrated compliance with the
following sections of the 6th Edition (2017) Florida Building Code and Florida Building Code, Residential Volume
through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements
and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Property
Standard
Year
1507.2.4 / 1507.1.1,
Physical Properties
ASTM D1970
2015
R905.2.3 / R905.1.1
1507.2.5; R905.2.4
Physical Properties
ASTM D3462
2010
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D3161
2016
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D7158
2011
1507.2.7.1, R905.2.6.1
Wind Resistance
TAS 107
1995
3. REFERENCES:
kniitl
Examination
Reference
Date
GAF (PDM 1915)
Letter of Equivalency
Seal -A -Ridge Impact Resistant IR
01/13/2012
PRI (TST 5878)
Physical Properties
GAF-025-02-01
03/27/2002
PRI (TST 5878)
ASTM
D3462
GAF-059-02-01
09/02/2004
PRI (TST 5878)
ASTM
D3462
GAF-080-02-01
05/25/2005
PRI (TST 5878)
Physical Properties
GAF-324-02-01
12/01/2011
PRI (TST 5878)
Wind
Driven Rain
GAF-407-02-01
01/21/2013
UL (TST 1740)
ASTM
D3462
93NK6295
11/29/1993
UL (TST 1740)
ASTM
D3462
99NK43835
01/12/2000
UL (TST 1740)
TAS 107
94NK9632
03/29/2000
UL (TST 1740)
ASTM
D3462
01NK06632
02/02/2001
UL (TST 1740)
ASTM
D3161, TA5107
01NK9226
05/21/2001
UL (TST 1740)
ASTM
D3161
01NK37122
12/18/2001
UL(TST 1740)
ASTM
D3462
01NK37122
12/19/2001
UL (TST 1740)
ASTM
D3161, TAS 107
02NK12980
04/10/2002
UL (TST 1740)
ASTM
D3161, TAS 107
02NK30871
09/09/2002
UL (TST 1740)
ASTM
D3161
03CA5367
03/11/2003
UL (TST 1740)
ASTM
D3462
03NK26444
10/17/2003
UL (TST 1740)
ASTM
D3462
04NK13850
06/07/2004
UL (TST 1740)
ASTM
D3161
04NK13850
06/23/2004
UL (TST 1740)
ASTM
D3161
04NK30546
03/10/2005
UL (TST 1740)
ASTM
D3462
04NK22009
05/06/2005
UL (TST 1740)
ASTM
D3161
04NK22009
05/09/2005
UL (TST 1740)
ASTM
D3462
05NK27924
02/10/2006
UL (TST 1740)
ASTM
D3161
05NK27924
02/11/2006
UL (TST 1740)
ASTM
D3161,D3462
06CA18077
06/05/2006
UL (TST 1740)
ASTM
D3161,D3462
06CA18074
06/16/2006
UL (TST 1740)
ASTM
D3161,D3462
06CA35251
10/18/2006
UL (TST 1740)
ASTM
D3462
06CA31603
12/01/2006
UL (TST 1740)
ASTM
D3161,D3462
06CA41095
12/27/2006
UL (TST 1740)
ASTM
D3161
07NK05228
03/13/2007
UL (TST 1740)
ASTM
D3161
06CA31611
04/04/2007
UL (TST 1740)
ASTM
D3161
06CA61148
04/09/2007
UL (TST 1740)
ASTM
D3161,D3462
07CA31742
11/08/2007
UL (TST 1740)
ASTM
D3161, D7158, D3462
08CA06100
03/13/2008
Exterior Research and Design; I.I.C. Evaluation Report 01506.01.08-1122
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL10124-1120
GAF Asphalt Roof Shingles Revision 22: 09/20/2017
Page 2 of 6
QfT INITY I ERD
tatiY
Examination
Reference
Date
UL (TST 1740)
ASTM D3161, D3462
07CA55908
04/01/2008
UL (TST 1740)
ASTM D3161, D3462
09CA10592
03/26/2009
UL (TST 1740)
ASTM D3161, D3462
09CA06856
05/15/2009
UL (TST 1740)
ASTM D3161, D7158, D3462
09NK06647
08/01/2009
UL (TST 1740)
ASTM D3161, D7158, D3462
09CA27281
08/27/2009
UL (TST 1740)
ASTM D3161, D7158, D3462
IOCA35554
03/05/2010
UL (TST 1740)
ASTM D3161, D7158, D3462
10CA13686
05/15/2010
UL (TST 1740)
ASTM D3462
IOCA07264
05/27/2010
UL (TST 1740)
ASTM D3462
IOCA11953
10/29/2010
UL (TST 1740)
ASTM D3161, D7158, D3462
IONK11951
10/30/2010
UL (TST 1740)
ASTM D3161, D7158, D3462
IONK12070
11/04/2010
UL (TST 1740)
ASTM D3161, D7158, D3462
08CA06100
01/30/2010
UL (TST 1740)
ASTM D3161, D7158, D3462
IOCA53934
03/31/2011
UL (TST 1740)
ASTM D3161, D7158, D3462
11CA48924
10/22/2011
UL (TST 1740)
ASTM D3161, D7158, D3462
11CA47919
12/03/2011
UL (TST 1740)
ASTM D3161, D7158, D3462
11CA48408
12/08/2011
UL (TST 1740)
ASTM D3161, D7158, D3462
11CA48725
12/09/2011
UL, LLC. (TST 9628)
ASTM D3462
12CA34891
10/12/2012
UL, LLC. (TST 9628)
ASTM D3161, D7158, D3462
12CA58151
02/15/2013
UL, LLC. (TST 9628)
ASTM D3161
12CA38083
02/26/2013
UL, LLC. (TST 9628)
ASTM D3161
13CA32332
06/18/2013
UL, LLC. (TST 9628)
ASTM D3161
13CA37934
08/02/2013
UL, LLC. (TST 9628)
ASTM D3161, D7158, D3462
4786875675
07/17/2015
UL, LLC. (TST 9628)
ASTM D3161, D7158, D3462
4787434542
05/17/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Mobile, AL
10/25/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Myerstown, PA
10/20/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Tuscaloosa, AL
11/11/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Michigan Cty, IN
11/01/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Shafter, CA
11/17/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Savannah, GA
11/11/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Minneapolis, MN
10/25/2016
UL, I.I.C. (QUA 9625)
Quality Control
Inspection Report, R21, Mt. Vernon, IN
10/25/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Baltimore, MD
10/21/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Tampa, FL
11/17/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Dallas, TX
11/04/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Ennis, TX
11/03/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Fontana, CA
11/01/2016
PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Marquis® WeatherMax®, Royal Sovereign® and Sentinel® are a fiberglass reinforced 3-tab asphalt roof
shingles.
4.1.2 Camelot®, Camelot® II, Fortitude TI, Glenwood TM, Grand Canyon®, Grand Sequoia®, Grand Sequoia® IR,
Grand Sequoia® ArmorShieldT1, Monaco®, Sienna®, Timberline® American Harvest®, Timberline®
ArmorShieldTM II, Timberline® Natural Shadow®, Timberline HD®, Timberline® Cool Series®, Timberline Ultra
HD® and Woodland® are fiberglass reinforced, laminated asphalt roof shingles.
4.1.3 Slateline® is a fiberglass reinforced 5-tab asphalt roof shingle.
4.2 Hip & Ridge Shingles:
4.2.1 Seal -A -Ridge® Ridge Cap Shingles, Seal -A -Ridge® IR Impact -Resistant Ridge Cap Shingles, Seal -A -Ridge®
ArmorShieldT1 Ridge Cap Shingles and Timbertex® Premium Ridge Cap Shingles are fiberglass reinforced, hip
and ridge asphalt roof shingles.
Research and Design, I.I.C. Evaluation Report 01506.01.08-1122
a oJAuthorizotion #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL10124-1120
GAF Asphalt Roof Shingles Revision 22: 09/20/2017
Page 3 of 6
TRINITY � ERD
I,
4.3 Accessory Starter Strips:
4.3.1 Pro -Start® Eave/Rake Starter Strip Shingles and WeatherBlockerTM Premium Eave/Rake Starter Strip Shingles
are starter strips for asphalt roof shingles.
4.3.2 QuickStart® Peel & Stick Starter Roll is a is a mineral -surfaced, fiberglass -reinforced, self -adhering SBS
modified bitumen starter strip, nominal 9-inch x 33 ft roll, for use with asphalt shingles with exposure of 6
inch or less.
4.3.3 StarterMatchTM Starter Strip Shingles are color -coordinated starter strips for use with Grand Canyon® and
Grand Sequoia® series asphalt shingles. StarterMatchTM are installed as the second starter for Grand,
Canyon® and Grand Sequoia® series installations.
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
I
5.4 Wind Classification:
5.4.1 The GAF asphalt shingles noted in Section 4.1 are Classified in accordance with FBC Tables 1507.2.7.1 and
R905.2.6.1 to ASTM 03161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable for
use in all wind zones up to Vasd = 150 mph (V,,it = 194 mph). Refer to Section 6 for installation requirements
to meet this wind rating.
5.4.2 The GAF hip & ridge shingles noted in Section 4.2 are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161, Class F, indicating the shingles are acceptable for use in all wind zones up
to Vasd =150 mph (V it = 194 mph). Refer to Section 6 for installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies only to exposure category B or C, as defined in FBC 1609.4.3, and a
mean roof height of 60 feet or less. Calculations by a qualified design professional are required for
conditions outside these limitations. Contact the shingle manufacturer for data specific to each shingle.
�I
5.5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule 61G20�3.
6. INSTALLATION:
6.1 Underlayment:
6.1.1 Underlayment shall be acceptable to GAF and shall hold current Florida Statewide Product Approval, oij be
Locally Approved per Rule 611320-3, per FBC 1507.2.3, 1507.2.4 or R905.2.3.
6.2 Starter Shingles or Starter Strip:
6.2.1 Installation of Pro -Start Eave/Rake Starter Strip Shingles, WeatherBlocker Premium Eave/Rake Starter Strip
Shingles and QuickStart Peel & Stick Starter Roll shall comply with the GAF current published instructions.
6.3 Asphalt Shingles:
6.3.1 Installation of asphalt shingles shall comply with the GAF current published instructions, using minimum four
(4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following exceptions: I
➢ Camelot, Camelot II, Grand Canyon, Grand Sequoia, Grand Sequoia IR, Grand Sequoia ArmorShield,
and Woodland require minimum five (5) nails per shingle.
➢ Slateline requires minimum six (6) nails per shingle.
6.3.2 Fasteners shall be in accordance with manufacturer's published requirements, but not less than FBC 1507.2.6
or R905.2.5. Staples are not permitted.
6.3.3 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. Contact the GAF for details. j
Exterior Research and Design, I.I.C. Evaluation Report 01506.01.08' R22
Certificate of Authorization #9503 CH EDITION (2017) FBC NON-HVHZ EVALUATION FL10124R20
GAF Asphalt Roof Shingles Revision 22: 09/20/2017
Page 4 of 6
I
R®,
TRINITY I E
6.4 Hip & Ridge Shingles:
6.4.1 Installation of'Seal-A-Ridge Ridge Cap Shingles; Seal -A -Ridge IR Impact -Resistant Ridge Cap Shingles and
Seal -A -Ridge ArmorShield Ridge Cap Shingles. shall comply with the GAF current published instructions with
a minimum two (2) nails, minimum 3/8-inch head diameter, per shingle and nominal 0.25-inch diameter
beads of Henkel "Loctite PL S30 Roof & Flashing Sealant".
11.5° Sealant
1° (292mm) 1°- Sellante
(25 mm) (25 in Enduit d'etancheite
12"
Nail (305 mm)
Clavo
( 68/8°194 mm) Clouer
12°
(305 mm)
6.4.2 Installation of Timbertex Premium Ridge Cap Shingles shall comply with GAF current published instructions
with a minimum two (2) nails, minimum 3/8-inch head diameter, per shingle and beads of Sonneborn NP1
Gun Grade Polyurethane Sealant or Henkel PL Roofing and Flashing Sealant.
1 t 5° sealsIA
1� (292 rnm( � j� ollanle
rrnnI $25rnrw' Er,
dailtdWarchdirA
�x'3i F
} 4
la,
uer
(22A MMD
1�
6.4.3 Fasteners shall be in accordance with GAF published requirements, but not less than FBC 1507.2.6 or
R905.2.5. Staples are not permitted.
Research and Design, I.I.C.
a of Authorization r19503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION
GAF Asphalt Roof Shingles
Evaluation Report 01506.01.08-R22
FL10124-R20 +
Revision 22: 09/20/2017
Page 5 of 6
,l I RINITY I ERD
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1 / R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 61G20-3 QA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC — QUA9625; (847) 664-3281
- END OF EVALUATION REPORT -
Exterior Research and Design, I.I.C. Evaluation Report 01S06.01.08-1122
Certificate ojAuthorization #9503 CH EDITION (2017) FBC NON-HVHZ EVALUATION FL10124-R20
GAF Asphalt Roof Shingles Revision 22: 09/20/2017