Product Evaluation Report RECEIVED
GULF COAST SUPPLY & MANUFACTURING, LLC
JUL 19 e"013
26 Ga. 5V Crimp Roof Panel over 15132" Plywood ST. Lucie County, Pernim.ing
i MESS P4NS AND ALL PROPOSED WORK Florida Product Approval #11651.13 R3
Am SUDJ T TO ANY CORRECTIONS Florida Building Code 2017
REQUIRED i�Y FIELD INSPECTORS TWAT Per Rule 61 G20-3 COT. LUC'E !'!aTTICT•; BUI? Dr;� !ON
Method: 1 -D REVIEWED FOR C©AIP �l�T
I',,�AY BE N CESSARY IN ORDER TO az;;vI�tviv �
COMPLY l TH A tMl!" POD, i` DATE
Category: Roofing PLAINS AND PERMIT NWST BE KEPT OSi JOD
Subcategory: Metal Roofing cry PTO MPECTION IV _ L U 11IA E.
Compliance Method: 61 G20-3.005(1)(d)
.ARE THE RESPONSIBILITY OF THE NON HVHZ
TRACTOR OF RECORD
Product Manufacturer:
Gulf Coast Supply & Manufacturing, LLC.
14429 SW 2nd Place, Suite G30
Newberry, FL 32669 ��% PN1EL S, k/11
Engineer Evaluator:
Dan Kuhn, P.E. #75519
Florida Evaluation ANE ID: 10743
Validator:
Locke Bowden, P.E. #49704
9450 Alysbury Place
Montgomery, AL 36117
Contents:
Evaluation Report Pages 1 — 5
11651.13 R3 • OCTOBER 5, 2017
� •��c�Ns� titi,,
* ' No. 7551.9 -
;� -• STATE OF : Q
1. All
s A IGN.
O VA L ,VN `1D/o5/202
7t F r R� M� •.laY IY. IJ �h. ♦i,.
NX
kRIDA , Gulfcod t
SUPPLY & MANUFACTURING
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2017, Sections 1504.3.2.
Product Description: 5V Crimp Roof Panel, 26 Ga. Steel, 24" Coverage, through fastened
roof panel with fasteners in the panel flat over minimum ,5/32" plywood decking.
Non Structural application.
Panel Material/Standards: Material: Minimum 26 Ga. Steel, ASTM A792 or ASTM A653 G90 conforming to
Florida Building Code 2017 Section 1507.4.3.
Paint Finish Optional
Yield Strength: 80.0 ksi
Corrosion Resistance: Panel Material shall comply with Florida Building
Code 2017, Section 1507.4.3.
Panel Dimension(s): Thickness: 0.018" Minimum
Width: 24" Coverage
Rib Height: 3/8" {Major Rib
Panel Fastener:
Substrate Description:
Design Uplift Pressures:
11651.13 R3 • OCTOBER 5, 2017
#9-15x1.5" with sealing washing in the flat of the panel or approved equal,
1/4" minimum penetration through plywood.
Corrosion Resistance: Per Florida Building Code 2017, Section 1506.6, 1507.4.4
Minimum 75/3z" thick, APA Rated plywood over supports at maximum 24" O.C.
Design of plywood and plywood supports are outside the scope of this
evaluation. Must be designed in accordance w/ Florida Building Code 2017.
Table "A"
Maximum Total Uplift Design_ Pressure
94.25 psf;
131.0 psf
Fastener Pattern
12"-12"
9.5"-2"-9.5"
Fastener Pattern Spacing
16" O.C. `
16".O.C.
Design Pressure includes a Safety Factor = 2.0.
L
FLORIDA P.. , APPROVAL G6iCoakt
'11SUPPLY & MANUFACTURING
5V
26 • 5VCRIMP ROOF PANEL OVER • •
TM
Code Compliance: The product described herein has demonstrated compliance with. the
Florida Building Code 2017, Sections 1504.3.2.
Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2017, as relates to Rule 61 G20-3.
Performance Standards: The product described herein has demonstrated compliance with:
• UL 580-06 - Test for Uplift Resistance of Roof Assemblies
• UL 1897-12 - Uplift Test for Roof Covering Systems.
Reference Data: 1. UL 580-94 / 1897-98 Uplift Test
Force Engineering & Testing, Inc. (FBC Organization # TST-5328)
Report No. 117-0053T05 & 117-0331T-08
2. Certificate of Independence
By Dan Kuhn, P.E. (FL# 75519) ® Kuhn Engineering, LLC
(FBC Organization # ANE ID: 10743)
Test Standard Equivalence: 1. The UL 580-94 test standard is equivalent to the UL 580-06 test standard.
2. The UL 1897-98 test standard is equivalent to the UL 1897-12 test
standard.
Quality Assurance Entity: The manufacturer has established compliance of roof panel products in
accordance with the Florida Building Code and Rule 61 G20-3.005(3) for
manufacturing under a quality assurance program audited by an approved quality
assurance entity.
Minimum Slope Range: Minimum Slope shall comply with Florida Building Code 2017, including
Section 1507.4.2 and in accordance with Manufacturers recommendations. For
slopes less than 3:12, lap sealant must be used in the panel side laps.
Installation: Install per Manufacturer's recommended details.
Underlayment: Shall comply with Florida Building Code 2017 section 1507.1.1.
Roof Panel Fire Classification: Fire classification is not part of this acceptance.
Shear Diaphragm: Shear Diaphragm values are outside the scope of this report.
11651.13 R3 • OCTOBER 5, 2017
G 6 li'CWoa �'t
SUPPLY & MANUFACTURING
TM
Design Procedure: For roofs within the parameters listed on the load table, fastening pattern must
at a minimum meet those listed for the applicable wind zone. For all roofs outside
the parameters listed on the load table, design wind loads shall be determined
for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10
using allowable stress design. The maximum fastener spacing. listed herein shall
not be exceeded. This evaluation report is not applicable in High Velocity
Hurricane Zone. Refer to current NOA or HVHZ evaluation report for use of this
product in High Velocity Hurricane Zone.
11651.13 R3 • OCTOBER 5, 2017
Gu"If C&&
SUPPLY & MANUFACTURING
ENGINEER LOAD TABLE: 26 Ga..5VCrimp Roof Panel over 15/32" Plywood
Buildi'ngs having a Roof Mean Height 5 20'-0"; Roof Slope: 2"A2" - 12"/12". Gable or Hip Roof; Wind Speeds 1.20-
180rriph, Exposure C, Risk Category II, Enclosed Building, based on Florida Building Code 2017.
120
130
140
150
160
170
180
WII
D
FASTENER
.SUBSTRATE
SP
D
(MIN.
Penetration)
(MIN. 15/32")
ON CENTER
ON CENTER
ON CENTER
ON CENTER
ON CENTER
ON CENTER
ON CENTER
SPACING
SPACING
SPACING
SPACING
SPACING
SPACING
SPACING
ZONE 1
#9-15x1.S"
Plywood
16" TYPE 1
16" TYPE 1
16" TYPE 1
16" TYPE 1
16" TYPE 1,
16" TYPE 1
16" TYPE 1
ZOI IE 2
,
#9-15x4.5"
Plywood
16" TYPE 1
16" TYPE 1
16" TYPE 1
16" TYPE 1
16" TYPE 1
16"-TYPE 1
16" TYPE 1
ZONE 3
#9-15x1.5"
Plywood
16" TYPE 1
16" TYPE 1
16" TYPE 1
16" TYPE 1
16" TYPE 1
16" TYPE 2
16" TYPE 2
1.).P�iNEL DESCRIPTION: 5V CRIMP, MIN. 26 GA., GRADE 80, 24"COVERAGE.
2.) PANEL FASTENER: #9-15X1.5" HWH WITH SEALING WASHER W/ MIN. 'A" PENETRATION.
3.) 'AXIMUM ALLOWABLE PANEL UPLIFT PRESSURE: -94.25 PSF® 16" O.C. FASTENER SPACING TYPE 1 FASTENER PATTERN, -131.0
PSF 116" O.C. FASTENER SPACING TYPE 2 FASTENER PATTERN BASED ON TAS 125, UL 580/UL 1897 TESTING.
4.) P, Y OOD DECKING: MIN. 's/a2" THICK PLYWOOD MUST BE DESIGNED IN ACCORDANCE WITH FLORIDA BUILDING CODE 2017.
5.) R , OF SLOPE: ON ROOF SLOPES LESS THAN 3:12, LAP SEALANT MUST BE USED IN PANEL SIDE LAPS.
6.) LI AD TABLE BASED ON WIND PRESSURES CALCULATED PER ASCE 7-10 (KD = 0.85) MULTIPLIED BY 0.6 PER FLORIDA BUILDING
CODI 2017.
ZONE 2 HIP ROOF ,a Note: Dimension (a) is defined as 10% of the minimum width of the building or
ZONE 3- 40% of the mean height of the roof, whichever is smaller, however, (a) cannot be
a
� - - �• less than either 4% of the minimum width of the building or 3 feet.
--RIDGE
-----------—ZONE1
/—--\i— —�\ �—\�-
\ iI
ZONE 2 GABLE ROOF
--�—---=-------------1 - 5a.
I 1
I I
RIDGE
+----------------------4 a
I
ZONE
i I
—ZONE 3 `- EAVE
11651.13 R3 at OCTOBER 5, 2017
TYPE 1 FASTENER PATTERN
�=l
115 x 1-1/2" HWH w/Sealing Washer
2" 12"
f
At Panel Lap
TYPE 2 FASTENER PATTERN
(1) #9-15 x 1-1/2" HWH w/Sealing Washer