Loading...
HomeMy WebLinkAboutENGINEERINGGENERAL NOTES 1. DESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS: 1. THE 2017 FLORIDA BUILDING CODE, 6TH EDITION SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2. ASCE 7-10. & SEI7 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4. ACI318 CONCRETE REFRENCE MANUAL. 5. PCI PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM 1 WIND LOADS: 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: C 3. SCREENED ROOF ENCLOSURE FBC 2017 CH. 20 TABLE 2002.4 ALUMINUM SPECIFICATIONS: 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE SPECIFIED. ANNED 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WI Qy #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050".. Lb m9e cQuntv 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE . WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. FASTNER SPECIFICATIONS: 1. FASTNERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG.) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. E ENT USE 1/4"X3 1/2" GALV LAG CONCRETE & FOUNDATION DESIGN: 3. WHERE WOOD DECK IS PR S - 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE SPECIFIED. REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE 4. 1 "X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST APPLICABLE: A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE 1/4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS FOLLOWING COMPONENTS: B. FOR WOOD APPLICATION USE #14X2-3/4" WOOD SCREW AT I. PORTLAND CEMENT TYPE 1 - ASTM C 150 24" O.C. AND 6" FROM ENDS. II. AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 C. FOR ALUMINUM APPLICATION USE #10X1-1/2" SMS OR TEK III. AIR ENTRAINING +/- 1 % - ASTM C 260 SCREW AT 24" O.C. AND 6" FROM ENDS IV. WATER REDUCING AGENT - ASTM C 494 D. WHERE VX2" INSTALLED THROUGHOUT AN "OPEN VIEW" V. CLEAN POTABLE WATER SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS VI. OTHER ADMIXTURES NOT PERMITTED MASONRY SPECIFICATIONS: B. METAL ACCESSORIES SHALL CONFORM TO: I. REINFORCING BARS - ASTM A615, GRADE 60 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD II. WELDED WIRE FABRIC - ASTM A185 HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" ON TYPE M OR S MORTAR. OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT 2. ALL MORTAR SHALL BE TYPE M OR S. PERMITTED. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING INCLUDING HOT WHEATHER RECOMMENDATIONS. REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. HEIGHT. ; F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE MISCELLANEOUS: FBC. 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC BARRIER. R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. FOOTING SIZE: EXISTING CONCRETE SLAB. NO ADDITIONAL 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH SLAB (3000 PSI) IS PROVIDED IN SOUND CONDITION, FREE WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO FROM STRUCTURAL CRACKING, SPALLING & OTHER ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER 3. DOOR LOCATION_ MAY BE_RELOCAT_ED_ BY C_ ONTRAGJO_RAN =- =--= _ CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE - -=VERIFIED=6Y€ONTRAGTOR SER=TYPICAL-F'OOTINdDETAILS 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. . SHALL EPDXY TO DECK OR GROUT TO DECK W/3000 PSI 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, GROUT WITH BONDING AGENT. DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED (OR EQUAL) TYP. ALL LOCATIONS: STRUCTURE. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO 6. ALL 2X4 & GREATER ARE TO BE SMB UNLESS OTHERWISE INDICATED EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ RESPONSIBILITIES: NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING NOTED. CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. IFS/ / _ v__I�i ST. LUCIE COUNTY BUILDING DIVISION REVIEWED FOR COMPLIA REVIEWED BY// DATE SlI( PLANS AND PE MIT MUST BE KEPT ON UOB OR NO INSPECTION WILL BE MADE LEGEND: (ALL MAY NOT APPLY) o H SCR = SCREEN ca KIP = KICK PLATE O U PW = PICTURE WINDOW v o X = HORIZ. SLIDING WINDOW�- O = HORIZ. STATIONARY WINDOW o DH = DOUBLE HUNG WINDOW = SH= SINGLE HUNG WINDOW -A SIP = SOLID INSULATED PANEL o CT = CABLE TIE o-- VV � SG = SUPER GUTTER a- s nu :c ZUOS U�-- CS =CLEAR SPAN w; d=j �u `tj z KB = KNEE BRACE ALUMINUM MEMBERS DIMENSIONS ui Lu Ci >- �8 HOLLOW SECTIONS Ec 2 x 2: 2"x2"x0.044" 2 x 3: 2"x3"x0.044" 2 x 4: 2"x4"x0.044" 2 x 5: 2"x5"0.050" s = OPEN BACK SECTIONS o 1 x 2: 1 "x2"x0.044" r 1 x 3: 1 "x3"x0.044" oc o m SNAP SECTIONS o CID 2 x 2 SNAP: 2"x2"x0.050" 2 x 3 SNAP: 2"x3"x0.050" ' ac 2 x 4 SNAP'_ 2'_x4-''- - -x0.045_ = = t� SELF MATING (SMB) , a"'i 2 x 4 SMB: 2"x4"x0.044"x0.100" a 2 x 5 SMB: 2"x5"x0.050"x0.100" o c� 2 x 6 SMB: 2"x6"x0.050"x0.120" 2 x 7 SMB: 2"x7"x0.057"x0.120" 2 x 8 SMB: 2"x8"x0.072"x0.124" 2 x 9 SMB: 2"x9"x0.082"x0.124" 2 x 10 SMB: 2"x10"x0.092"x0.398" NOTE: AS INDICATED ABOVE ALL MEMBER PROFILES ARE I D IN INCHES. A MR C u r T I I Em f-mm. } -� �11111111F111//// 'co o O p: J a =::D'w . Z z° ; W c9 U d.. rJn m V Nz LL � W Q Z / V I- z Q W _ Q 2 0 H C0 OLo J ,qt LL C) co m cM p o U p U j � LL Lo ' L N LLI M C F_ 0 d N 2 � U a. N 00 0 w U U ti rn ti oo V_ W Q YLL I­_Z Q W_ �U Q W o J LL o QoU) co a W w U' M 0_. z 0 O 0 w a DESIGN DATE: 07/16/2018 REVISION 1: DATE PAGE: I REVISION 2: DATE SCALE: NTS THESE PLANS WERE PREPARED BASED 01, PREMISE THAT THE EXISTING STRUCTURE WAS DESIGNED BY A PROPERLY LICENSED PROFESSIONAL ENGINEER OF THE STATE OF FLORIDA, WAS PERMITTED BY THE APPROPRIATE PERMITTING AGENCY, WAS CONSTRUCTED BY A FLORIDA LICENSED CONTRACTOR AT THE TIME OF CONSTRUCTION, HAS NOT BEEN SUBJECT TO DAMAGE BY MAJOR EVENT, AND HAS BEEN CERTIFIED BY THE CONTRACTOR THAT THE EXISTING STRUCTURE CURRENTLY SHOWS NO DEVIATIONS OR DEFECTS FROM THE STATE OF THE STRUCTURE AS PERMITTED BY THE FINAL INSPECTION OF THE PERMITTING AGENCY. ALSO, THE OWNER AND ALL PARTIES CONCERNED WILL INDEMNIFY FLORIDA ENGINEERING LLC FROM ANY DAMAGES OR CHANGES TO THE EXISTING STRUCTURE AS A -RESULT OF ANY MODIFICATION OR FOR ANY OTHER REASON. 3X3X.125 - o C/) �t Q0 x N 3X3X.125 m co Z U) a� O m CDQ N -1 0 N Z D 3X3X.125 O LL CD z m c/) - C° x U) W X N 3X3X.125 �81-0"� I NEW BREEZEWAY! L —8'-0 0 NEW CARPORT m U) x 3" X .024" X 1 LB `"' COMPOSITE PANELS 3003-H154 1/4"-1' SLOPE (MIN.) (FL.# 7561.1-R4) j� EXISTING APPROVED SCREEN ROOM m :53- c - x o N 3X3X.125 POST, TYP. 9 PLCS. Ire, EXISTING APPROVED SHED O O N -------------- = 6'-0"-------- N E K L0 Ln�A O D P* P RO�%RD� O N N XV� V ����� �� O oo 7 M cx M \ ti M ci EXISTING FOUNDATION 8'-0" 1'-011 .1 8'-0" 6'-0l� 33'-0" O z D O O LL r- Z m w •� •((/ N LL •, W / LLI •GO o - O O w Q o -� :U y '> z 6' ........p... ��' r w V z E W rz V w Q 0 LL O co rn cM M p U cl� p U O� LL. Lo L W M c: cy)o N 2 � O 0- z i- :5.- U N 00 r- 0 M w 0 U O z H U W O Q Y� z_ LL Q w_ Ui U QW J h- ¢ Q d. U) w F w O LLI (D M D- 0 of a DESIGN DATE: 07/16/2018 REVISION 1: DATE PAGE: REVISION 2: DATE n SCALE: NTS L Q / w BEAM PER PLAN o I BEAM PER PLAN F (2) EA. 1/4" 0 STL BOLTS OR BEAM PER PLAN (2) 3/8" 0THRU-BOLT #12X3/4" TEKS EA. SIDE SEE ALSO COUEDGE 0: / QUANITY = BEAM SIZE BEAM ALTERNATES cl) (EXAMPLE FOR 2X6 USE: (6) #12) F- -1 ----------------------------- 0 2" X 1/8" RECEIVING CHANNEL POST 2" X 1/8" REC CHANNEL W/ #12 SMS (QUANITY= BEAM SIZE) W/ (2) 3/8" O STL BOLTS OR #12X3/4" TEKS EA. SIDE COL. PER PLAN FOR ALUMINUM PANS OR GALVALUME STEEL PANS USE #12 X 9/16" W/ 5/8" NEO-WASHER (3) PER PAN (2" MIN. EMBED.) INTO HOST STRUCTURE (WOOD) OR QUANITY = BEAM SIZE 1/4" 0 TAPCONS X 2-1/4" @ 1-1/2" O.C. STAGGERED (EXAMPLE FOR 2X6 USE: (6) #1 FOR COMPOSITE PANELS #12 X 1" LG. THAN PANEL THICKNESS SMS W/ 1-1/2" NEO-WASHER 12" 0/C (MIN. OF 2 PER CONN.) OR 2"X2"X.050" ANGLE EA. SIDE OF BEAM FASTENED SAME AS CHANNEL. BEAM TO WALL SCALE: N.T.S. BEAM TO COLUMN SCALE: N.T.S. FOR ALUMINUM PANS OR GALVALUME STEEL PANS USE #12 X 9116" W/ 5/8" NEO-WASHER (3) PER PAN FOR COMPOSITE PANELS #12 X 1" LG. THAN PANEL THICKNESS SMS W/ 1-1/2" NEO-WASHER 12" O/C COVER END OF PANEL ,, L ROOF PER PLAN PER PLAN (2) 3/8" THRU-BOLT BEAM PER PLAN u ST PO COL. PER PLAN ROOF TO CARRIER BEAM CONNECTION SCALE: N.T.S. 24GAALUMINUM FLASHING #8 SMS W/ 5/8" CEO- \ / WASHER 12" O/C \`Jr FOR ALUMINUM PANS OR GALVALUME STEEL PANS USE #12 X 9/16" W/ 5/8" PLAN NEO-WASHER (3) PER PAN ROOF PER FOR COMPOSITE PANELS #12 X 1" LG. j THAN PANEL THICKNESS SMS W/ 1-112" NEO-WASHER 12" O/C (2) 3/8" THRU-BOLT BEAM PER PLAN u ADJACENT MOBILE HOME POST COL. PER PLAN I 1/2" CLEARANCE 4TH WALL / ROOF TO C.B. CONNECTION SCALE: N.T.S. J WOOD FRAME WALL PER PLAN w `` DETAIL: ROOF PANEL ATTACHMENT TO WD FRAME WALL SCALE: N.T.S. (4) 3/8"x4" TAPCON THRU BOTTOM LEG OF ANGLE INTn rntir. � T f VAA�11111111111I//////7 _ z o O O: J U Q :Z y '> )\`O m CO J cy) V ~ co Z Z Q E \ _ O p U Lu 0 06 � W LL.Lo '� w Z w 0 Q F_ U LO li O LO LL N O O O W a 00 N c � U O w W m Q (2) 3/8" DIA EXPANSION BOLTS ' (4) 1/4"x3" TAPCON THRU BOTTOM LEG OF ANGLE INTO CONC. 2" 2" FROM EDGE ( ® 2" FROM EDGE j�T14 OF SLAB ` 2" FROM EDGE OF SLAB ` OF SLAB SEE MFG. GUIDELINES 1" FOR ANCHOR SPACING/ SETBACK REQUIREMENTS z _ TOP VIEW TOP VIEW 3X3 POST PER PG. 2 2 V A (2) 1/4" DIA MACHINE A T(1P \/IF1A/ SE3/8" DIA PSION E NOTE #E1 THIS PAGEBOLTS FOR BOLT PLACEMENT 125 ANGLE FRONT VIEW MIN. 3000 PSI CONC. FTG/SLAB W/ 6x6 -10x10 W.W.M. OR FIBERMESH (TYP.) YxY POST CONNECTION DETAIL OPTION #1 SCALE: N.T.S. (4) 1/4"x3" TAPCON THRU (LENGTH) ANGLE THRU BOTTOM LEG (INTERNAL) OF ANGLE INTO CONC. I I FRONT VIEW MIN. 3000 PSI CONC. FTG/SLAB W/ 6x6 -10x10 W.W.M. OR FIBERMESH (TYP.) YxY POST CONNECTION DETAIL OPTION #2 SCALE: N.T.S. (3) 1/4" DIA MACHINE BOLTS wANASHERS (4) 3/8"x4" TAPCON THRU BOTTOM LEG OF ANGLE INTO COI 1/8"x2"x2"x33/4" (LENGTH) ANGLE (INTERNAL) ............. . FRONT VIEW 4"x4" POST CONNECTION DETAIL SCALE: N.T.S. MIN. 3000 PSI CONC. FTG/SLAB W/ 6x6 - 10x10 W.W.M. OR FIBERMESH (TYP.) N n 0 W U U ti ti 00 T- z LL W �0 Q 0 W Q J LL O a Q Q U d I W w U` cm a z O 0 Of DESIGN DATE: 07/16/2018 REVISION 1: DATE PAGE: 3 REVISION 2: DATE SCALE: NTS