HomeMy WebLinkAboutBUILDING PAGE PAGE 1-14• STATE OF FLORIDA
CERTIFIED BUILDING
CONTRACTOR:
DR HORTON HOMES
1430
CULVER DRIVE NE
PALM
BAY, FL 32907
TEL:
(321) 733-7092
FAX:
(321)
733-7972
• STATE OF FLORIDA
PROFESSIONAL ARCHITECT:
ROLAND A. ABOUCHACRA
AR No. 93723
A.B. DESIGN GROUP, INC.
1441 NORTH RONALD REAGAN BLVD.
LONGWOOD, FLORIDA 32750
Tel: (407) 774-6078
Fax: (407) 774-4078
DRAWING / CONTRACT DOCUMENT
THE BUILDER ASSUMES ALL LIABILITY FOR
INTERPRETATION OF THE CONTRACT DOCUMENTS.
IF ANY ASPECT OF THE CONSTRUCTION (AS
DESCRIBED IN THIS DRAWING SET) ARE UNCLEAR
AND IN NEED OF FURTHER DETAILING OR
EXPLANATION IN ORDER TO BUILD THIS PROJECT
BASED ON THIS DRAWING SET, THE CORRECT
PROCEDURE IS FOR THE BUILDER TO SUBMIT A
WRITTEN R.F.I. (REQUEST FOR INFORMATION) TO
THE ARCHITECT OR ENGINEER FOR CLARIFICATION.
AB DESIGN GROUP WILL RESPOND TO ALL WRITTEN
RFI's IN WRITTEN DRAWN FORMS IN A TIMELY
MANNER. AB DESIGN GROUP TAKES NO
RESPONSIBILITY FOR INTERPRETATIONS OF
CONSTRUCTION BY THE BUILDER WHEN NO RFI's
HAVE BEEN GENERATED FOR UNCLEAR ASPECTS OF
THE CONSTRUCTION BASED ON THE DRAWING SET.
i
1430 CCUILVER [DRIVE NE, PALM BAY, FL 32907
Tel= (321) 733-7092
DESIGN CRITERIA:
• FBC RESIDENTIAL 6TH EDITION (2017) ABC
• FLORII)A FIRE PREVENTION CODE 6TH
EDITION
ADJ.
• NATIONAL ELECTRICAL CODE (NEC) —
2014 EDITION
AMP.
.ALL LOCAL AND
STATE CODES
BD.
CL
• OCCUPANCY
- RESIDENTIAL, GROUP
R3
B.
CLG
• CONSTRUCTION TYPE
- VB
CLR.
• MIN. INTERIOR FINISH
— CLASS B
cFc.
• BASIC WIND SPEED
— Vult=160 MPH
C.T.
D.
Vasd=124 MPH
DBL.
• EXPOSURE
— C
D.G.
DIA.
• 1-STORY RESIDENCE
-
DIM.
• 2-STORY RESIDENCE
- MAX. HEIGHT AS PER
LOCAL
DISP.
DP.
AND STATE CODES
DR.
D.S.
SQ.FT. CALC.'
D W.
EA.
TOTAL 3031 S. FT.
A/C VOLUME 20211.2
ELEV.
EQ.
EXH.
EXT.
F.G./FX .
F.G.
FIN.
FLR.
FLUOR.
FR. DR.
FTG.
GA.
GAR. DISP
G.F.I.
GL.
1 GYP. BD.
H.B.
H.C.
HDR.
HOT. OR HT
INSUL.
INT.
LAV.
LUM.
M.C.
Fax: (321) 733-7972
ABBREVIATIONS
ABOVE
MFR.
MANUFACTURER
AIR CONDITIONING
MIN.
MINIMUM
ADJUSTABLE
M.T.
METALTHRESHOLD
ALTERNATE
MTD.
MOUNTED
AMPERAGE
MTL.
METAL
BOARD
N.T.S.
NOT TO SCALE
CENTER LINE
O.C.
ON CENTER
CABINET
PL
PROPERTY LINE
CEILING
P.B.
PUSH BUTTON
CLEAR
PH.
PHONE
CONCRETE
PLT.
PLATE
CARPET
PLYWD.
PLYWOOD
CERAMIC TILE
PR.
PAIR
DRYER
P.T.
PRESSURE TREATED
DOUBLE
R.
RISER
DUAL GLAZED
RAD.
RADIUS
DIAMETER
R.A.G.
RETURN AIR GRILL
DIMENSION
REF.
REFRIGERATOR
DISPOSAL
RM.
ROOM
DEEP
R.O.
ROUGH OPENING
DOOR
S.C.
SOLID CORE EXT DR
DOWNSPOUT
S.D.
SMOKE DETECTOR
DETAIL
S.H.
SINGLE HUNG
DISHWASHER
SHT.
SHEET
EACH
SHTHG.
SHEATHING
ELEVATION
SHWR.
SHOWER
EQUAL
SIM.
SIMILAR
EXHAUST
SL.
SLIDING
EXTERIOR
SL. GL.
SLIDING GLASS
FIXED GLASS
STD.
STANDARD
FUEL GAS
SWS
SHEAR WALL
FINISH
SECTION
FLOOR
TEMP.
TEMPERED GLASS
FLUORESCENT
THK.
THICK
FRENCH DOOR
T.O.C.
TOP OF CURB
FOOTING
T.O.P.
TOP OF PLATE
GAUGE
T.O.S.
TOP OF SLAB
GARBAGE DISPOSAL
TYP.
TYPICAL
GROUND -FAULT
U.N.O.
UNLESS NOTED
CIRCUIT INTERRUPTER
OTHERWISE
GLASS
V.P.
VAPORPROOF
GYPSUM BOARD
W.
WASHER
HOSE BIB
W/
WITH
HOLLOW CORE
WD.
WOOD
HEADER
WDW.
WINDOW
HEIGHT
W/H
WATER HEATER
INSULATION
W.I.
WROUGHT IRON
INTERIOR
LAVATORY
LUMINOUS
MEDICINE CABINET
DATE
REVISIONS
INDEX OF DRAWINGS
ARCHITECTURAL SHEET
PG Cl—COVER SHEET
PG GN—GENERAL NOTES
PG Al —FIRST FLOOR PLAN
PG AIA—FLOOR PLAN SECTIONS/DETAILS
PG A2—SECOND FLOOR PLAN
PG A311—ELEVATIONS FRONT & REAR "H"
PG A411—ELEVATIONS LEFT & RIGHT "H"
PG Ei—FIRST FLOOR ELECTRICAL PLAN
PG E2—SECOND FLOOR ELECTRICAL PLAN
PG Ml—FIRST FLOOR MECHANICAL PLANS
PG M2—SECOND FLOOR MECHANICAL PLANS
PG P1—PLUMBING PLAN
PG DI —DETAILS
PG D2—DETAILS
PG D3—DETAILS
PG D4—PRODUCT APPROVALS
PG WAl—WALL ASSEMBLY DETAILS
PG WA2—WALL ASSEMBLY DETAILS
PG WA3—WALL ASSEMBLY DETAILS
PG WA4—WALL ASSEMBLY DETAILS
PG WA5—WALL ASSEMBLY DETAILS
PG WA6—WALL ASSEMBLY DETAILS
STRUCTURAL SHEET
PG Sl—FOUNDATION PLAN
PG SIAA—DETAILS
PG SLIB—DETAILS
PG S1.2—FIRST FLOOR DOWEL PLAN
PG S1.2A—DETAILS
PG S2—FIRST LIFT BEAM PLAN AND NOTES
PG S2.1A—DETAILS
PG S3—FIRST FLOOR FRAMING PLAN
PG S3.1A—DETAILS
PG S3.1B—DETAILS
PG S4—SECOND FLOOR PLAN
PG S4.1A—DETAILS
PG S4.2—SECOND FLOOR DOWEL PLAN
PG S5—SECOND LIFT BEAM PLAN AND NOTES
PG S6—ROOF FRAMING PLAN
PG S6.1A—DETAILS
PG SNl—DETAILS
DESCRIPTION
JUL 2 7 2018
Permitting uepartment
St. Lucie County, FL
DESCRIPTION
1441 N. RONALD REAGAN BL
LONGWOOD, FL 32750
PH: 407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
AA #: 0003325
F
W
U
W
�
may..
O
h
A
W
F
�
Ln
r
StJHDIV. 'k LOT:
CREEKSIDE
LOT #61
PROJECT
04321.000 061R1
MODEL:
4EGB
"GALEN"
GARAGE SWING:
RIGHT
PAGE:
COVER
SHEET
L160 MPH EXP.
ARCHITECT -
STATE OF FLORIDA
K
DATE: 06 /13/18
SCALE: 1/4"=1'-0"
_�
ci
U3
in t
J
..I
11T
ZI Z
zUj
ga
FLAME SPREAD AND SMOKE INDEX FOR WALL AND CEILING FINISHES SHALL BE IN
ACCORDANCE WITH SECTION FSC R302.9.1 THROUGH FBC R302.9.4
FLAME SPREAD AND SMOKE -DEVELOPED INDEX FOR INSULATION SHALL BE IN
ACCORDANCE WITH SECTION FBC R302.10.1 THROUGH FBC R302.10B
m
.)i
Ld
IF
38' -8"
4'
T_4' _4"
I
I
C
I
LAVERENAID
8-8' 11'-4"I
9'-0"TOND1
I
3052-SH
(2) 3052-SH
KIT-
6068 CsD
`q
I
I
29'-2'
I
GREAT
I
II
A
O
II
ROOM DINING
I
1
OIO
8'-8' cLG
8'-8' cLG.
j
KITCHEN
I I •
'n 8'.8, �
V
CONT.
I
HANDRAILIlia::`
0
I
42' H. HALF
' `
WALL W/ CAP
I
-----
OPT.
I'-s"
I
n
REF
�j
`"'-8"
4'-(D'
8'-8"
5'-0"
5'-8"
4'-0" i�3'-0
`Oa`7\
2X8
C. ---
?.
8
I
I I I I I
I STOR.
m
uP I
I I I I I
I
INK
A
ti.�+ C �o
PAN,
PWDR.
8'-8' CLG 3-SH
O
STAIR DATA
iryT.�\`a
I6 RISERS * -tB4'
15 TREADS 0 10'
�IIV
+1' NOSING
III
BOLLARD
III
III
PER�BLDG.
B
II
FLEX
CODE
Q' All
8'-8' CLG.
GARAGE
III
8'-8' CLG.
FOYER pl
V-e' CLa- III
3068 W/
36'XIO' TRANS. MT
(2) 3052-W
ENTRY
—
— — — — — — — — — — — — —
16'-0'X7'-O'O.HD.
— — — — — —
8'-8' CLG
-
2'-8'
-0"
21'-4"
I71_4"
FIRST FLOOR PLAN
SCALE: 1/4 IN 1'-0'
ki
m
1
SQ.FT.
CALC.'S
IST FLR LIVING
2ND FLR LIVING
1019
1413
SQ. FT.
SQ. FT.
TOTAL LIVING
GARAGE
LANAI
FORCN
2432
432
80
81
SQ. FT,
SQ. FT.
SQ. FT.
SQ. PT.
TOTAL
3031
SQ. FT.
" VOLUME
20211.2
A"
COIrP0 M AND CLADDNO WND LOADS
MW WND BPOBIAiE FOR B BECOFD OUSTS
OPom
AN) r PE
BOUAFE
FOOTAGE
210PE
10D WH WI'D MA
FE MAWGB
MIN. WINDOW
10
5
34/-45
CRITERIA
EXTERIOR SWING
21
5
32/-42
OR. MIN. CRITERIA
SGP. MIN.
12
5
30/-3'i
CRITERIA
80iv O.H.D.
56
5
30/-38
160-to O.H.D.
112
5
211
SOFFIT
N/A
5
31b/-38.8
-6815
IF
IF
ROOF TILE
N/A
3
-58.2s9
BASIC WIND SPEED MPH = 160 (Vult) INTERNAL
PRESSURE COEFFICENT = t 0.18 BLDG. CAT.=II,
EXP.=C, MEAN ROOF HT. = 23'-0'
PRESSURES HAVE BEEN MODIFIED PER FBCR R301.2.1
TO MEET TESTED ALLOWABLE OR NOMINAL WIND LOAD
VALUES FROM THE PRODUCT MANUFACTURER.
MASONRY /FRAME
WALL LEGEND
8'-8' BLOCK WALL
UNA ON PLANS
BRCS. HGT. VARIES
8' BLOCK WALL
UNA ON PLANS
IS'-8' BRG.
INTERIOR LOAD
BR!s. WALL U.N.O.
ON PLANS
INTERIOR �_�
LOAD BFYs. WALL
U.N.O. ON PLANS
-ALL INTERIOR
DOORS TO BE 6'-8'
-ALL EXTERIOR
DOORS TO BE 6'-8'
UNLESS NOTED
OTHERWISE
NOTE-
-2-8 LOUV. DOOR W/ AIR HANDLER ON METAL STAND OR 2-8 SOLID
DOOR LU/ RETURN PLENUM AND RETURN AIR GRILLE.
-VERIFY CONDENSER PAD LOCATION WITH SITE PLAN
-OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE
EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1 3/0' (35 MM)
IN THICKNESS, SOLID OR HONEYCOMB -CORE STEEL DOORS NOT
LESS THAN 1 3/8' (35 MM) THICK, OR 20-MINUTE FIRE -RATED DOORS.
-THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE t ITS
ATTIC AREA BY NOT LESS THAN 11/2'(12.1mm) GYPSUM BOARD APPLIED
TO THE GARAGE SIDE, GARAGES BENEATH HABITABLE ROOMS
SHALL BE SEPARATED FROM ALL HABITABLE ROOMS BY NOT LESS
THAN %'(15.9mm) TYPE X GYPSUM BOARD OR EQUIVALENT.
UNDER STAIR PROTECTION:
ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS,
UNDER STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE
ENCLOSED SIDE WITH 1/2 INCH GYPSUM BOARDS. FBCR 201-1 l(PTH
ED.) 3021
JUL 21 ZOlg
I Permittng [)Lp3rtment
1441 N. RONALD REAGAN BL
LONGWOOD, FL 32750
PH: 407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
AA #: 0003325
F
M
d2
y
z
0
v
63
m
r.
C
f.
d ti
3 p
s
d
q
SUHDIV. & LOT:
CREEKSIDE
LOT #61
PROJECTgj:
04321.000 061R1
MODEL
4EGB
' G ALEN"
GARAGE STnNG:
RIGHT
PAGE:
FIRST
FLOOR PLAN
60 MPH EXP.
AF> CH TECT-
STATE OF FLOFA
2
raua� a
DATE: 06/13/18
SCALE: 1 /4"=1'— 0'
SHEET
w
99
o ) Q
o )
o
z,,,,--,
STATE OF FLORIDA
CERTIFIED BUILDING CONTRACTOR:
DR HORTON HOMES
1430
CULVER DRIVE NE
PALM
BAY, FL 32907
TEL:
(321) 733-7092
FAX:
(321)
733-7972
STATE OF FLORIDA
PROFESSIONAL ARCHITECT:
ROLAND A. ABOUCHACRA
AR No. 93723
A.B. DESIGN GROUP, INC.
1441 NORTH RONALD REAGAN BLVD.
LONGWOOD, FLORIDA 32750
Tel: (407) 774-6078
Fax: (407) 774-4078
DRAWING / CONTRACT DOCUMENT
THE BUILDER ASSUMES ALL LIABILITY FOR
INTERPRETATION OF THE CONTRACT DOCUMENTS.
IF ANY ASPECT OF THE CONSTRUCTION (AS
DESCRIBED IN THIS DRAWING SET) ARE UNCLEAR
AND IN NEED OF FURTHER DETAILING OR
EXPLANATION IN ORDER TO BUILD THIS PROJECT
BASED ON THIS DRAWING SET, THE CORRECT
PROCEDURE IS FOR THE BUILDER TO SUBMIT A
WRITTEN R.F.I. (REQUEST FOR INFORMATION) TO
THE ARCHITECT OR ENGINEER FOR CLARIFICATION.
AB DESIGN GROUP WILL RESPOND TO ALL WRITTEN
RFI's IN WRITTEN DRAWN FORMS IN A TIMELY
MANNER. AB DESIGN GROUP TAKES NO
RESPONSIBILITY FOR INTERPRETATIONS OF
CONSTRUCTION BY THE BUILDER WHEN NO RFI's
HAVE BEEN GENERATED FOR UNCLEAR ASPECTS OF
THE CONSTRUCTION BASED ON THE DRAWING SET,
GN CRITERIA:
f_1An
I� l tl
1„�
III
1430 CULVER [DRIVE NE, PALM BAY, FL 32907
Tel: (321) 733-7092 Fax: (321) 733-7972
N'D1
• FBC RESIDEL 6TH EDITION (2017)
A/C �
• FLORIDA FIRE PREVENTION CODE 6TH EDITION
ADJ.
• NATIONAL ELECTRICAL CODE (NEC) — 2014 EDITION
T.
MP.
,ALL LOCAL AND STATE CODES
BD.
GL
•OCCUPANCY — RESIDENTIAL, GROUP R3
CLs.
• CONSTRUCTION 'TYPE — VB
CON
• MIN. INTERIOR FINISH— CLASS B
c.
CPT
• BASIC WIND SP5D — Vult=160 MPH
C.T.
Vasd=124 MPH
D.
DBL.
• EXPOSURE — C
D.G.
el —STORY RESID9NCE —
DM.
• 2—STORY RESIDP;NCE — MAX. HEIGHT AS PER LOCAL
DISP.
AND STATE CODES
DR.
D.S.
SQ.FT. CALC.'S
D W.
EA.
ELEV.
IST FLR LIVNG 1019 SQ. FT.
EQXH.
2ND FLR LIVNG 1413 SQ. FT.
EXT.
F.G./FX .
TOTAL LIVING 2432 SQ. FT.
F.G.
FIN.
4ARAGE 432 SQ. FT.
FLR.
PORCH 51 SQ. FT.
FLUOR.
FR. DR.
TOTAL 3031 SQ. FT.
FTG.
GA.
GAR. DISP.
A/C VOLE 202-11.2
G.F.I.
GL.
GYP. BD.
H.B.
H.C.
HDR.
HGT. OR HT
INSL'L.
INT.
LAV.
LUM.
M.C.
ABBREVIATIONS
REVISIONS
INDEX OF DRAWINGS
ABOVE MFR. MANUFACTURER
AIR CONDITIONING MIN. MINIMUM
ADJUSTABLE M.T. MRESHGLD
ALTERNATE MTD. MOUNTEDOUNTED
AMPERAGE MTL. METAL
BOARD N.T.S. NOTTOSCALE
CENTER LINE O.C. ON CENTER
CABINET PL PROPERTY LINE
CEILING P.B. PUSHBUTTON
CLEAR PH. PHONE
CONCRETE PLT. PLATE
CARPET PLYWD. PLYWOOD
CERAMICTILE PR. PAIR
DRYER P.T. PRESSUETREATED
DOUBLE R. RISER
DUAL GLAZED MD. RADIUS
DIAMETER R.A.G. RETURN AIR GRILL
DIMENSION REF. REFRIGERATOR
DISPOSAL RM. ROOM
DEEP R.O. ROUGH OPENING
DOOR S.C. SOLID CORE EXT DR
DOWNSPOUT S.D. SMOKE DETECTOR
DETAIL S.H. SINGLE HUNG
DISHWASHER SHT. SEAT
EACH SHTH(J. SHEATHING
ELEVATION SSHOWER
IM.
EQUAL Sim. SIMILAR
EXHAUST SL. SLIDING
EXTERIOR SL. GL. SLIDING GLASS
FIXED GLASS STD. STANDARD
FUEL GAS SwS SEAR WALLFINON
FLOOR TEMP. TEMPERED SH IGLASS
FLUORESCENT THE, THICK
FRENCH DOOR T.O.C. TOP OF CURB
FOOTING T.O.P. TOP OF PLATE
GAUGE T.O.S. TOP OF SLAB
GARBAGE DISPOSAL TYP. TYPICAL
GROUND -FAULT U.N.O. UNLESSNOTED
CIRCUIT INTERRUPTER OTHEVAPOR
GLASS V.P. VAPOR PROOF
GYPSUM BOARD W. WASHER
HOSE BIB W/ WITH
HOLLOW CORE WD. WOOD
HEADER WDW. WINDOW
HEIGHT W/H WATER HEATER
INSULATION W.I. WROUGHT IRON
INTERIOR
LAVATORY
LUMINOUS
MEDICINE CABINET
DATE
DESCRIPTION
ARCHITECTURAL SHEET # DESCRIPTION
PG Cl—COVER SHEET
PG GN—GENERAL NOTES
PG Al —FIRST FLOOR PLAN
PG AlA—FLOOR PLAN SECTIONS/DETAILS
PG A2—SECOND FLOOR PLAN
PG A3H—ELEVATIONS FRONT & REAR "H"
" „
PG A4H—ELEVATIONS LEFT & RIGHT H
PG El —FIRST FLOOR ELECTRICAL PLAN
PG E2—SECOND FLOOR ELECTRICAL PLAN
PG Ml—FIRST FLOOR MECHANICAL PLANS
PG M2—SECOND FLOOR MECHANICAL PLANS
PG Pl —PLUMBING PLAN
PG DI —DETAILS
PG D2—DETAILS
G D3—DETAILS
PG D4—PRODUCT APPROVALS
PG WAl—WALL ASSEMBLY DETAILS
PG WA2—WALL ASSEMBLY DETAILS
PG WA3—WALL ASSEMBLY DETAILS
PG WA4—WALL ASSEMBLY DETAILS
PG WA5—WALL ASSEMBLY DETAILS
PG WA6—WALL ASSEMBLY DETAILS
STRUCTURAL SHEET DESCRIPTION
PG Sl—FOUNDATION PLAN
PG S1.lA—DETAILS
PG SLAB —DETAILS
PG S1.2—FIRST FLOOR DOWEL PLAN
PG S1.2A—DETAILS
PG S2—FIRST LIFT BEAM PLAN AND NOTES
PG S2.1A—DETAILS
PG S3—FIRST FLOOR FRAMING PLAN
PG S3.1A—DETAILS
PG S3.1B—DETAILS
PG S4—SECOND FLOOR PLAN
PG S4.1A—DETAILS
PG S4.2—SECOND FLOOR DOWEL PLAN
PG S5—SECOND LIFT BEAM PLAN AND NOTES
PG S6—ROOF FRAMING PLAN
PG S6.1A—DETAILS
PG SNl—DETAILS
1441 N. RONALD REAGAN BL
LONGWOOD, FL 32750
PH:407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
AA #: 0003325
F
W
ct
U
W
to.-
ti
rq
rq
FH
ac LOT:
CREEKSIDE
LOT #61
PROJECT#
04321.000 061R1
MODEL:
4EGB
"GALEN"
GARAGE SWING:
PAGE:
COVER
SHEET
60 MPH EXP.
ARCHITECT:
STATE OF FLOFN
d
�p
F
w
GENERAL NOTES
1. ALL WORK DONE UNDER THIS CONTRACT SHALL BE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE RESIDENTIAL (FBCR)
6th EDITION, (2017).AND IN CONJUNCTION WITH ASCE 7-10. ALL REFERENCED CHAPTERS, CODE SECTIONS AND TABLES STATED
IN THESE DOCUMENTS ARE UNDER FBCR 6TH EDITION (2017) LINO.
2. WHERE BUILDING LOCATIONS ARE DETERMINED TO BE IN WIND BORNE DEBRIS REGIONS, ALL EXTERIOR
BUILDING OPENINGS SUCH AS WINDOWS AND DOORS SHALL BE PROTECTED AGAINST WINDBORNE DEBRIS BY
THE INSTALLATION OF STRUCTURAL PANELS OR IMPACT -RESISTANT GLASS. THESE OPENING PROTECTIONS SHALL BE
DESIGNED AND INSTALLED IN ACCORDANCE WITH CHAPTER 3, SECTION R301.2.1.2.
3. DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO WORK
PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
4. THE CONTRACTOR SHALL BRING ERRORS AND OMISSIONS WHICH MAY OCCUR IN CONTRACT DOCUMENTS TO THE ATTENTION
OF THE ARCHITECT IN WRITING AND WRITTEN INSTRUCTIONS SHALL BE OBTAINED BEFORE PROCEEDING WITH THE WORK.
THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR THE RESULTS OF ANY ERRORS, DISCREPANCIES OR OMISSIONS IN THE
CONTRACT DOCUMENTS, OF WHICH THE CONTRACTOR FAILED TO NOTIFY THE ARCHITECT BEFORE CONSTRUCTION AND/OR
FABRICATION OF THE WORK.
5. THE ARCHITECT/ENGINEER SHALL NOT BE RESPONSIBLE FOR THE SAFETY AND CONSTRUCTION PROCEDURES, TECHNIQUES,
OR THE FAILURE OF THE BUILDER TO CARRY OUT THE WORK IN ACCORDANCE WITH THE DRAWINGS OR THE REQUIRED CODES.
6. THE STRUCTURAL DESIGN IS BASED ON THE INTERACTION OF ALL PARTS OF THE COMPLETED BUILDING. THE CONTRACTOR
SHALL SOLELY BEAR THE RISK FOR PROVIDING ADEQUATE STABILITY AND SAFETY OF THE STRUCTURE DURING
CONSTRUCTION UNTIL PERMANENT MEMBERS ARE COMPLETELY INSTALLED.
7. DETAILS SHOWN ON THE DRAWINGS ARE TO BE CONSIDERED TYPICAL FOR ALL SIMILAR CONDITIONS.
8. THE CONTRACTOR SHALL MAKE NO STRUCTURAL CHANGES WITHOUT WRITTEN APPROVAL FROM THE ARCHITECT/ENGINEER.
9. NO STRUCTURAL MEMBERS ARE TO BE CUT FOR PIPES, DUCTS, ETC. UNLESS SPECIFICALLY DETAILED.
GARAGES AND CARPORTS
1 GARAGE DOOR
A. ENGINEERED FOR MIN. WIND LOAD, LISTED ON COVER SHEET
B. DETAIL TO BE SUPPLIED BY GARAGE DOOR SUPPLIER
C. DETAIL TO BE ATTACHED TO PERMIT PACKAGE BY BUILDER
2. AS PER SECTION R302.5.1: OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING
PURPOSES SHALL NOT BE PERMITTED. OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH
SOLID WOOD DOORS NOT LESS THAN 1 3/8 INCHES IN THICKNESS, SOLID OR HONEYCOMB CORE STEEL DOORS NOT LESS THAN
1-3/8 INCHES THICK, OR 20-MINUTE FIRE -RATED DOORS.
3. AS PER SECTION R302.5.2: DUCTS IN THE GARAGE AND DUCTS PEI IETRATING THE WALLS OR CEILINGS SEPARATING THE
DWELLING FROM THE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM NO.26 GAGE (0.48 MM) SHEET STEEL V MIN. RIGID
ON -METALLIC CLASS OR CLASS 1 DUCT BOARD OR OTHER APPROVED MATERIAL AND SHALL HAVE NO OPENINGS INTO THE
GARAGE.
4. AS PER SECTION R302.6 & TABLE R302.6: THE GARAGE SHALL BE SEPARATED FROM THE -RESIDENCE AND ITS ATTIC AREA BY NOT
LESS THAN''/2 -INCH GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH HABITABLE ROOMS SHALL BE
SEPARATED FROM ALL HABITABLE ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH TYPE X GYPSUM BOARD OR EQUIVALENT.
WHERE THE SEPARATION IS A FLOOR -CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE SEPARATION SHALL ALSO BE
PROTECTED BY NOT LESS THAN''/z-INCH GYPSUM BOARD OR EQUIVALENT.
`.e:
SITE WORK
1. REFER TO THE SOILS REPORT FOR SPECIFIC DESIGN REQUIREMENTS (IF REQUIRED BY BUILDING DEPARTMENT).
2. REFER TO THE CIVIL DRAWINGS FOR LOCATION OF BUILDING WORKING POINTS, ROUGH GRADING, ON -SITE UTILITIES,
SITE IMPROVEMENTS, SITE RETAINING WALLS, AND SPECIFIC GENERAL NOTES. THE SOILS REPORT AND CIVIL
DRAWINGS SHALL OVERRIDE CONFLICTS WITH SITE WORK NOTED HEREIN.SEE LANDSCAPE DRAWINGS FOR FINAL
FINISH GRADES, PLANTING AND IRRIGATION.
3. ELEVATIONS SHOWN ON THE SITE DRAWINGS ARE MINIMUM REQUIRED DEPTHS, IF DIFFERENT CONTACT THE
ARCHITECT.
4. NO EXCAVATION SHALL BE MADE WHOSE DEPTH BELOW THE FOOTING IS GREATER THAN'/ THE HORIZONTAL
DISTANCE FROM THE NEAREST EDGE OF THE FOOTING.
5. ALL BACKFILL AT STRUCTURES, SLABS, STEPS, AND PAVEMENTS SHALL BE CLEAR OF GRANULAR FILL. PLACE IN 8"
LAYERS AND COMPACT TO 95% MAXIMUM DRY DENSITY DETERMINED IN ACCORDANCE WITH ASTM D1557. THE
BUILDING SITE SHALL BE KEPT DRY SO THAT EROSION WILL NOT OCCUR IN THE FOUNDATIONS.
6. COMPACTION BY FLOODING OR JETTING IS STRICTLY PROHIBITED.
7. DO NOT BACKFILL UNTIL SLABS HAVE CURED OR HAVE BEEN PROPERLY BRACED. (WHERE APPLICABLE)
8. EXCAVATIONS TO BE A MINIMUM OF T- 0" BEYOND NEW FOOTING LINE.
9. THE GENERAL CONTRACTOR MUST TAKE MEASURES TO CONTROL SOIL EROSION AS PER ALL LOCAL AND STATE
REQUIREMENTS.
10. THIS BUILDING IS NOT DESIGNED TO BE CONSTRUCTED WITHIN A FLOOD ZONE, LINO. CONTRACTOR IS TO VERIFY THE
ELEVATION OF THE FINISHED FLOOR SLAB WITH THE SIGNED AND SEALED SURVEY WHICH COMPLIES WITH ALL LOCAL
CODES HAVING JURISDICTION, INCLUDING ALL APPLICABLE STATE, CITY, AND COUNTY BUILDING AND ZONING CODES.
11. SWIMMING POOL, DECK, SPA, AND ASSOCIATED WORK IS TO BE PERMITTED SEPARATELY BY ENGINEERED SHOP
DRAWING.
12. TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMENT PROTECTION
LABELED FOR USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION. UPON COMPLETION OF THE
APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING STATEMENT:
THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
AGRICULTURE AND CONSUMER SERVICES."
TIMBER
1. ALL WOODS AND WOOD CONSTRUCTION SHALL COMPLY WITH SPECIFICATIONS AND CODES MODIFICATIONS AS SPECIFIED
HEREIN:
A. AMERICAN INSTITUTE OF TIMBER CONSTRUCTION (STANDARDS MANUAL)
B. NATIONAL FOREST PRODUCTS ASSOCIATION:
I. NATIONAL DESIGN SPECIFICATIONS (NDS) FOR WOOD CONSTRUCTION
C. SOUTHERN PINE INSPECTION BUREAU:
I. STANDARD GRADING RULES FOR SOUTHERN PINE LUMBER
D. TRUSS PLATE INSTITUTE:
I. NATIONAL DESIGN STANDARDS FOR LIGHT METAL PLATE CONNECTED WOOD TRUSSES (TPI-2002)
E. APA - THE ENGINEERED WOOD ASSOCIATION :
I. ENGINEERED WOOD CONSTRUCTION GUIDE
F. AMERICAN WOOD PRESERVERS ASSOCIATION STANDARDS
2. ALI- LUMBER EXPOSED TO WEATHER, OR AGAINST SOIL, CONCRETE OR MASONRY MUST BE PRESSURE TREATED.
3. MINIMUM NAILING PER CHAPTER 6- WALL CONSTRUCTION AND TYPICAL NAILING SCHEDULE ON PLANS.
4. NOTCHING OR CUTTING OF FRAMING MEMBERS SHALL COMPLY WITH CHAPTER 6- WALL CONSTRUCTION.
5. WALL SHEATHING SHALL BE PER STRUCTURAL, SEE ROOF/WALL/FLOOR SHEATHING FASTENER SCHEDULE ON SHEET SN1.
6. MINIMUM DIMENSION OF ANY PLYWOOD SHEET SHALL BE 24" AND THE MINIMUM AREA SHALL BE 8 FT . SQ.
PLUMBING
1. SANITARY LINES SHALL BE OF CAST IRON OR PVC (SCHEDULE 40) AS APPROVED BY THE BUILDING OFFICIAL,
2. WATER SUPPLY LINES SHALL BE CPVC OR UPONOR PEX "A" (CROSS -LINKED POLYETHYLENE) WITH F1960 FITTINGS.
3. CONDENSATION LINES SHALL BE MINIMUM %" PVC (SCHEDULE 40), INSULATED WITH%" AMAFLEX.
4. SHOWER HEADS SHALL HAVE A FLOW CONTROL DEVICE TO GIVE A MAXIMUM FLOW OF 3 GPM EACH.
5. ALL CLEANOUTS SHALL BE FLUSH WITH GRADE.
6. NO VENT STACKS SHALL PASS THROUGH ROOF CRICKETS, VALLEYS, OR RIDGES.
7. SIZE. AND LOCATION OF CLEANOUTS SHALL CONFORM TO SECTION P3005.2.
8. FIXTURE SUPPLY SIZES SHALL CONFORM TO SECTION P2903.
9. THE PLUMBER IS TO DIVERT ALL VENTS TO REAR ELEVATION WHEN POSSIBLE.
10. DRILLING & NOTCHING OF WOOD FRAMED STRUCTURAL MEMBERS SHALL FOLLOW PROVISIONS OF SECTION P2603.2.
EXTERIOR WALL COVERINGS
1. ALL EXTERIOR WALL COVERINGS AND SOFFITS SHALL BE CAPABLE OF RESISTING THE DESIGN PRESSURES SPECIFIED FOR
THE WALLS FOR COMPONENTS AND CLADDING LOADS IN ACCORDANCE WITH TABLE R301.2(2) AS MODIFIED BY TABLE
R301.2(3), MANUFACTURED SOFFITS SHALL BE TESTED AT 1.5 TIMES THE DESIGN PRESSURE
EXTERIOR FINISHES
1. WHEN PLASTERING WITH CEMENT, PLASTER SHALL NOT BE LESS THAN THREE COATS, %" THICK, OVER FRAMED WALLS
APPLIED OVER PAPER BACKED METAL LATH OR WIRE FABRIC LATH AND WITH TWO LAYERS OF VAPOR BARRIER, NOT LESS
THAN 2 COATS, 1/2" THICK, WHERE APPLIED OVER MASONRY OR CONCRETE.
2. STUCCO OR PORTLAND CEMENT PLASTER SHALL BE INSTALLED, PROPORTIONED AND MIXED IN ACCORDANCE WITH
ASTM-C926 & ASTM-C1063-12a.
3. LATH & ACCESORIES PER ASTM-C-1063-11A & R703.7.1. ALL STUCCO APPLICATION DETAILS, INCLUDING BUT NOT LIMITED TO:
ALL STUCCO CONTROL JOINTS KICK -OUT DETAILS
"L" FLASHING HORIZONTAL LATH AND PAPER DETAILS
PIPE PENETRATION DETAILS VENT PENETRATION DETAILS
WEEP SCREED DETAILS CONDUIT PENETRATION DETAILS
CASING BEAD DETAILS DRIP EDGE DETAILS
CANTILEVER DRIP EDGE DETAILS CORNER BEAD DETAILS
WINDOW CASING DETAILS STUCCO TO SIDING TRANSITION DETAILS
WINDOW FLASHING DETAILS
4. SHALL BE INSTALLED PER ASTM-Cl063 -11A AND R703.7.
2-STORY GYPSUM BOARD
UNDER STAIR PROTECTION:
1. ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER STAIR SURFACE AND ANY SOFFITS PROTECTED
ON THE ENCLOSED SIDE WITH 1/2" GYPSUM BOARD. R302.7.
1441 N. RONALD REAGAN BL
LONGWOOD, FL 32750
PH: 407-774.6078
FAX: 407-774-4078
www.abdesigngroup.com
AA #: 0003325
111111
1
0
U
SUBDIV. 8e LOT:
CREEKSIDE
LOT #61
PROJECT#
04321.000 061R1
MODEL:
4EGB
"GALEN"
GARAGE SWING:,
oRfe L
PAGE:
GENERAL
LNOTES
160 MPH EXP. C
ARCH7F:LCOTF1DA
STATE OF
JOIN 11 3
c
L OLAND A ABOUCHACRA
AR NO 93723
06/13/18
SCALE: 1/4"=11- 0"
SHEET �T
G .90
FLAME SPREAD AND SMOKE INDEX FOR WALL AND CEILING FINISHES SHALL BE IN
ACCORDANCE WITH SECTION FBC R302.9.1 THROUGH FBC R302.S4
FLAME SPREAD AND SMOKE -DEVELOPED INDEX FOR INSULATION SHALL BE IN
ACCORDANCE WITH SECTION FBC R302.10.1 THROUGH FBC R302.10.5
38' -8'
I/
I
I
COVERED
I
I
I
LANAI
I
(
8'-8' CLG
[�O�NO
6'-8"
ll'-8°
Il'-4'I
9'-0"
I
(
3052-SH
(2) 3052-SH
Pq
pq
6068 SssD
I
I
II
9 A O
ROOM
DINING
I
I I
I OI
V-e' CLG.
j
°
I I
KITCHEN
s
r
l
I I °
�' 8'-v CLG.
CONT.
HANDRAIL
v
i
III :�`
Q I
42 H, HALF
WALL W/ CAP
OPT,
1 -
all
I
��
0'
4'-0"
8'-8'
5'-0"
5'_a-
4'_O- li
POST
U
y u
2X8
C.
I
I I I I I I
STOP.
pEp�
uP I
I I I I I I
,y,� C�
INK v PAN. 0'
I
PWDR, s'-8' CLG.
„ W14.
STAIR DATA
IMT. e
8'-8' GLG. 3-SH
� -
16 RISERS • 7.54'
15 TREADS 6 10'
�I
+I' NOSING
III
BOLLARD
III
AS REQ.
PER BLDG.
'
FLEX
CODE
6'
III
S'-8' CLG.
GARAGE
III
V-8' CLG.
FOYER
III
cLG.
III
3068 W/
361X10' TRANS. MT. N
0
(2) 3052-SH
ENTRY
8'-8' CLG.
-----
---------- 0
2 -8"
16'-(a"
2'-8" 4'-8'
-0" 8'-8' '-D'
21' -4'
38'-8'
FIRST FLOOR PLAN
SCALE: 1/4 = 1'-&
1�
11
0
SQ.FT.
CALC.'S
IST FLR LIVING
2ND FLR LIVING
1019
1413
$a FT.
SGt Ft.
TOTAL LIVING
GARAGE
PORCH
2432
432
81
SQ. FT.
SQ.FT,
SQ. FT.
TOTAL.
3031
$a FT.
AC VOLUME
202 112
cowcoff MD U A M no L008
MW =WWM FOR$8E= M=
OPIEWO
AND TYPE
8OUARE
FOOTAOH
ZM
te0 WH YYID lV
RBIAlIGB
MIN. WINDOW
10
5
34/-45
CRITERIA
EXTERIOR SWING
21
5
32/-42
DR MIN. CRITERIA
SGD. MIN.
12
5
30/-31
CRITERIA
8010 O.H.D.
56
5
30/-38
16010 O.W.D.
112
5
29/-35
SOFFIT
N/A
5
31b/-380
-6829/
IF
ROOF TILE
N/A
3
-5829
APPLICABLE
BASIC WIND SPEED MPH = 160 (Vult) INTERNAL
PRESSURE COEFFICENT = f 0.18 BLDG. CAT.=II,
EXP.=C, MEAN ROOF HT. = 23'-0"
PRESSURES HAVE BEEN MODIFIED PER FBCR R301.2.1
TO MEET TESTED ALLOWABLE OR NOMINAL WIND LOAD
VALUES FROM THE PRODUCT MANUFACTURER.
MASONRY/FRAME
WALL LEGEND
1H11111!1H1
8'-&' BLOCK WALL
UN.O ON PLANS
BRG. HGT. VARIES
8' BLOCK WALL
UNA ON PLANS
18'-8' BRG.
,7777
ii
INTERIOR LOAD
BRG. WALL U.N.O.
ON PLANS
INTERIOR NON
LOAD BRCS. WALL
U.N.O. ON PLANS
-ALL INTERIOR
DOORS TO BE 6'-8'
-ALL EXTERIOR
DOORS TO BE 6'-8'
UNLESS NOTED
OTHERWISE
NOTE:
-2-8 LOUV. DOOR W/ AIR HANDLER ON METAL STAND OR 2-8 SOLID
DOOR W/ RETURN PLENUM AND RETURN AIR GRILLE.
-VERIFY CONDENSER PAD LOCATION WITH SITE PLAN
-OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE
EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1 3/8' (35 MM)
IN THICKNESS, SOLID OR HONEYCOMB -GORE STEEL DOORS NOT
LESS THAN 1 3/9' (35 MM) THICK, OR 20-MINUTE FIRE -RATED DOORS.
-THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE t ITS
ATTIC AREA BY NOT LESS THAN "2'(12.7mm) GYPSUM BOARD APPLIED
TO THE GARAGE SIDE. GARAGES BENEATH HABITABLE ROOMS
SHALL BE SEPARATED FROM ALL HABITABLE ROOMS BY NOT LESS
THAN YOD.9mm) TYPE X GYPSUM BOARD OR EQUIVALENT.
UNDER STAIR PROTECTION:
ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS,
UNDER STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE
ENCLOSED SIDE WITH 1/2 INCH GYPSUM BOARDS. FBCR 201-1 (6TH
ED.) 302.71
1441 N. RONALD REAGAN BLVD
LONGWOOD, FL 32750
PH: 407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
AA #: 0003325
�111111_
SUBDIV. de LOT:
CREEKSIDE
LOT #61
PEtOJECT#
04321.000 061R1
MODEL:
4EGB
"GALEN"
GARAGE STrMG:
i�`.
PAGE:
FIRST
FLOOR PLAN
160 MPH EXP.
ARCFFTECT-
STATE OF FLORIDA
DATE: 06/13/18
SCALE: 1/4"=1— O"
10,-0 3/4, 2HD FIN. FLR
8'-8' BRGs. HGT.
NOTE:
STAIRS RISERS TO CONFORM
TO FBCR 6TH EDITION (2011).
MIN. TREAD-10' MAS<- RISER --I
3/4' 3A6' MAX VARIATION IN
RISERS/iREAD8 ADJACENT TO
EACH OTHER 3/8' MAX.
VARIATION IN ANY
RISER wzAD HANDRAIL
CIRCULAR CROSS SECTION
DIA TO BE 1 3/4' +-1/4' OR
PROVIDE EQUIVALENT
GRASPA5ILITY WINDERS- MIN.
6' WIDE i NARROW AND MIN. II'
WIDTH a 12' FROM NARROW
END 34' MIN. HANDRAIL HGT.
�Q cro
IfKK o
� m
0'-0' FIN. PLR
C1' 411
D5L.
TOP
PLATE
A BAR DETAIL
SCALE: V4'.I'-0'
0
in
(2) LAYERS OF 3/4' PLYWOC
OR (2) LAYERS OF 3/4' "
FLOOR MATERIAL RIPS FOR
SOLID NAILING
SECURE TREADS TO STRINGER—
WK3)1s 3' SCREWS • EA
STRINGER UNTHREADED SHANK
TO EXTEND BEYOND THICKNESS
OF SUB -FLOOR SHEATHING
0
/� FLR
42' H. 1/2 3/4' KICK
WALL W/ CAP I MAX. PLATE / $tAIR DAtA:
NI NOSING 1011 16R ®iNOSING/ 15 TREADS e
CONT. MIN. / 10'+ I' NOSING
HANDRAIL
STOR.
w!r?,,
Z
i�
x
/,
(/tpoop"� 2 E 4 2R5-lNFORCING
STRINGER
/ 0 EA 2 X I2 STRINGER
SECURE W/12d 6'-8' O:
2X4 ATTACHED W/ 10d
MASONRY NAILS • 2X4 P-T.
SLEEPER INTO SLAB WITHIN 8'
OF EACH END, 32' O C. MAX.
3-2x12 SYP STRINGER
REINFORCED W/2X4 SPF
W/CONT. BEAD OF
SUB -FLOOR ADHESIVE
PL-400 OR SIMILAR •
EA HORIZONTAL RUN
STAIR DETAIL
V eca_e• ia•.r-o•
3/4, T#G SUB FLOOR
GLUED 4 SCREWED
PER FASTENER
SCHEDULE
HANDRAIL IV 36'
W/ 2X4 RF-INFOR
a
DIM VARIES
\
iA
m
61
61
r
B ARCH DETAIL
SCALE: 1/4'=I'-C'
tHE CLEAR SPACE 5ETWI=EN
tHE HANDRAIL AND THE WALL
5HALL BE NO LESS THAN 1 1/2'
AS PER F5CR R311.1.8.2
NOTE:
I. HANDRAILS SHALL HAVE EITHER A CIRCULAR CROSS SECTION WITH A
DIAMETER OF 1J"t 2" OR A NONCIRCULAR CROSS SECTION WITH A
PERIMETER DIMENSION OF AT LEAST 4" BUT NOT MORE THAN 6 1/4' AND
A LARGEST CROSS SECTION DIMENSION NOT EXCEEDING 2 1/4". EDGES
SHALL HAVE A MINIMUM RADIUS OF 1/8'.
2. THIS RAILING SYSTEM IS DESIGNED TO RESIST A LOAD OF 50 PLF
FOR A CONCENTRATED LOAD OF 200 POUNDS APPLIED IN ANY
DIRECTION AT THE TOP OF SUCH BARRIERS AT ANY LOCATION ON THE
SAFEGUARD, WHICHEVER CONDITION PRODUCES THE MAXIMUM
STRESSES- PER SECTION 16015.1 / F.B.C. (201-1) 6th EDITION.
D HANDRAIL DETAIL
SCALE: 3/4' - I'-0'
1441 N. RONALD REAGAN BL
LONGWOOD, FL 32750
PH:407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
L AA #: 0003325
F
W
w
0
A
h
F
SUBDIV. da LOT:
CREEKSIDE
LOT #61
PROJECT#
04321.000 061R1
MODEL:
4EGB
"GALEN"
GARAGE STnNG:
PAGE:
DETAILS
160 MPH EXP.
ARCHRECT:
STATE OF FLOR
06/13/18
' SCALE: 1/4"=1'-0"'
SHEET
STAIR DATA
16 RISERS w i54'
15 TREADS w 10"
+1' NOSING
�o
N
12' -0" 2' -4' II' -8" 12, -8"
8'-4' „ V-4" II'-8' „ 10'-4'
io EGRESS TEMP I
BDRM.#2
8'-8' CL&
!,limm
-0"
`.'' - 4'
3052-SH
EGRESS
BATH #2
8'-8' CLa
II'-10"
EGRESS
a
N BDRM.#4
8'-8' CLo.
CHASE
— — 42' H. HALF
WALL W/
ceHasE CAP
I
I W.I.C.
s'-a' CLGL 17
,
OWNER'S
SUITE
8'-8' CM
3052-SH
EGRESS
I ii
3052-SH
EGRESS
BDRM.#3
8'-8' act
/Au nl AI
22'x36'
ATTIC
i- V-2" ACCESS„ 8 -,
OMAR
a
N
F, Azi,
IN
�f
Y
hLAV.
LAV.
TEMP.
m
2'-4"
6'-4"
�-
> W-V CLk
3-SH I n r irII �' I
I II I
2'-4' 2'-6' 3'-10"
OWNER'S I�
BATH
CL& 'x6
H
W L.
8'-4'
rr-t-ter
TEMP.
4'-4' 9'-S" 1'-4"
38' -8'
SECOND FLOOR PLAN
SCALE: 1/4 = I'-O'
NOTE:
-2-5 LOUV. DOOR W/ AIR HANDLER ON METAL STAND OR 2-8 SOLID
DOOR W/ RETURN PLENUM AND RETURN AIR GRILLE.
- VERIFY CONDENSER PAD LOCATION WITH SITE PLAN.
-OTHER OPENINGS BETWEEN THE GARACsE AND RESIDENCE SHALL
BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1 3/8' (35
MM) IN THICKNESS, SOLID OR HONEYCOMB -GORE STEEL DOORS NOT
LESS THAN 1 3/8' (35 MM) THICK, OR 20-MINUTE FIRE -RATED DOORS.
I
a
MASONRY/FRAME
WALL LEGEND
V-S' BLOCK WALL
UNA ON PLANS
5R3. WGT. VARIES
S' BLOCK WALL
UN.O ON PLANS
BRIz-
INTERIOR LOAD
51W-s. WALL U.N.O.
ON PLANS
INTERIOR NON
LOAD BRCS. WALL
UN.O. ON PLANS
-ALL INTERIOR
DOORS t0 BE 6'-S'
-ALL EXTERIOR
DOORS TO BE 6'-8'
UNLESS NOTED
OTHERWISE
1441 N. RONALD REAGAN BLVD
LONGWOOD, FL 32750
PH: 407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
AA #: 0003325
F
W
ji
v
w
0
a
SUHI.IIV. & LOT:
CREEKSIDE
LOT #61
PROJECT#
04321.000 061R1
MODEL:
4EGB
"GALEN"
GARAGE SWING:
ofif etrf
PAGE:
SECOND
FLOOR PLAN
60 MPH EXP. i
ARCHffECT
STATE OF FLORIDA
D TE:, 06/13/18
SCALE: 1/4"=11- 0"
SHEET
A
26'-0' SLD HGT
2ND FLR
8RCs. HGsT
I'
4' RAISED —
BAND, TYP-
8' RAISED —
BAND
10'-C 3/4' 2ND FLR.
FIN. FLR.
8'-8' 15T FLR
SRSs HGT.
COACH —
LIGHT
LIGHT
IME":
I
i
FRONT ELEVATION
TEXTURED FINISH
NOTE: WALL FENESTARTION FLASHIWs PER FBCR -103.4
OFF RIDGE VENT
I
r-
r-
SHINGLE
ROOF
416-8' 2ND FLR.
0, HRCs. HGT.
10'-0 3/4" 2NP FLR.
—SIN. FLR.
Z.8LT
FLR
Ha—T.
4' RAISED
15AND (TYPJ
-0" FIN.
5'-IPA" ni
oilll 8' 2ND FLR.
81�'s. HGT.
N 12 10-0 3/4 q - -- -
10'-0 3/4' 2ND FLR.
2ND FLR_ _----_—_-- _- -
FIN. FLR- - -- $FIN. FLR.
8'-8" IST FLR IST 1ST FLR
BT2Ci. HCat.
8 -8 IST FLR - BRCs. HGT. - — - sRr�. HGT.--- -- �
0'-0" FIN. FLR
m
REAR ELEVATION
TEXTURED FINISH
MODEL 2432-GALEN-4EGB (2-Story)
AREA OF ATTIC
= 1451 SQ. FT.
NET FREE VENTILATION AREA RI
1/ 300
REQUIRED VENTILATION AREA
= 1451 /300
= 4.84 SQ. FT.
4.84
= 696.48 SQ. IN.
MI N. REQUIRED VENTILATION
= AX 696.48
IN UPPER PORTION OF ATTIC
= 278.592 SQ. IN.
(BALANCE TO BE PROVIDED IN
SOFFITVENTS)
OFF RIDGE VENTI LATION AREA
= 115 SQ. IN. PER VENT (net free area)
TOTAL# OF VENTS REQUIRED
= 2.42
TOTAL#OF VENTS PROVIDED
= 3
SOFFIT VENTILATION AREA
7 SQ. IN. PER LIN EAR FT (net free
area)
LIN EAR FEET OF SOFFIT REQUIRI
39.80
1441 N. RONALD REAGAN BLVD.
LONGWOOD, FL 32750
PH: 407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
AA #: 0003325
E
W
U
W
may..
0
A
F
h
SU133DIV. de LAT:
CREEKSIDE
LOT #61
PROJECT#
04321.000 061R1
MODEZ •
4EGB
"GALEN"
GARAGE SWING:
'c�
PAGE:
FRONT &
REAR
ELEVATION "H"
60 MPH EXP. C
ARCHITECT.
STATE OF FLORIDA
a DAATET:
` 06 13 18
SCALE: 1/4"=1'-0"
BHEET
A3H
a
18'-S' 2ND FLR
5RCs. H T.
10'-0 3/4' ND FLR
FIN. FLR
S'-V 1ST FLR,
I!5RG. HCsT.—
2ND FLR
51:;Z3. HCxT.
10'-0 3/4' 2ND FLR
FIN. FLR.
8'-8" 15T FLR
5Rr4. HCsT.
LEFT ELEVATION
TEXTURED FINISH
RIGHT ELEVATION
TEXTURED FINISH
2ND FLR.
SRG. H4GT.
610'-0 3/4" 2ND FLR.
FIN. FLR.
a'-W IST PLR
Y5RCs. HC.sT.
1441 N. RONALD REAGAN BL
LONGWOOD, FL 32750
PH: 407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
AA #: 0003325
rh
0.
U
v
O
y
4
F
4
F
SUBIXV. de LOT:
CREEKSIDE
LOT #61
PROJECT#
04321.000 061R1
MODELe
4EGB
"GALEN"
GARAGE SV#MG:
PAGE:
LEFT & RIGHT
ELEVATION "H"
160 MPH EXP. C
ARCH TECT-
STATE OF FLORDA
kJ
m
1 SCALE: 1/4"=1'-0" 1
SHEET
ELECTRICAL LEGEND
SYM.
DESCRIPTION
d�
STANDARD SWITCH
d
3-WAY SWITCH
�{}
4-WAY SWITCH
DIMMER SWITCH
HE
PUSH BUTTON
DISCONNECT
T
THERMOSTAT
SINGLE RECEPTACLE (125v/20-AMP
SINGLE POLE)
=0
110V DUPLEX EqeCEPtACLE
IIVV DUPLEX RECEPTACLE (EQUIPPED
=0
WITH GROUND FAULT
NTERUP'TER/TAMPER RESISTANT TYPE)
110V DUPLEX OUTLET (HALF OF OUTLET
WIRED TO SWITCH)
EXTERIOR WATERPROOF/GFI
4p:
RECEPTACLE (GROUND FAULT
INTERUPTER)
1OV QUADPLEX RECEPTACLE
®
IIOV DUPLEX RECEPTACLE (FLOOR
OUNTED)
220V RECEPTACLE (4 WIRE
:ONNECTOR)
i Q
ALL MOUNTED LIGHT
CEILING MOUNTED LIGHT
wENDENT LIGHT
LOOD LIGHT
WALL SCONCE PRE -WIRE
VENT FAN WITH LIGHT (1 cFm PER SQ. FT.)
nee
3 BULB LIGHT FIXTURE
Been
4 BULB LIGHT FIXTURE
annann
6 BULB LIGHT FIXTURE
48' TRACK LIGHTING
ATTIC LIGHT WITH PULL CHAIN
UNDER CABINET LIGHT
®
I'x4' FLUORESCENT LIGHT (RECESSED)
FLUORESCENT LIGHT (SURFACE
NT)
FLUORESCENT LIGHT (RECESSED)
hl'x4'
w FLUORESCENT LIGHT (IDURFACE
ESS LIGHT
ESS LIGHT (VAPOR PROOF)
ING MOUNTED LIGHT WITH J-BOX
OPT. FAN
GtRICAL PANEL (FIELD VERIFY
ATION)
P153LOX
OX (WALL MOUNTED)
(CEILING MOUNTED)
CEILING MOUNTED FAN
Q
VENT FAN (1 CF1M PER SQ. FT.)
PHONE JACK
(•Q
SMOKE DETECTOR (CEILING MOUNTED)
®
SMOKE/CASMOKE/CARESON MONOXIDED TECTOR
(CEILING MOUNTED)
CHIMES
®CEILING
MOUNTED OUTLET
DOOR OPENER
TV
TV JACK
USB PORT
NOTES-
• LOCATION OF TV JACKS 4 PHONE OUTLETS 4 FANS
TORE VERIFIED s HOMEOINER
PRE -CONSTRUCTION MEETING.
• ALL RECEPTACLES IN ALL INHABITABLE ROOMS
TO BE ARC FAULT PROTECTED PER NEC 210.12(b)
• 20 AMP DEDICATED LAUNDRY CIRCUIT.
+ GFI 0 ISLAND (NOT ON KITCHEN CIRCUIT)
• DISHWASHER DISCONNECT TO BE LOCKOUT IN
PANEL
• BATHROOM EXHAUST FAN TO HAVE MIN. CAPACITY
OF 50 CPr INTERMITTENT PER TABLE M11501.4 OF
FBCR 6TH EDITION (201-1).
• LAUNDRY ROOM RECEPTACLE SHALL BE GROUND
FAULT CIRCUIT-INTERUPPTER PROTECTION FOR
PERSONNEL ON FEEDERS)
• WIRING METHOD SHALL BE NON METALLIC CABLE
AS NEC 2014 ARTICLE 30OA(5X2)
• ALL RECEPTACLE TO BE TAMPER -RESISTANT
TYPE
• ALL LAMPS SHALL BE SELECTED BY BUILDER
AND 15% OF LIGHTING MUST BE ENERGY EFFICIENT
TYPE PER F.B.C. ENERGY CONSERVATION
(RESIDENTIAL ENERGY EFFICIENCY) 2011. 6th
EDITION 1111111404.1
FIELD
VERIFY
LOC.
CWP„PF.
,y APP.
0
IRRIGATION
OUTLET
48' APP.
❑ C� D E
CEILING MTD.
Ai
LIGHT TO 5e
C
INSTALLED,
PROVIDE
I
J-BOX FOR
OPT. FAN
GFI
GFII-F t " _i
I ITCH IN
GREAT CABINET
ROOM KITCHE w
PIREA
CL s FAD DINING of
^ a
22'-8'
\I '
GFI OUTLET OF
FOR DW
t
f
AFL T�OR.
I _ r I �li'CCJIH
/ PWDR. I PAN.
GFI A 44'
APP.
/
/ P.S. FOR!
/ GARAGE
DOOR
/
,-' GARAGE
KEYLESS
FIXTURE
GFI
GARAGE
DOOR
F REWIRE
PRE -WIRED
CLG FAN
FLEX
Cam' �J
r
r
P.S. FO
HIMES
c�NTRY
t — --- J
— — — — — — — — — — — — — — — — — — —
31 r/
OPT.
COACH ^_^ �-•
LIGHT ^1----------"" -
FIRST FLOOR
ELECTRICAL PLAN
SCALE. 1/4 m P-O'
HOOD WIRE W/
OUTLET FOR
FUTURE MICRO.
WP Panel MAIN -A
PANEL: 8/16 wp crt. breaker VOLTAGE: 120 / 240 V -1 Ph MAIN: 150 Amp M.C.B
FEEDER: 3- #1 Cu THWN & 1- #6 Cu (G) in 1 1/2" C. OR 3- #2/0 AL THWN & 1- #6 Cu (G) in 1 1/2" C.
Wire
Polo
Bkr
Description
Watts
Circuit
I
I Circuit
Watts
Description
Bkr
Pole
Wire
#12
1
20
Exterior Receptacle GFI for TUG
1200
1
2
Space
#12
2
20
Irrigation Pump
1000
3
4
Space
5
6
6240
A/C C.U.
40
2
#8
S ace
7
8
PANEL -A
PANEL: 42 crt breaker VOLTAGE: 120 / 240 V -1 Ph MAIN: 150 Amp M.L.O.
FEEDER: 3- 91 Cu THWN & 1- #6 Cu (G) in 1 1/2" C. OR 3- #2/0 AL THWN & 1-#6 Cu (G) in 1 1/2" C.
Wire
Pole
Bkr
Description
Watts
Circuit
Circuit
Watts
Description
Bkr
Pole
Wire
#12
1
20
Small Appliance
1500
1
2
8000
Range
50
2
#6
# 12
1
20
Microwave / Hood GFI
1800
3
4
#12
1
20
Small Appliance
1500
5
6
4500
Water Heater
25
2
#10
# 12
1
20
Refrigerator
1500
7
8
# 12
1
20
Dining Appliance Receptacles AFCI
1500
9
10
1200
Disposal GFI
20
1
#12
#12
1
20
Bath GFI Receptacles
1200
11
12
1500
Dishwasher GFI
20
1
#12
#14
1
15
Foyer / Hall / Flex / PWDR AFCI
900
13
14
5000
Dryer GFI
30
2
#10
#14
1
15
Lanai, Dining Lts, Kitchen Lts AFCI
900
15
16
#14
1
15
Great Room / Stairs AFCI
900
17
18
1500
Washer GFI
20
1
#12
#14
1
15
SD & C/O AFCI
900
19
20
1000
Garage Door Opener GFI
20
1
#12
#12
1
20
Hall / Laundry AFCI / Opt. Loft
1200
21
22
1200
Garage Lights and Receptacles GFI
20
1
#12
#14
1
15
Bedroom #2 / Bathroom #2 AFCI
900
23
24
900
Owner's Suite AFCI
15
1
#14
#14
1
15
1 Bedroom #3 / Bedroom #4 AFCI
900
25
26
900
Owner's Bathroom AFCI
15
1
#14
Space
27
28
1000
Exterior Lights and Receptacles GR
20
1
#12
Space
29
30
1000
lIrrigation controls only
20
1
912
Space
31
32
Space
Space
33
34
Space
Space
35
36
Space
Space
37
38
Space
#8
2
35
A/C A.H.U.
(Heater 5 KVA at 65%)
5525
39
40
Space
Space
41
42
Load subject to demand factor calculations 1 line
17800
27700
Load subject to demand factor calculations / line
Demand Factor Calculations:
ABBREVIATIONS:
AFCI: ARC FAULT CIRCUIT INTERRUPTER
NC: NON -COINCIDENT LOAD
GFI: GROUND FAULT INTERRUPTER
Total load bjecl to demand facto
su
45500
First 10000 watts at 100%
10000
Remaining watts at 40°k
14200
Total A/C load
11765
7LOAD CALCULATION IS BASED ON AIC NON -COINCIDENT LOAD
Total Connected Load Watts
35965
Total Am s(watts / 240 molts)
149.9
General Li hting & Rec e tacle Load
Total A/C Square Feet
2436
7308
General Us & Rec 3 W / Sq. Ft.
Hi -Hats 1 at 65W/Li ht at 100%
65
General
7373
Ckts# Watts/C
Total watts
General Us & Rec Panel A
111
6701
7373
PROVIDE 3 2/0 CU, TWM ♦ 1% CU IN 2' CONDUIT OR 3
04/0 AL, THWN + NS CU N 2' CONDUIT.
(CONDUIT TO TERMINATE A50YE SOFFIT • OVERHANG.)
150 AMP ELECTRICAL RISER
NOT TO SCALE.
GENERAL NOTES! O
A. ELECTRICAL MATERIALS AND INSTALLATIONS SHALL
COMPLY WITH ELECTRICAL PROVISIONS OF THE FBCR &tH
EDITION (20171 LOCAL CODES, AND ALL LOCAL POWER
COMPANY REQUIREMENTS. ( III
Et ALL CONDUCTORS 4HA1 L BE TYPE THHN/rHWN UNLESS M
NOTED OTHERWISE
PROVIDE ISO AMP, 120/240 VOLT, 1 PHASE SECONDARY
ELECTRICAL SERVICE PROVIDE 3 01 COPPER (CU) N
I-I/2" DIA SCHEDULE SO PVC CONDUIT OR PROVIDE 3
02/0 ALUMINUM (AL) N 2" DIA SCHEDULE 80 PVC
CONDuii UNLESS SERVICE i8 PROVIDED BY THE
ELECTRIC COMPANY. C 0RDINAlE WITH THE ELECTRIC
COMPANY PRIOR TO BID.
COMBINATION SERVICE
DISCONNECT SWITCH AND
ELECTRIC METER IN
NEMA 3R ENCLOSURE
TELEPHONE SERVICE
ENTRANCE
EQUIPMENT
INTERSYSTEM CONDNG
IMR INAL At LOW
VOLTAGE CONNECTIONS
00 AMP
0440 VOL'
1 PHASE
MLO
PANEL
CABLE TELEVISION
SERVICE ENTRANCE
EQUIPMENT
1 04 CU SERVICE GROUND CONNECTED TO
CONCRETE ENCASED FOOTER STEEL PER
ELECTRICAL PROVISIONS OF THE PI 6tH
EDITION (20M).
8/8" DIA X 8 FT LONG COPPER CLAD GROUND ROD
1441 N. RONALD REAGAN BLVD
LONGWOOD, FL 32750
PH: 407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
AA #: 0003325
F
W
03
W
p
W
A
F
ti
SU'BDIY. die LOT:\
CREEKSIDE
LOT #61
PROJECT#
MODEL:
4EGB
"GALEN"
GARAGE SVMGi:
' %&Rf fT
PAGE:
FIRST FLOOR
ELECTRICAL
PLAN
.60 MPH EX.P.
ARCHITECT -
STATE OF FLORIDA
DATE: 06/13/18
SCALE: 1/4"=11— 0"
SHEET
ELECTRICAL LEGEND
GYM.
DESCRIPTION
-#A-
STANDARD SWITCH
-4
3-WAY SWITCH
-4
4-WAY SWITCH
DIMMER SWITCH
b
PUSH BUTTON
DISCONNECT
7
THERMOSTAT
-8
SINGLE RECEPTACLE (125v/20-AMP
SINGLE POLE)
110V DUPLEX RECEPTACLE
110v DUPLEX RECEPTACLE (E6IUIPPED
ITH GROUND FAULT
INTERUPTER/TAMPER RESISTANT TYPE)
110V DUPLEX OUTLET (HALF OF OUTLET
WIRED TO SWITCH)
EXTERIOR WATERPROOF/GFI
RECEPTACLE (GROUND FAULT
NTERUPTER)
110V GUADPLEX RECEPTACLE
®MOUNTED)
110V DUPLEX RECEPTACLE (FLOOR
20V RECEPTACLE (4 WIRE
CONNECTOR)
F_o
WALL MOUNTED LIGHT
CEILING MOUNTED LIGHT
PENDENT LIGHT
L000 LIGHT
WALL SCONCE PRE -WIRE
VENT FAN WITH LIGHT (I CFM PER 60. FT.)
neon
3 BULB LIGHT FIXTURE
An=
BULB LIGHT FIXTURE
=QDA
rp BULB LIGHT FIXTURE
48' TRACK LIGHTING
ATTIC LIGHT WITH PULL CHAIN
UNDER CABINET LIGHT
®
I'x4' FLUORESCENT LIGHT (RECESSED)
®
1'x4' FLUORESCENT LIGHT (SURFACE
MOUNT)
2'x4' FLUORESCENT LIGHT (RECESSED)
x
O
RECESS LIGHT
•
RECESS LIGHT (VAPOR PROOF)
CEILING MOUNTED LIGHT WITH J-BOX
FOR OPT. FAN
ELECTRICAL PANEL (FIELD VERIFY
LOCATION)
LOCATION)ELECTRJCAL METER (FIELD VrmRR;y
i QJ
J-BOX (WALL MOUNTED)
®
-BOX (CEILING MOUNTED)
FILING MOUNTED FAN
0VENT
FAN (I CFM PER Sa. FT.)
�Q
ONE JACK
QE
DETECTOR (CEILING MOUNTED)
®
/C RBON MoNoxim D C OR
G I ING MOUNTED)
CHIMES
®
C I MOUNTED OUTLET FOR GARAGE
OOR OPENER
TV
TV JACK
• mac•
USB PORT
NOTES:
• LOCATION OF TV JACKS t PHONE OUTLETS 4 FANS
TORE VERIFIED s HOMEOWNER
PRE -CONSTRUCTION MEETING.
• ALL RECEPTACLES IN ALL INHABITABLE ROOMS
TO BE ARC FAULT PROTECTED PER NEC 210.12(b)
• 20 AMP DEDICATED LAUNDRY CIRCUIT.
• GFI ® ISLAND (NOT ON KITCHEN CIRCUIT)
• DISHWASHER DISCONNECT t0 BE LOCKOUT IN
PANEL
• BATHROOM EXHAUST FAN TO HAVE MIN. CAPACITY
OF 50 CFM INTERMITTENT PER TABLE MI501.4 OF
FBCR 6TW EDITION (2011).
• LAUNDRY ROOM RECEPTACLE SHALL BE GROUND
FAULT CIRCUIT-INTERUPPTER PROTECTION FOR
PERSONNEL ON FEEDERS)
• WIRING METHOD SHALL BE NON METALLIC CABLE
AS NEC 2014 ARTICLE 300.4(5=
• ALL RECEPTACLE TO BE TAMPER -RESISTANT
TYPE
• ALL LAMPS SHALL BE SELECTED BY BUILDER
AND 15% OF LIGHTING MUST BE ENERGY EFFICIENT
TYPE PER F.B.C. ENERGY CONSERVATION
(RESIDENTIAL ENERGY EFFICIENCY) 2011. 6th
EDITION R404.1
3
,'
PRE -WIRED
CLCs FAN
J' `J
I
W,I,C.,
I
PRE -WIRED
CLG FAN
BDRM.#4
.� WALL MOUNTED
LIGHT W/SWITCH IN
At
i
PRE -WIRED �''
CLG FAN ,
Cam' `J
OWNER'S
SUITE
SAD.
F_
PRE -WIRED
CL* PAN
J' `J
BDRM.#3
rl
i T
IAUN
�roPt.'
NER'S
I, BATH
SECOND FLOOR
ELECTRICAL PLAN
SCALE: 1/4 = I'-V
1441 N. RONALD REAGAN BL
LONGWOOD, FL 32750
PH: 407-774-6078
FAX: 407-774-4078
www.abdesigngroup.com
L AA #: 0003325
E
02
ct
W
0
w
4
11,
MOM 8e LOT:
CREEKSIDE
LOT #61
PROJECT#
04321.000 061R1
!MODEL:
4EGB
"GALEN"
GARAGE STrMG:
'RIGHT .
PACE:
SECOND
FLOOR
ELECTRICAL
PLAN
60 MPH EXP.
ARCMEM
STATE OF FLORIDA
Ell
06/13/18
SCALE: 1/4"=1'-0" 1
E2
F
y
04
Cai
h
q
F
A
64
h
SUHDIV. & LOT:
CREEKSIDE
LOT #61
PROJECT#
04321.000 061R1
MODEL:
4EGB
"GALEN"
GARAGE SV#MG:
RIGHT
PAGE:
FIRST
FLOOR
MECHANICAL
PLAN
60 MPH EXP.
fDA 06/13/18
aSCALE: 1/4"=1'-0"
RINT
i9MEET
NJ[ 1
l
w
Is
0
q
4
svaaiv. & LOT:
CREEKSIDE
LOT #61
PROJECT:
04321.000 061R1
MODEI.e
4EGB
"GALEN"
GARAGE S'�'1►ING:
RIGHT
PAGE:
SECOND
FLOOR
MECHANICAL
PLAN
60 MPH EXP. C
DATE: 06/13/18
SCA.LE: 1/4"=11— 0"
SHEET
1441 N. RONALD REAGAN BLVD,
LONGWOOD, FL 32750
PH: 407-774-6078
FAX:407-774.4078
www.abdesigngroup.com
AA #: 0003325 J
r
�111111
S UBDIV. ee LOT:
CREEKSIDE
LOT #61
PROJECT#
04321.000 061R1
MODEL:
4EGB
"GALEN"
GARAGE SWING:
RIGHT
PAGE:
PLUMBING
PLAN
60 MPH EXP. ic
ARCHrMCT=
STATE OF FLORIDA
PRINT 06/13/18
SCALE: 1/4 11=11-0"
SHEET