LUCIE COUNTY- FORT PIERCE FIRE PREVENTION BUREAU
FORT PIERCE; FLORIDA ,
TELEPHONE 465-6655
PLAN NUMBER
#1931
DATE RECEIVED
10-11-89
CONTRA TOR:
Catalfumo Construction
PHONE NUMBER:
471-0338
ARCHIT 'CT:
Kuo ala & Associates
pp
PHONE NUMBER:
439-6424
OW N E R:I
GRABBER SOUTHEAST St.
Lucie Business'Park
LOCATIO
8288 Busine,s Park Dr.
TYPE OF
OCCUPANCY:
Factor Industrial
y�
TYPE OF CONSTRUCTION:--
IV unprotected
SIZE OF
BUILDING:
2,400 sq. ft.
NUMBER OF FLOORS:
1
REQUIREMENTS:
1. Wa is separating occupancies of the same group
shall be constructed of materials
ha 'inR a fire resistant rating of one 1
hour. Partitions shall extend
from
thel'Ifloor to tight
against the underside of the roof deck and shall extend
outl'lard to include
the eave line.
--
Nuih: iruss asseMiles are nOL ParL. Ut Eil-a Lru nnncuivI V _
WJIL have to extend to the roof deck above. _.
2. ;Occ1 ancies utilizing or storing highly combustible flammable corrosive or
oxiIlizins liquids or solids in excess of the amounts deemed hazardous by the
Authoritv Having Jurisdiction shall be properly ventilated and properly separated
fro I',Ithe remainder of the building in accordance with the appropriate NFPA Standard
or tle entire buildin;; will be classified as Group "H", Hazardous Occupancy. _
a I '
buildin of mixed occupancy shall be the higher rating found in Table 403.1 for the
CONTRACTORS RESPON$113JLITY TO NOTIFY BUREAU ON ALL INSPECTIONS
24 HOUR N tICE REQUIRED ON ALL INSPECTIONS
REVIEWED IBY' J�.-� �.. DATE
SIGNATURE
FORM 263 PRINTING BY REARM
a ,
r
STJ
BUILDING PLAN CHECK
LUCI E COUNTY- FORT PIERCE FIRE PREVENTION BUREAU
FORT PIERCE, FLORIDA
TELEPHONE 465-6655
CONTRACTOR:
i
ARCHI IECT:
n1A/AICQ•
PLAN NUMBER
DATE RECEIVED_
PHONE NUMBER:
PHONE NUMBER:
LOCATIION:
TYPE OF OCCUPANCY: TYPE OF CONSTRUCTION:
SIZE OF BUILDING: NUMBER OF FLOORS.
REQUIREMENTS:
occul,ancies being separated.
4. Provide a 2A-IOBC rated fire extinguisher for each 75' of travel distance.
#1931
5_ 11he interior finish on walls and ceilings shall be Class "C" in operating areas and
Class "A" or "B" in,corridors and exit ways.
II
i
I'
REVIEWED
CONTRACTORS RESPONSIBILITY TO NOTIFY BUREAU ON ALL INSPECTIONS
24 HOUR NOTICE REQUIRED ON ALL INSPECTIONS
BY: DATE
SIGNATUiE