PLAN REVIEW FORM
'
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
N
r
x
x�l
Telephone: 772-621-3322
9FDISS�`�
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept.
SLC
FMO Permit # B-19-82
Project,Name
Waa&f Faith & Praise Ministry
BLDG Permit # 1706 0576
Address
8251-3253 Business Park Drive
City PSL
Contractor
DCR General Construction
Address
134 NE Jettie Terrace
City PSL
State
FL Zip 34983
Telephone 361-3650
Architect/Engineer I Telephone
Occupancy Type Assembly Construction Type VB Square Feet
Occupant Load 138 per plans Number of Stories F- Access Box Access
�Key Switch
AFS Permit 1 FA Permit F FFP Permit I
I General Notes I
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located Indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire. Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2015 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector.3
2. Assembly occupancies with an occupant load greater than 100 persons require panic hardware or fire exit hardware on the
required means of egress doors.
Page �1 of Reviewed by Tony Jerger Date 03-14-2019