Product Evaluation Report
Of
398 E. Dania Beach. Blvd
Suite 338
Dania Beach, FL 33004
954.399.8478 PH
954.744.4738 FX
contact@buildingdrops.com
JELD-WEN, inc.
Contours Steel Door, Wood Edge
8'-0" Outswing Impact Glazed Single. or Double Door Unit
for
Florida Product Approval
Report No. 3391
Current Florida Building Code
Method:
Category:
Sub — Category:
Product:
Material:
Product Dimensions:
I — A (Certification)
Exterior Door Assembly
Swinging Exterior Door Assemblies
Contours Steel Door, Wood Edge
Wood/24 Ga. Steel
73.938"x 96.75"
Prepared For:
Jeld-Wen Inc.
3737 Lakeport Blvd.
Klamath Falls, 012. 97601 .��E51FrrrO�``''
Prepared by:
Hermes Norero, P.E. = _
Florida Professional Engineer #i7
i „ .CY
Date: 01/26/2015 -
Contents:
Evaluation Report Pages 1-4
r111%
Digitally signed by -Hermes F. Norero, P.E. 11rll1
Reason: I am approving this document Hermes Norero, P.E.
Date: 2015.02.09 10:47:40-05'00' Florida No. 73778
NOTICE OF PRODUCT CERTIFICATION
CERTIFICATION NO:
DATE:
CERTIFICATION PROGRAM:
COMPANY:
CODE:
REVISION DATE:
NI006254-R5
10/14/2005
Structural
JELD-WEN
104-3
05/05/2015
To verify that the "Notice of Product Certification" is valid, please visit www.NAMICertification.com to assure that the
product is active and currently listed. This certificationrepresents product conformity to the applicable specification and
that certification criteria has been satisfied. A NAMI approved certification labelmust be applied to the product to claim
certification status. Please review and advise NAMI if any corrections are required to this document.
COMPANY NAME AND ADDRESS
PRODUCT DESCRIPTION
JELD-WEN
JELD-WEN. s "Steel Wood-Edge"Double
3737 Lakeport Boulevard
In-Swing/Out-Swing Entry Doors w/ODL
Klamath Falls, OR 97601
Impact Glass or ODL Impact Allen Frame
and Endura Ultimate Hurricane Astragal
Configuration: XX
Glazing: IG-1/8" Tempered Glass/
Laminate-1/8" Annealed Glass/0.090"PVB by
Solutia/l/8" Annealed Glass
Frame: W-1880mm(74") H-2489mm(98")
Panel: W-965mm(38") H-2413mm(95")
DLO: W-559mm(22") H-2032mm(80")
SPECIFICATION
PRODUCT RATING
TAS 201/202/203-94
Design Pressure: +501-50 psf
Large Missile Impact.Rated
Product Tested By: National Certified Testing Laboratories
Report No: NCTL-210-3196-1/SJW2011-072/W-1488
Expiration Date: September 30, 2019
Administrator's Signature:
NATIONAL ACCREDITATION AND
MANAGEMENT INSTITUTE, INC.
4794 George Washington Memorial highway
Hayes, VA 23072
Tel: (804) 684-5124
Fax: (804) 684-5122
RESPONSE TO COMMENTS
127/2018 Comment: RECEIVED NEW, REVISED PLANS 09/21/2018AND WILL PERFORM NEW PLAN REVIEWS * FEES TO BE
AID UPON RE -SUBMITTAL
response: Per Carl Petersen, St. Lucie County Building Official, fees are to be waived on these drawings (Established in meeting on August
5- 2018).
iment: ENGINEER TO REMOVE ALL OF BAY #2 FROM PLANS AND REVISE ALL SQUARE FOOTAGE NOTES ON
NS TO THRE NEW FOOTAGES * CONTRACTOR TO NOTE THE CORRECT ADDRESS RANGE ON THE
MIT APPLICATION *
sheet A 0. Drawings now reflect reduced footprint of the space and the square footage has been changed on all shhets. Please note the
t discrepancy of areas on the occupancy areas table on sheet LS-1 to sheetA-0 is due to that table showing the inside area of rooms
reas the gross area on A-0 shows footprint area which includes the walls.
/2018 Comment: ENGINEER TO SHOW A RATED WALL OPENING CLOSURE DETAIL ON PLANS FOR THE OPENING FROM
COMMUNITY ROOM INTO THE WAITING ROOM
:)onse: Detail shown. See sheet A 2.
GV IV
nent: ENGINEER TO DESIGN THE CORRECT FIRE SEPARATION WALL DETAILS ON PLANS PER FBC TABLE 508.4
ADJOINING TENANTS * SHOW THE ADJOINING TENANT OCCUPANCY CLASSIFICATIONS ON PLANS
THE SEPARATION IS 2 HOUR FOR NON -SPRINKLED SPACES
lone: See'.2 hour wall detail on sheet A 1
9/27/2018
Comment: ENGINEER HAS CLASSIFIED THIS AS ATYPE II BUILDING * SEE FBC TABLE 601 FOR THE REQUIRED
CONSTRUCTION TO BE THIS TYPE * SHOW ALL PROTECTED AREAS ON PLANS * YOU HAVE A WOOD LOFT,
STAIRS AND PULPET SHOWN ON PLANS
Response: Seei sheet A-0. Classification has been corrected to Type V B. This allows for the interior wood construction to remain as per FBC
Table 601.
9/27/2018
Comment: ENGINEER TO ADD ALL REQUIRED RATED FIRE DOORS TO DOOR SCHEDULE ON A-3 * ADDRESS ALL
DOORS PENETRATING THE RATED WALLS AND SUBMIT [3] SETS OF THE PRODUCT APPROVALS FOR THE DOORS
Response: Existing exterior doors will remain. Interior fire -rated doors are shown on the schedule and are called out as Jeld-Wen 90 min Fire
Rated interior doors. See sheetA-3
9/27/2018 Comment: ROOM FINISH SCHEDULE IS NOT TO CODE 803.11
Response- Finishes in the Rest Rooms and the Janitor's Closet have been modified to comply with code. See revised finish schedule on
sheetA-3. 1
10/1/2018 Comment: STEPS FROM THE STAGE DOWN TO THE LOWER LEVELS CANNOT BE 10" * SEE FBC 1011.5.2
Response: See sheetA 2. The stage is accessed by steps on 2 sides. Railings were previously shown to deter movement over the 8" edge
of the left lower platform. The right Lower platform is 6" above the Sanctuary level and can be accessed directly. The left lower platform is
accessed from the stage by steps w/ 5" risers against the back wall.
10/1/2018 Comment: SHOW THE CORRECT GRASPABLE HANDRAIL DETAILS ON STAGE STAIRS, RAMP AND LOFT STEPS PER
FBC 1014.6 * HANDRAILS ARE TO BE ON BOTH SIDES OF STAIRWAYS PER FBC 1011.11
Response: See details on sheet A-3. The stairs are enclosed by sidewalls and the rails are attached to the side walls.
10/1/2018 Comment: LS-1 OCCUPANCY TABLE IS INCOMPLETE * ENGINEER TO LABELALL OCCUPANCY CLASSIFICATIONS PER
FBC TABLE 1004.1.2
Response: Occupancy Table has been completed. See sheet LS-1
I
10/1/2018 Comment: WALL LEGEND DOES NOT MATCH THE PLANS ON LS-1
Response: Wall legend on LS-1 has been revised to match the plans.
10/1/2018 Comment: PLEASE SHOW LOCATION OF WATER HEATER FOR ALL LAVS 607.1 FPC
Response: the Water Heater is an Tankless wall -mounted Water Heater that was shown in the Janitor's Closet See sheet P-1
10/1/2018 C Imment: PLEASE LABLE HI LO DRINKING FOUNTAIN AS SUSH TABLE 403.1 FPC
Response: The hi-lo drinking fountain is labeled as such on sheet P-1
L. Hugh Anglin -
J
BUILDING DROPS
A Perfect Solution'" Every Drop
Certificate of Authorization: 29578
Date: 01/26/2015
Report No: 3391
,nce of Test Standards: if any, between tested Code.
e editions referenced in the current Florida Building
Various test stan
dards have been evaluated for differences in test methodology
products to the following test standard edition(s):
editions of the test standards listed below and those
3ELDANEN, inc. has tested their p
1} ASTM E84-08 editions of the above mentioned
Chapter
35 of the current Florida Building Code references the following
test standards:
1) ASTM E84-09 it has been found that no significant
minimum requirements of the
test standards that would affect the results. All referenced
After review of the above mentioned referenced standards and editions, e
uivalent. All materials test results me
technical changes have been made to
standards have been found to beequivalent.
current FBC in
HVHZ provisions.
on: 1. Approved anchor types and substrates are as follows:
installati
Thg rou h Frame Installation: rate, use #10 Wood Screw type installation anchors of sufficient
A. For 2x wood buck subst embedment of 1.50" into the wood substrate.
length to achieve a minimum
te where one by (1X), non-structural, wood bucking is
substrate g, For concrete or masonry meter Ite Tapcon ' type concrete screw anchors of sufficient
employed, use 3/16" dla
to achieve minimum embedment of�1.25" into concrete or masonry.6"
length employed, use 3/1
substrate.whean hors of sood bucking ufficient length to achieve
C. For concrete or masonry a concrete screw
diameter ITW Tapcon type
minimum embedment of 1.25" into concrete or masonry• a details of the installation
(jW0509-01) for anchor
Refer to ins
tallation instructions spacing and more
requirements.
Design Pressure: Design Pressure 50 pSF
positive 50 pSF
Negative
I
Hermes od
a No. r737
, page 4of4
NOTICE OF PRODUCT CERTIFICATION
CERTIFICATION NO:
DATE:
CERTIFICATION PROGRAM:
COMPANY:
CODE:
REVISION DATE:
NI006254-R5
10/14/2005
Structural
JELD-WEN
104-3
05/05/2015
To verify that the "Notice ofProduct Certification" is valid, please visit wWw.NAMICertification.com to assure that the
product is active and currently listed. This certification represents product conformity to the applicable specification and
that certification criteria has been satisfied. A NAMI approved certification label must be applied to the product to claim
certification status. Please review and advise NAMI if any corrections are required to this document.
COMPANY NAME AND ADDRESS
PRODUCT DESCRIPTION
JELD-WEN
JELD-WEN7s "Steel Wood-Edge"Double
3737 Lakeport Boulevard
In-Swing/Out-Swing Entry Doors w/ODL
Klamath Falls, OR 97601
Impact Glass or ODL Impact Allen Frame
and Endura Ultimate hurricane Astragal
Configuration: XX
Glazing: IG-1/8" Tempered Glass/
Laminate-1/8" Annealed Glass/0.090"PVB by
Solutia/l/8" Annealed Glass
Frame: W-1880mm(74") H-2489mm(98")
Panel: W-965mm(38") H-2413mm(95")
DLO: W-559mm(22") H-2032mm(80")
SPECIFICATION
PRODUCT RATING
TAS 201/202/203-94
Design Pressure: +501-50 psf
Large Missile Impact Rated
Product Tested By: National Certified Testing Laboratories
Report No: NCTL-210-3196-1/SJW2011-072/W 1488
Expiration Date: September 30, 2019