HomeMy WebLinkAboutSCREEN ENCLOSUREs- Design Parameters 1. Building`.OccupaitcyCategory, Paragraph 1604.6 and Table 1604.5: Risk Category 1. 2. Basic Wind Speed, Table 1609C, State of Florida Debris Region & Basic Wind Speed, Paragraph 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed, VuLT=160 MPH 3. Exposure Category, Paragraph 1609.4.3 : C Applicable Codes, Regulation and Standards 1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and Specifications for Aluminum Structure, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association, Inc. Washington, D.C., 2010 Edition 3. ASCE 7-10 General Notes: 1. The contractor shall verify all dimensions prior to construction 2. All work shall comply with all local and regional ordinances. 3. Any deviation from this plan shall be reviewed by the engineer of record and is subject to approval. Specifications The following specifications are applicable to this projects: 1. Where concrete specification are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable. 1.1. Concrete shall conform to ASTM C94 for following components: 1.1.1. Portland Cement Type 1, -ASTM C 150 1.1.2. Aggregate - Large Aggregate 3/4" max - ASTM C 33 1.1.3. Air entraining +/-1%- ASTM C260 1.1.4. Water reducing agent - ASTM C 494 1.1.5. Clean Potable water 1.1.6. Other admixture not permitted 1.2. Metal accessories shall conform to: 1.2.1. Reinforcing Bars - ASTM A615, grade 60 1.2.2. Welded wire fabric - ASTM At 85 1.3. Concrete slump at discharge per chute not less then 3" or more than 5". Water added after batching is not permitted. 1.4. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2 and 3 including hot weather recommendations. 1.5. Moist cure or polyethylene curing permitted. 1.6. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. 1.7. Concrete shall be placed over polyethylene vapor barrier. 1.8. All aluminum components embedded within concrete shall be coated with a bituminous paint or epoxy. 2. Aluminum extrusions shall be 6005 T5 Alloy. 3. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plate to ASTM B633, or stainless steel series "300". 4. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from end 24" on center or #12 screws 6" from end 12" on center. 5. Screened enclosures containing swimming pools shall comply with the applicable requirements of FBC R4501.17 Residential Swimming Barrier requirements. 6. Door location shall be determined by contractor in the field. 7. When installing pavers over concrete slab or footing which are supporting aluminum members, such as continuous screen tracks or upright, the pavers must be bonded to the concrete with an epoxy, thinset, or 3,000 PSI grout to ensure full positive contact with concrete. 8. All flashing and waterproofing shall be provided by the contractor. 9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. Foundation Design: New 8"xB" (1 #5 bar Cont.) thickened edge, 4" monolithic slab Concrete shall be a minimum 2,500 psi. Reber 31" 4-5uiiding_CodeFResidentiii Section-401.4.T�-s-oils testing is not using the presumptive bearing pressure of 1,500 psf. Roof Type Screen Size MANSARD 18 114 MESH HOLLOW SECTIONS SELF MATING BEAM (SMB) PORCH FACTORY BEAM (PFB) 2x2: rxrxo.o46- 2x4SMB: rx4-x O.044-x O.113 FB: rx 3.75'x 0.050" 2x3: rx3'x0.050° 2x5SM8: rx5•x 0.050°x0.100"FB: rx5.75'z 0.055" 2x 4: 2'x 4•x 0.050° 2x 66MB: rx6"X 0.050° x 0.120"FB: rx6.75'x0.05r 2x5: rxS"x0.050" 2x7SMB: rx rx 0.057"x0,120"NEE F5.75 SMB: rX8•x0.072-x BRACE - OPEN eACKSECTIONS-_2x6 O.124° 2x08MB�'XO x0.07rx0.124- I 11'xrx0.040" 2x 106MB: rx10k0.092'x 0,388° 1 x 3: 1-x 3' x 0.045" MINIMUM FASTENER EDGE DISTANCE: 117 SNAP SECTIONS MINIMUM FASTENER SPACING: 314" 2 X 2 Snap: r x 2' x 0.04S" CONCRETE SCREW ANCHOR: SHEET MATEL SCREWS (SMS) : 2 x 35p: rx 3-x0,050- SIMPOSON TITEN HD OR EQUIVALENT ITW BUILDER OR EQUIVALENT 2 x4Srop: rx4-x 0.04S' ROOF OVERHANG CARRY BEAM PER RAN PANELABOVEHOST ROOF OVERHANG 2c10 SMB (TYP) r 3.75 PFB 2x2 BOX, BACK END SIM T- MITERED WTIHW U•CLIP, (4) 13, #14 SMS INTO COLUMNICARRY BEAM, (2) s14 SMS INTO EACH SIDE OF KNEE BRAY OW) COLUMN PER RAN PANELOVFRHANG 3' O.D3r ALUM. SKIN I- B FPS ELITE FOAM CORE ROOF PANELS, (FLOMI.1) NOTE: THIS DRAWING IS FOR ILLUSTRATIVE PURPOSES. DRAWING NOT TO SCALE. USE DIMENSIONS GIVEN. CABLE BRACING MAY TERMINATE AT SLAB IN DIFFERENT LOCATION. MAINTAIN ANGLE PER DETAIL REVISIONS EXISTING POOL ENCLOSURE UJ SvU VIA D rrc�N r �nBYCM de v O O� do°Di J 0 =V o C Z �� 3LL W o a d d ST. LUCIE COUNTY BUILDING IL LU _ Z DIVISION REVIEWED I- r •: W a , It FOR COMPLIANC REVIEWED BY .LL: W c1 . ri W ��' DATE �� PLANS AND PERMIT li o 0 V v IL MUST BE KEPT ON JC R Co NO INSPECTION WILL Bum-; DE 0 - - �p0 flDU0000 THESE PLANS AND ALL PROPOSED ARE SUBJECT TO ANY COMC710 No. B P REQUIRED BY FIE1U INSPECTORS - MAY BE NECESS ARy itq ORDER TO o COrfiPLY WITH fill L APPXARE GOD P _ ..`p- 00 0 p0 GONCFAI.ED FASTENERS OR A17ACHMEMS SHEET ARE THE RESPONSISI00FI A-1 C4NTRACiCR CF s,r� ��D � - t� Cd Ii ti .1 _2 OTE - NOT ALL DETAILS ARE USED FOR THIS PROJECT. SEE PLAN FOR DETAIL CALL OUTS... REVISION$ 118" x 2° x 2• EXTRUDED (4) #14 x 3/4"SMS ANGLE 5052 H-32 ALLOY O O INTO POST O O BRICK PAVERS SONDEDTO� CONCRETE IY z0 • ••.. ',•. • gU� SLAB/FOOTING i d: • •' •• ' 'zdW SEE PLAN ; • d —• w w •', SIDE VIEW BRICK PAVERS. MAY NOT BE INTI PRESENT. FOLLOW ANCHOR MINIMUM CONCRETE EMBEDMENT 1" x 2• BASE PLATE ANCHORED TO CONC W/ 1/4" CONCRETE SCREW ANCHOR (MIN. 1 1/4- EMBED) 6" MAX EACH SIDE OF POST AND 24.O.C, MAX 4x314•SMS 2"x2`DJ POST (1) 3/8' DIA,CONCREfE SCREW ANCHORS (21/2' CONC. EMBED) FRONT VIEW SCALE: CORNER POST (2) #10 x 11/2' SMS THRU SCREW BOSSES BRICK PAVERS. MAY NOT BE PRESENT. FOLLOW ANCHOR MINIMUM CONCRETE EMBEDMENT SLAB/FOOTING ..4: . SEE PLAN SIDE VIEW (4) #14 x 3/4• INTO POST ANCHORED TO CONC Wl 1/4" CONCRETE SCREW ANCHOR (MIN. 11/4" EMBED) 6" MAX EACH SIDE OF POST AND 24• Q.C. MAX (9) #1, 1/8• PLATE O 6063-T6 ALUI R Pit,- SEP 12,9i8 Lermittfng Dep,:,, rj,;ent Sty u� CilE? CoUnty� r 1" x 2' O.B. FASTENED TO CORNER POST W/ #12x11/2" SMS AT 6" FROM EYE CAE H-2 CABLE CONNECTION AT CORNER A-2 SCALE: NTS TOP & BOTTOM RAILS. TYPICALLY@ 1/8'X2-XY EXTRUDED I I (1)1/2• DIA THRU BOLT W/NYLOCK 24' O.C. ANGLE 5052 H.32 ALLOY JAM NUT -IN LIEU OF NYLOCK JP1M EA SIDE NUT. JAM NUT w/THREADLLOCKER 1/8" x 2' x 2" EXTRUDED ANGLE 5052 MAY BE USED H32 ALLOY EA CORNER W/ (2). #14 x 2° BRICK PAVERS TIGHTEN TO CONTACT. DO NOT SMS INTO POST & (1) 3/8' DIA, OVER TIGHTEN CONCRETE SCREW ANCHOR INTO CONCRETE BONDEDTO CONCRETE •, • BRICK PAVERS. MAY NOT BE d' PRESENT. FOLLOW o w • ANCHOR MINIMUM O g • i • .� r, CONCRETE EMBEDMENT v W SLAB/FOOTING w •, d . - •• • ' g w SEE PLAN •, • • • o a . "= SIDE VIEW N Z CONCRETE POST W/ 1"X2' @ BACKSIDE (1) 318• DIA CONCRETE SCREW ANCHORS _ I I UPRIGHT 3/8' x LENGTH AS REQUIRED (21/4" CONC. EMBED) FOR 2114" EMBED CONCRETE SCREW ANCHOR INTO CONCRETE - - - -- — 1")Q• BASE PLATE BRICK PAVERS ANCHORED TO CONC W/ 1/4` i6"MAX CONCRETE SCREW ANCHOR (MIN. 1 1/4• CONIC. EMBED) EACH SIDE OF POST U FRONT VIEW 2 POST TO CONCRETE • • ' < .• i , SLABIFOOTING SEE PLAN d •• •• B �2"x4" Ifid DETAIL DBL. COMPRESSION SLEEVES BRICK PAVERS. MAY NOT BE PRESENT. FOLLOW ANCHOR MINIMUM CONCRETE EMBEDMENT SLAWFOOTING SEE PLAN 1/8' S.S. CABLE 1 1/4' x 5 51W x 1/8• ALUM. FLAT BAR. 6063-T6 ALUM. W/ (2) 3/8' DIA. x 2 3/4' EMBEDMENT CONCRETE ANCHORS w l0� U)It •: n • Zo • .. ,•r .. .4 — • M z •: ly /\ 1/8" S.S. CABLE 2k 1 1/4• x 5 SM. x 1/8' ALUM. p FLAT BAR. 6063-T6 ALUM. 94 IN :d i • ••.. - a ,.., (2) 3/8" DIA. x 3' EMBED \—SLAB/FOOTING CONIC. SCREW ANCHOR SEE PLAN F• 1 CABLE CONNECTION AT FOUNDATION A-2 SCALE:NTS 114" LAGS, 4• FROM ENDS & 18' O.C. MAX l" MIN LONGER THAN THE PANEL THICKENESS. W/ NEOPRENE WASHER ON EACH LAG I' X 0.082 ALUM RECEIVING CHANNEL W/ #12 X 3/4• TOP AND BOTTOM AS END CAP (2) 3/8' DIA THRU BOLTS IF SCREEN WALL BENEATH COMPOSITE ROOF, 1' x 2' W/ (2) #1Q x 2" SMS INTO SCREW BOSSES INTO UPRIGHT & (1) #10 X 2" SMS 6• FROM EACH SIDE OF UPRIGHT & @ 24.O.C. UPRIGHT OR POST. SEE PLAN SHEET FOR MEMBER INFORMATION S CARRY BEAM CONNECTION A-2 SCALE: NTS COMPOSITE ROOF PANEL I' X 1" X 1/8" ALUM ANGLE W/ (3) #12 X 3/4' SMS EACH SIDE CARRY BEAM. SEE PLAN SHEET FOR -MEMBER_ iNFORMATIQ� ; O '�1 0 c T( 0 w 'A J C v♦ i 9_ O w co = V O z N LL LV 9L .. , Lu = N J ~ �C4lto W O a h O a O UC.)IL 0) ma 0 a a /70nn,.. L� R A-2 - NOT ALL DETAILS ARE USED r° ,. 6" WIDE x 0.125" "Z" BRACKET @ EACH BEAM ATTACHED TO FASCIA W/ 3/8' x 3" LAGS (3 PER BRACKET) AND (1) 318' X 3" LAG @ 24" O.C. AT GUTTER 1" x 2" x 0.044" OPEN BACK W/ (2) #10 x 2112"SMS THRU- BEAM INTO SCREW BOSSES (1) #10 x 11/2" SMS 6" ----� FROM BEAM AND 24" O.C. O O 001 MATING ELEMENT 1/8'x2"x2"x2"ALUM. p ANGLEWI (4) #14 x 3/4" SMS EACH FLANGE EACH SIDE OF BEAM 0.062" BACKING PLATE ON INSIDE OF GUTTER 2118° x 1 1/B° x 0.062" (MIN.) ALUM RECEIVING CHANNEL W/ MIN. (2) #12 x 3/4" SMS NOTE: (2) 318" DIA. x 4" LAG SCREWS FOR SPANS GREATER THAN 30'-0" CONTRACTOR TO VERIFY 2° x 4" FASCIA- IF LESS THAN 2" x 4" FASCIA, 2" X 4" SUB FASCIA SHALL BE 5" SUPER PLACED OVER, LENGTHEN GUTTER LAG SCREWS TO FULLY PENETRATE SUB FASCIA, IF OTHER FASCIA, ADD 2" x 4" PT FASCIA wl 12" LAG BOLTS- 1112" INTO TRUSS TAILS- COUNTERSINK FLUSH. WHEN INSTALLING 112" LAG SCREWS. PRE -DRILL w/318" DRILL TO PREVENT SPLITTING G GUTTER BRACE & MATING ELEMENT ATTACHMENT DETAIL A-3 SCALE:NTS MEMBER SIZE EDGE "C" 2X4 1/2" 2X5 1" 2X6-2X10 112" FLASHING EAVE RAIL (SEE A-1 FOR SL INTERNALLY SCREW THRU W/(3) 010 x 11/2" SMS 1"x FASTEN TO EAVE RAIL W/#10x11/2"SMS 6"FROM UPRIGHT & 24" O.C. (1) 1/2" DIA. x 212" THRU BOLT W/ NYLOCK JAM NUT- IN LIEU OF NYLOCK JUM NUT. JAM NUT W/ THREADLOCKER MAY BE USED INSTALLATION REQUIREMENTS: BOLT IS TO BE INSTALLED AS TO NOT DAMAGE BASE MATERIAL DO NOT OVER TIGHTEN. 2" x SMS BEAM NOTCHED OVER UPRIGHT (SEE A-1 FOR SIZE) 6" WIDE x 0.125" "Z' BRACKET @ EACH - BEAM ATTACHED TO FASCIA W13/8" x 3" LAGS (3 PER BRACKET) AND (1) 3/8" X 3° LAG @ 24' O.C. AT GUTTER NOT NEEDED IF GUTTER HAS SPLINE - GROOVE. OTHERWISE, 1" x 2" x 0.044° OPEN BACK W/ (2) #10 x 2112" SMS THRU BEAM INTO SCREW BOSSES (1) #10 x 11/2" SMS 6" FROM BEAM AND 24" 2" x 2" xl/8" x 2" ALUM. RECEIVING CHANNEL W/ (4) #14 x 5/8' SMS — 1-1/4" O.C. INTO BEAM EACH SIDE 5" SUPER I I 16' "Z° GUTTER BRACE O � (1) 318" DIA. x 4" LAG O (2) 318" x W SCREW INTO EXISTING LAG SCREWS OVERHANG FRAMING p OR RAFTER TAIL p /_G "Z" UiT CONTRACTOR TO VERIFY 2" x 4" FASCIA- IF LESS THAN 2" x 4" FASCIA, 2" X 4" SUB FASCIA SHALL BE PLACED OVER, LENGTHEN LAG SCREWS TO FULLY PENETRATE SUB FASCIA, IF OTHER FASCIA, ADD 2" x 4" PT FASCIA w/ 112" LAG BOLTS -112"INTO TRUSS TAILS- COUNTERSINK FLUSH. WHEN INSTALLING 12" LAG SCREWS. PRE -DRILL WWII" DRILL TO PREVENT SPLITTING G-1 GUTTER BRACE & PURLIN ATTACHMENT DETAIL A-3 SCALE: NTS Note - Orientation may be different. 3/.16° 5052-H32 GUSSET —� #14 SMS @ 11/4" O.C. 2" x PURLINS ATTACHED TO — BEAM WMIN (4) 910 x 112" SMS PLACE WASHER UNDER SCREW IN GUSSEST CORNER 2" x SMS UPRIGHT (SEE A-1 FOR SIZE) NOTES: 1. SEE THE NOTE BELOW FOR SCREWS SPACING. THE NUMBER OF SCREWS SHOWN ARE FOR ILLUSTRATIVE PURPOSES. DO NOT COUNT SCREWS ON DRAWING. 2. GUSSET DIMENSIONS AREA MINIMUM (2) REQ'D - (1) EA SIDE OF BEAM- MAYBE INTERNAL OR EXTERNAL 3. AS BEAM SIZE CHANGES, ADD OR SUBTRACT SCREWS TO MAINTAIN 11/4" C/C SPACING. 4. GUSSET LENGTHS REMAIN CONSTANT WIDTHS CHANGE TO MATCH BEAM SIZE. UPRIGHT TO BEAM CONNECTION A-3 SCALE: NTS E TYPICAL INTERNAL OR EXTERNAL GUSSET DETAIL- RIGID MEDIUM A-3 SCALE: NTS 2" x 2" PURLIN DEPTH x 0.125" ALUM ANGLE W/ (4) # 3/4" — SMS EACH FLANGE W/ INTERNAL BACKING PLATES MATING ELEMENT 2" x 2" PURLIN DEPTH x 0.125" ALUM ANGLE W/ (4) # 314" — SMS EACH FLANGE W/ INTERNAL BACKING PLATES w w O 2 Q GUTTER Z" x 2" PURLIN DEPTH x 0.125" ALUM ANGLE W/ (4) # 3/4" SMS EACH FLANGE W/ INTERNAL BACKING PLATES rAA 4 MATING ELEMENT ATTACHMENT GUTTER CORNER DETAIL 4 A-3 SCALE: NTS 2 x 2' PURLIN -NOTCH BOTTOM FLANGE TO OVERLAP UPRIGHT 2 x 3" x 1/8" 5052 - H32 ANGLE EA SIDE OR —� 2 x 3" x 0.062' 5052 - H32 RECEIVING CHANNEL 2" x 3" 1"x 2" x 0.044" OPEN BACK INTERNALY SCREW TO UPRIGHT W/ (2) #10 x 112" SMS & FASTEN TO EAVE RAIL W/ — #10 x 112" SMS SPACED 6" FROM UPRIGHT AND AT 24" O.C. FOR 2" x EAVE RAIL O (4) #12 x 3/4" EACH LEG O EACH SIDE -SCREWS SHALL ENGAGE BOTH PURLIN AND UPRIGHT F SLOPED PURLIN CONNECTION DETAIL A-3 SCALE: NTS REVISIONS W V/ o 0 N W I- ; O) ♦ ♦� Q ' ` 0I v v v o 0 Z wr-3LL W 1L,r V m x V) _1 Z LW�'O�N °a! o d o. G O U 0IL STATER A-3 REVISIONS WOOD: 910 x 3" WOOD SCREWS, 6" FROM GIRT & @ 12- D.C. CONC. 1/4" DIA. x 3" CONCRETE SCREW ANCHOR, 6- FROM GIRT & @ 24" O.C. (4) #10 x 1112" INTO SCREW BOSS 2" HOLLOW SECTION #10 x 3" WOOD SCREWS, 6" FROM GIRT & @ 12" O.C. 2" x HOLLOW SECTION CONC. GIRT OR PURUN 1/4" DIA. x 3" CONCRETE SCREW ANCHOR, 6" FROM GIRT & @ 24" O.C. 6-1 1X2 TO HOST STRUCTURE DETAIL A-4 SCALE: NTS 1" x 2" OPEN BACK INTERNALLY - SCREWED TO BEAM W/ (2) #10 x 2" 2" x 2" 1/8' ANGLE W/ (2) 014 x 3/4" INTO BEAM & 014 x 2" SELF TAPPING SCREW INTO HEADER 0 0 O O O 0 0 0 O 0 I ROOF BEAM -- I 1/2" x 2 1/8- x 0.062 6063-T6 ALUM RECEIVING CHANNEL WI (6) #14 x 3/4" SMS EACH FLANGE OST 1/4" x 3" LAG SCREWS, 6" FROM END & @ 24" O.C. CONC. 1/4" DU\. x 2 114" CONCRETE SCREW ANCHOR, 6" FROM END & @ 24" O.C. (3) 1/4" x 3" LAG SCREWS, 6" FROM END & @ 24" O.C. CONC. (3) 1/4" DIA. x 2 1/4" CONCRETE SCREW ANCHOR, S" FROM END & @ 24" O.C. G-2 BEAM TO HOST STRUCTURE ATTACHMENT r A-4 SCALE: NTS GUSSET PLATI PER E-SERIES DETAIL #2 DETAIL #1 SELF MATING BEAM CONTRACTOR TO INSTALL (2) #14 x 2"SMS THRU BRACE INTO BEAM THRU GUSSET PLATE NTRACTOR SHALL RUN THRU BOLT TO ATTACH NYLON WASHER & UNLESS STEEL NUT Fi-3 ROOF BRACING CONNECTION DETAIL A-4 SCALE:NTS 2" x 2" x 1/8" x EAVE BEAM DEPTH INTERNAL ALUM RECEIVING CHANNEL W/ (4) #14 x 3/4" EACH FLANGE 6063-T6 ALUMINUM 1 1/2" x 16" x 0.125DETAIL AT CORNER (PLAN VIE" ALUM STRAP W/ (5) 914 x 3/4" IN BOTH CARRIER BEAM AND POST EACH SIDE --4" x 2" O.D. ATTACH TO UPRIGHT WITH (2) #10 x 2 1/2" SMS THRU 1"x 2" O.B. ATTACHED---'-""" TTACHE UPRIGHT INTO SCREW BOSSES EACH SIDE OF POST W/ PLUS #10 x 1 1/2" SMS 6" FROM 012 x 1 1/2" SMS 6" EACH S1DE OF UPRIGHT AND FROM BOTTOM AND 24' TYPICAL AT 24" O.C. MAX O.C. 063-T6 ALUM POST PER PLAN S CARRIER BEAM CONNECTION A� SCALE: NTS CARRIER BEAM PER NOTCH UPRIGHT AROUND CARRIER BEAM O O O O 1"x 2" FASTEN TO CARRIER O O O O BEAM W/#10xIIW SPACED 6' FROM END AND 4 n @ 24" O.C. O 0 CARRIER BEAM PER -Y x 2" x 1/8" x ROOF BEAM DEPTH NOTCH UPRIGHT AROUN ALUM ANGLE EACH SIDE OF CARRIER BEAM UPRIGHT W/ (8) #14 x 3/4" EACH LEG EACH SIDE 1"x 2" FASTEN TO CARRIER 346 ALUM POST BEAM W/ #10 x 1 1/2" PER PLAN SPACED 61FROM END AND - @ 24' O.C. D-2 ROOF BRACING CONNECTION DETAIL A-4 SCALE: NTS 2" x 2" x 1/8" x ROOF BEAM DEPTH ALUM ANGLE EACH SIDE OF UPRIGHT W/ (8) #14 x 3/4" EACH LEG EACH SIDE 6063-T6 ALUM POST PER PLAN ROOF BEAM TO UPRIGHT CONNECTION SCALE: NTS W J C d 0 0 N W F- 9 J V•`c` ♦ ♦ LL v = V O O -3LL Z w W (L = m=J z W L:V00 waT ood 0 ♦V V a A-4