Loading...
HomeMy WebLinkAbout1404-0377-HVAC LOAD CALCULATIONSSCANNED BY St. Luda-CCU* Rizk Residence HVAC Load Calculations for Rizk Lot 1234 Nettles Blvd. Ft. Pierce, Florida Prepared By: Residential Energy Calc's Saturday, January 24, 2015 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. Me �-- t T -t Titl Project Of Rizk Residence Designed y: QEA Associates Project Da i: Wednesday,. April 16,.2014 Client Nan �e: Rizk Client Add' ess: Lot 1234 Nettles Blvd. Client City 1 Ft. Pierce, Florida Company ame: Residential Energy Calc!s Referenc 'City: Fort Pierce, Florida Building rientation: Front door faces East Daily Tem" erature Range: Medium Latitude: 27 Degrees Elevation: 25 ft. Altitude F ctor, 0.999 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 42 39.4 n/a n/a 70 n/a Summer: 90 78 59% 50% 75 61 �eck�,Fi� -- . ores Total Bull' ing Supply CFM: 1,518 CFM Per Square ft.: 0.884 Square ft of Room Area: 1,717 Square ft. Per Ton: 491 Volume (I r} of Cond. Space: 13,736 7 bld' Total He' Ting Required Including Ventilation Air.- 33,526 Btuh 33.526 MBH ti Total Se '6ible Gain: 33,783 Btuh 81 % Total Lat nt Gain: 8,170 Btuh 19 % Total Co '11�ing Required Including Ventilation Air: 41,953 Btuh 3.50 Tons (Based On Sensible + Latent) Rhvac is ACCA approved Manual J and Manual D computer program. Calculati, ns are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All comp;! ted results are estimates as building use and weather may vary. Be sure I I o select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your des Ign conditions. C:\ ... \Rik Residence.rh9 Saturday, January 24, 2015, 11:09 AM Rh Re idential & Light Commercial HVAC Loads. tote aottware uevelopmen;, mc. �; Res�dentraF .nergy Calc's Rizk Residence: Port Sa�nt.Llicie, FL, 34983 Pa e 3 Winter: 42 39.4 80% n/a 70 n a Summer: 'l 90 78 59% 50%, 75 61.09 Duct Sizi.' ":;In uts °: _:- Main Trunk Runouts Calculate Yes Yes Use Sche Jule: Yes Yes Roughnei s Factor: 0.00300 0.01000 .Pressure ,Drop: 0.1000 in.wg./l00 ft. 0.1000 in.wg./l00 ft. Minimum Velocity: 650 ft./min 450 ft./min Maximu Velocity: 900 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximurr Height: 0 in. 0 in. Infiltratio Winter Summer i� Specified: 0.380 AC/hr 0.200 AC/hr K CFM 46 CFM Infiltratio � Actual: 0.364 AC/hr 0.168 AC/hr Above G ade Volume: X 13,736 Cu.ft. X 13,736 Cu.ft. 5,000 Cu.ft./hr 2,302 Cu.ft./hr X 0.0167 X 0.0161 Total Bui ding Infiltration: 83 CFM 38 CFM Total Bui ding Ventilation: 25 CFM 25 CFM --- Syst m 1--- Infiltratio '� & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltratio � & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltratio '' & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter I r filtration Specified: 0.380 AC/hr.(87 CFM), Construction: Average Summer infiltration Specified: 0.200 AC/hr (46 CFM), Construction: Average Duct: Lo &Factor $cenani s for s stem 1 Attic `Duct Duct Surface -From No T ,e De`s..cn tion .. Location Ceiling= Leaka e . Insulation _ Area, MDD 1 Su'�ply Attic 16B 0.12 6 397 No 1 Re. urn Attic 16B 0.12 6 220 No C:1... 1Ritk Residence.rh9 Saturday, January 24, 2015, 11:09 AM Rh�ie iZe ';idenBal S Ught Cbom'dididlHVAC.Loads Elite'Software Development, tnc ResideniiaF, GaICS " 4 Ri K ResFa Port:Samt L {,nergy cie,FL}..34983. ' ecq 'Load 'review Report Sys Net ft.2 Sen Lat Net Sen Sys Aot Duct ScopeHtg Ton /Ton Area Gain Gain Gain Loss CFM CFM CFM Size Building 3.50 491 . 1,7171 33,783 8,170 41,963, 33,528 426 1,518: 1,518 System 1 3.50 491 1,717 33,783 8,170 41,953 33,526 426 1,518 1,518 14x18 Ventilation 412 1,038 1,450 769 Duct Latent 1,437 1,437 Zone 1 - CI : 37%, Htg.: 461/o 724 14,497 2,090 16,587 15,014 195 660 660 10x13 1-Ntchen 320 9,690; 875 10,565 7.745 101 441 441 5-5 2-Dining 95 367 348 715 847 11 17 17 1-4 3 Living 176 3,657 480 4,137 4,740 62. 166 166 2-5 . 4-Stairway 77, 327 48 375 817 11 15 15 1-4 5-Foyer 57 456 339 795 865 11 21 21 1-4 Zane 2 - CI 63%, Htg.: 54% 993 24,873 3,605 28,478 17,743 231 1,132 1,132 12x17 6-Bath2 77, 1,270 443 ' 1,713 1,51 0 20 58 58 1-4 7-Master th 126 1,055 443 1,498 1,613 21 48 48 1-4 8-Master Eedroom 272 5,033 755 5,788 4,865 63; 229 229 3-5. 9-Walk In it .Closet 42 263 48 311 471 6. 12 12 1-4 10-Bedroo P 2 182 3,315 684.• 3,999 2,753 36 151 1.51 2-5 11-Laundr, 54 147_ 600 747 161 2 7 7 1-4 aurora 70 6,831 48 6,879 2,198 29 311 311 3-6 13-Den i 170 6,958 584 7,542 4,171 54 317 317 3-6 -Sum of room aiifrows may be greater than system airflow because system has i idliplezones. i i ilf I i ii i i i I i ' i C:\ ...\Rizl 1 Residence.rh9 Saturday, January 24, 2015, 11:09 AM �il ' Duct Sze Preview Room or Source Minimum Maximum Rough. Design SP Duct Duct Htg I Cig' Act. Duct Duct Name Velocity Velocity Factor L/100 Loss Velocity Length Flow Flow Flow Size System 1 SupplyRu outs Zone 1 1-Kitchen Built -In 450 750 0.01 0.1 646.7. 101 41� 441 5-5 2-Dining Built-in 450 750. 0.01 0.1 191.2: 11 1 17 1-4 3-Living .- Built-in 450 750' - - 0.01 0.1 _- 610.1 62 1 166 166 2-5 4-Stairwa Built -In 460 750 0.01' 0.1 170.3 11 f 15 15 1-4 5-Foyer Built -In 450 750 0.01 0.1 237.9 _, 11 21' _.-. _ 21 1-4 Zone-2 6-Bath2 Built -In 450 750- 0.01 , 0.1 662.2 20 w B& 58 1-4 7-Master Bath Built-in 450 750 0.01 0.1 550 3;. 21 48[ 48 1-4 8-Master edroom Built -In 450; 750 0.01, 0.1' 559.8 63 229k 229 3-6.I 9-Walk In Closet - Built -In 450 750 --- 0.01 .. ._ 0.1 .__. 137.1 6 12 12 1-4 10-Bedro 2 Built -In 450 750 0.01 0.1 553.1 36 `151 151 2-5 11-Laund i Built -In 450' 750 0.01 0.1 76.9 2 7 1-4 12=Stai Built -In 450 ; 750 0.01 0.1 527.6 29 3t1" 311 3-6 13-Den Built-in 450' 750 0.01 0.1 537 4 T - 54 � -, 317 3-6 Other Duct in System 1 Supply M „in Trunk Built -In 650 goo' 0A03 0.1 867.6 426 I 1 % 1,518 14x18 Summary System 1 Heating Row: 426 Cooling Flow: 1518 C:1... 1Rizk r1i esidence.rh9 Saturday, January 24, 2015, 11:09 AM 4 thvac �R S'e _htc9mmerci HVAc Loads: lei0d ie Total ildim summary Loads IA-cb-o: Gl*ing-Siggle pane, operable window, clear, I metal fr4me with break,. u-value 1.08,. SHGC 0.75 IA-cm-o: Glozing-Single pane, operable window, clear, metal me no break, u-value 1.27, SHGC 0.75 4,' 7A-1: G-1aziq�' i g-GI ass or plastic block, smooth or wide ribs or fluted',1 no screen, no coating, u-value 0.6, SHGC 0.65 11 1 OA-m: Gla 1 ing-French door, single pane clear glass, metal N me no break, u-value 1.67, SHGC 0.53 11 D: Door- ood - Solid Core 13A-5oc . s: all -Block, board insulation only, R-5 board insulati n, open core, siding finish 12E-Osw:'P rt-Frame, R-1 9 insulation in 2 x 6 stud cavity, no boa 6 insulation, siding finish, wood studs 12E-Osw: all -Frame, R-19 insulation in 2 x 6 stud cavity, o'board insulation, siding finish,'wood studs 1*6C_T9-: R of/Ceiling-Under Attic with Insulation on Attic' Floor ( 11so use for Knee Walls and Partition Ceiling ), Vented Attic, No Radiant Barrier, White or Light Ceiling Shingles, Any Wood Shake, Light Metal,, Tar an Gravel or Membrane, R-1 9 insulation 22A-ph: FI or -Slab on grade, No edge insulation, no insulat on below floor, any floor cover, passive, heavy moist Pi 2013-30: FI . or -Over open crawl space or garage, Passive, R-30 blanket insulation, any cover Subtotals for structure: People: Equipme t: Lighti Ductwork Infilt tio Winter CFM:- 83, Summer CFM: 38 Ventilatio Winter CFM: 25, Summer CFM: 25 Total Build"inq Load Totals: Check Fi " ures Total Bui ding Supply CFM: 1,518 Square fl 1 of Room Area: 1,717 sate re ueveropr 117.5 4,179 0 8,606 8,606 4 68. 0 286 286 24 1,122 0 1,470 1,470 42 352 0 336 336 1306.3 4,574 0. 2,501 2,501 91 93 0 93 93 88 :1168 0 104 104 1717 2,357 0 3,365 3,365 88 3,346 0 0 0 993 973 0 349 349 23,301 0 25,232 25,232 4 800 920 1,720 3,300 600 3,900 0 .0 0 6,890 1,437 5,986 7,423 2,566 1,595 633 2,228 769____ _._1,038412 1,450 33,526 8,170 33,783 41,953 CFM Per Square ft.: 0.884 Square ft. Per Ton: 491 Volume (i-) of Cond. space: 13,7361 'Buildin Total He-lting Required Including Ventilation Air: 33,526 Btuh 33.526 MBH Total Se I sible Gain: 33,783 Btuh 81 % Total Lati"11"nt Gain: 8,170 Btuh 19 % Total Co ling Required Including Ventilation Air. 41,953 Btuh 3.50 Tons (Based On Sensible + Latent) Rhvac ijjan ACCA approved Manual J and Manual D.computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. I All computed results' are estimates as building use and weather may vary. �,�gn conditions. select a unit that meets both sensible and latent loads according to the manufacturer's performance data at Be sure rmanc i your i C:\ ... \Ri Residence.rh9 Saturday, January 24, 2015, 11:09 AM RhVac_- Res denttal &.Light Co_ mmercia! HVAC Loads , , � sate software, ueveiopment,;mc.: Residential E;` ergy Calc's Rrzk Residence: Port Saint Lugs FL' 34983, Pa e 7 BUildin i Pie Chart -.. Build ng Los 33,5 1116 Wall 14 Btu , Wall Buildi'I g Gai 41,9 3 Glass 4d Glass 34% ctwork 21 % x1% D uctwork 18% Equipment 9% e 4% Door 1 C:\ ...1Rizk Saturday, January 24, 2015, 11:09 AM RhVac Residential'&,Light Commercial HVAC Loads EIrte:Software Development,"Inc.' Resid6i tat nergy Calc's Rtzk Residence; f antLreF34Port S Pa e 8 ®etaileo Room Loads - Room 9 - Kitchen (Peak Fenestration Gain Procedure) General i` .... . Room is in " one 1, which peaks at 2 pm Calculationi'Mode: Htg. & clg. Occurrences: 1 Room Len 'th: 20.0 ft. System Number. 1 Room Wid 16.0 ft. Zone Number: 1 Area: Ceiling Hei i ht: 320.0 sq.ft. 8.0 ft. Supply Air: Supply Air Changes: 441 CFM 10.3 AC/hr Volume: 2,560.0 cu.ft. Req. Vent. Clg: 0 CFM Number of egisters: 5 Actual Winter Vent.: 6 CFM Runout Air: 88 CFM Percent of Supply.: 1 % Runout Du Size: 5 in. Actual Summer Vent.: 6 CFM Runout Air elocity: 647 ft./min. Percent of Supply: 1 % Runout Air elocity: 647 ft./min. Actual Winter Infil.: 14 CFM Actual Loss 0.343 in.wg./l00 ft. Actual Summer Infil.:. 7 CFM ltern `. Area U Htg Sen Clg Lat _ Sen. Description I Quanti `.., Valle._ ` `HT = Loss.. HTM - pain:.. Gain E -Wall-13A ',5ocs 18 X 8 131 0.125 3.5 459 1.9 0 251 SE-Wall-13 1,175ocs 11 X 8 53 0.125 3.5 186 1.9 0 101 S -Wall-13A 5ocs 11.5 X 8 50 0.125 3.5 175 1.9 0 96 E -GIs-lA-c ,o shgc-0.75 0%S 9 1.080 30.2 272 76.7 0 690 SE-GIs-lA-c -o shgc-0.75 0%S 35 1.270 35.6 1,245 80.2 0 2,806 E -GIs-7A-1 'shgc-0.65 0%S (2) 4 0.600 16.8 68 61.5 0 246 S -GIs-IA-cb'lo shgc-0.75 0%S (2) 24 1.080 30.2 726 64.1 0 1,538 S -GIs- shgc-0"75 0%S 18 1.080 30.2 544 64.1 0 1,153 UP-Ceif-16C'I19 20 X 16 320 0.049 1.4 439 2.0 0 627 Floor-22A-phli41 ft._Per. _ 41_ 1.358 38.0 1,559 0:0 0 0 Subtotals for Structure: 5,673 0 7,508 Infil.: Win.: 1 (4, Sum.: 6.6 324 1.367 443 0.336 275 109 Ductwork: 1,629 1,473 Equipment: _ 600 600 Room Totals:' i I� I I I I i 7,745 875 9,690 C:\ ...\Rizk Re�idence.rh9 Saturday, January 24, 2015, 11:09 AM II Mac as id ,hflal 8 Light Commercial tNAC Loads Resitlent Energy Calc'sResidence Eftte Software Development, Lucie,"FL":34983 :., , ,ort'saint Pa e`9 Detail'' d Room Loads - Room 2 - Dining (Peak Fenestration Gain Procedure) General h _ Room is in zone 1, which peaks at 2 pm Calcufati °n Mode: Htg. & clg. Occurrences: 1 Room Le gth: 13.5 ft. System Number: 1 Room Wk the 7.0 ft. Zone Number: 1 Area: 1 94.5 sq.ft. Supply Air: 17 CFM Ceiling H fight: 8.0 ft. Supply Air Changes: 1.3 AC/hr Volume: �I 756.0 cu.ft. Req. Vent. Clg: 0 CFM Number 'f Registers: 1 Actual Winter Vent.: 1 CFM Runout A r: 17 CFM Percent of Supply.: 4 % Runout D I ct Size: 4 in. Actual Summer Vent.: 0 CFM Runout A "r Velocity: 191 ft./min. Percent of Supply: 1 % Runout Ail,�� Velocity: 191 ft./min. Actual Winter Infil.: 2 CFM Actual Lolls: 0.043 in.wg./100 ft. Actual Summer Infil.: 1 CFM Item 1° Area U Htg Sen Clg Lat ` 5en Desen fio'' Quanti ° Value ; L-ITM Loss HTIVI. 'Gain ', Garn S -Wall-134,-5ocs 7 X 8 56 0.125 3.5 196 1.9 0 107 UP-Ceil-16 -19 13.5 X 7 94.5 0.049 1.4 130 2.0 0 185 FP-Ceil-1 �h 7 ft..Per. 7 1.358 -38.0 266 0.0 0 0 Subtotals f Structure: Infil.: Win.: .5, Sum.: 1.1 56 _ 592 1.375 77 0.339 0 48 292 19 Ductwork: 178 56 Equipment: I ---- - - - — --- - - -- - 300- _. _ . - 0 Room Totas: i i I! �I I I it II y 'I i I I i I I i i II I I I 847 348 367 C:1... 1Rizk Re �lidence.rh9 Saturday, January 24, 2015, 11:09 AM n f2hV$� Resider►trat.. dential.& Ught;CommercwHVAC loads El�te.Softv+iare Development; nc:: nergy, Calc's ` { R�zk Residence: °cie, P-.or[ Samt L .F.L.,34983, ,. :,;: = „ ... .. :..: Pa a .10 Detailea' Room Loads -Room 3 -Living (Peak Fenestration Gaon Procedure) General: Room is 211,,Izone 1, which peaks at 2 pm CalculatiMode: Room Len the Htg. & clg. 13.5 ft. Occurrences: System Number: 1 1 Room Width: 13.0 ft. Zone Number: 1 Area: 'I 175.5 sq.ft. Supply Air: 166 CFM Ceiling He'ght: 8.0 ft. Supply Air Changes: 7.1 AC/hr Volume: 1,404.0 cu.ft. Req. Vent. Clg: 0 CFM Number of'Registers: 2 Actual Winter Vent.: 4 CFM Runout Ai '� 83 CFM Percent of Supply.: 2 % Runout Du t Size: 5 in. Actual Summer Vent.:. 2 CFM Runout Air iVelocity: 610 ft./min. Percent of Supply: 1 % Runout Air Velocity: 610 ft./min. Actual Winter Infil.: 9 CFM Actual Los : 0.306 in.wg./l00 ft. Actual Summer Infil.: 4 CFM Item:.- ". = Area U H#g Sen Clg � Lat : Sen: Descn tion _ , '., Quantt` ., Value...Lo`ss f-1TW! Gain Gain: S -Wall-13 ','Sots 13 X 8 50 0.125 3.5 175 1.9 0 96 W Wall-13 1-5ocs 13.5 X 8 108 0.125 3.5 378 1.9 0 207 S -GIs-1A-c Lo shgc-0.75 94%S (3) 54 1.080 30.2 1,632 44.1 0 2,382 UP-Ceil-16 it 19 13.5 X 13 175.5 0.049 1.4 241 2.0 0 344 Floor-22A-p 27 ft..Per. 27 1.358 38.0_ 1,027 0.0 0 0 Subtotals fo Structure 3,453 0 31029 Infil.: Win.: '.4, Sum.. 4.3 212 1.368 290 0.340 180 72 Ductwork: 997 556 E _ ment: q�p i ___..__.._.--------------------------------------- .-..-- -- _. _. ___......--------------------- 300 --....- ---------------------- 0 Room Total ` I it Ili I I I i I i 4,740 480 ' 3,657 C:1... 1Rizk Relldence.rh9 Saturday, January 24, 2015, 11:09 AM II { RhV�a Re �denhal+, i.ight C,ommerc�al HVAC Loads:,:EIiW.S6ftwarb Development; Inc.: Residert6al nergy Ealcs rI Rik Residence, 'Po'rtSaint L cie, FL:34983.,, - 1 # � , s Pa` e.1�1 Detaileo Room Loads - Room 4 - Stairway (Peak Fenestration Gain Procedure) Room is in'j2one 1, which peaks at 2 pm Calculatio Mode: Htg. & clg. Occurrences: 1 Room Len the 11.0 ft. System Number: 1 Room Wid h: 7.0 ft. Zone Number: 1 Area: 77.0 sq.ft. Supply Air: 15 CFM Ceiling Hei' ht: 8.0 ft. Supply Air Changes: 1.4 AC/hr Volume: I,� 616.0 cu.ft. Req. Vent. Clg: 0 CFM Number of egisters: 1 Actual Winter Vent.: 1 CFM Runout Air:; 15 CFM Percent of Supply.: 4 % Runout Du ` Size: 4 Actual Summer Vent.: 0 CFM Runout Air, .in. elocity: 170 ft./min. Percent of Supply: 1 % Runout Air elocity: 170 ft./min. Actual Winter Infil.: 2 CFM Actual Los + 0.034 in.wg./100 ft. Actual Summer Infil.: 1 CFM Item t Area, U Htg Sen Clg: Lat Sen Desenptlon. Quantif<' .Value .' HTM . Loss HTM =Gam ,;; Gain; W -Wall-13 '! 5ocs 7 X 8 56 0.125 3.5 196 1.9 0 107 UP-CeiI-16C�!1911 X7 77, '17 0.049 1.4 106 2.0 0 151 Floor-22A-p -_-.—__ ft Per 7 1.358 38.0 266 0.0 0 . 0 Subtotals forlStructure: 568 0 258 Infil.: Win.: 21I6, Sum.: 1.1 56 1.375 77 0.339 48 19 Ductwork: — 172 50 Room Totals I i I� I �I II II 'I I i i i i I I I 817 48 327 C:1... 1Rizk Resi�ence.rh9 Saturday, January 24, 2015, 11:09 AM II sidmts Calc's w [=hA Energy Port<Sai _t Lucie, 34983 = Rik Residence. FL _ _ <' -Pa e.12 DetailDetailo, d Room Loads - Room 5 - Foyer (Peak Fenestration Gain Procedure) Room is i i zone 1, which peaks at 2 pm Calculati 'n Mode: Htg. & clg. Occurrences: 4 Room Le ,gth: 10.0 ft. System Number: 1 Room Wi' th:. 5.7 ft. Zone Number. 1 Area: 57.0 sq.ft. Supply Air: 21 CFM Ceiling H 'ight: 8.0 ft. Supply Air Changes: 2.7' AC/hr Volume: II� 456.0 cu.ft. Req. Vent. Clg: 0 CFM Number o i Registers: 1 Actual Winter Vent.: 1 CFM Runout Ai': 21 CFM Percent of Supply.: 3 % Runout D bt Size: 4 in. Actual Summer Vent.: 0 CFM Runout Ai. lVelocity: 238 ft./min. Percent of Supply: 1 % Runout Ai '� elocity: 238 ft./min. Actual Winter Infil.: 2 CFM Actual Loss: 0.066 17 in.wg./100 ft. Actual Summer Infil.: 1 CFM [Item` j Area: U Htg Sen Cig Lat ::Seri '04scnptio . ` Quanf'i "', Value _HT HTM`` `=Gain_ , Gain E Wall-13 ;'-5ocs 5.7 X 8 24.6 0.125_ 3.5 86 1.9 0 47 E -Door-11 3 X 7 21 0.390 10.9 229 10.1 0 213 UP-Ceil-16 -19 10 X 5.7 57 0.049 1.4 78 2.0 0 112 Floor-2 h 6 ft.. Per. 6 1.358 38.0 228 0.0 0 0 -- ,i-.--__ . __.---.-_—__-- ----------- --_ _._ -- Subtotals fo Structure: — -- -- - - --- --- - -... .....------- -- --- .-.. ---- - - - . _...- - —... Infil.: Win.: .0, Sum.: 0.9 46 621 1.360 62 0 0.329 39 372 15 Ductwork: 1 182 69 Equipment: !� _ 300 0 Room- Total �I I` I li� 9 III , I ,I I I 865 339 456 C:\ ...\Rizk Residence.rW Saturday, January 24, 2015, 11:09 AM iik. `—"Ri -Reside lja� eV P C6n tierclail; sidefflialA Light n Residence .,,k" d6ba! jftiin lu .. 11 . 'e r "I", � IE '; '% " I I 1846rgy�Ulds, Juc 13 -;P�ifs t Cle;�LFL,'-�3498 0 th2 (Peak pDetiail d Room Loads - Room 6 - Ba Fenestration. Gain Procedure) H Room is 111 zone Z, wr � Calcuiatiqn Mode: Room Le fi'gth: Room Wi th: Area: Ceiling H I 'ight: Volume: Number- 0 Registers: Runout Mir': Runout D ct Size: RunoutAi Velocity : Runout Ai'I Velocity: Actual Lo � It at 5 pm 1 Htg. & c1g. Occurrences: 1 11.0 ft. System Number: 7.0 ft. Zone Number: 2 77.0 sq.ft. Supply Air: 58 CFM 8.0 ft. Supply Air Changes: 5.6 AC/hr 616.0 cu-ft- Req. Vent. Clg: 0 CFM I Actual Winter Vent.: 1 CFM 58 CFM Percent of Supply.: 2 % 4 in. Actual Summer Vent.: I CFM 662 ft./min. Percent of Supply: 1 7 % CFM 662 ft./min. Actual Winter Infil.: 3 CFM 0.492 in.wg./100 ft. Actual Summer Infil.: SW-Part-1 00/1 50-12E-Osw 14 X 8 SW -Door -I , 11 D 7 'is s -0.757%S 'b I 0�s,X N -GIs hgc UP-Ceil-16 -19 11 X 7 ' 16"J',,� _ tC Floor-20P- "0 7--X 1-1-1--- - _--_--- Subtotals I -- Subtotals ,,r Structure: Infil.: Win.:,, .5, Sum.: 3.4 Ductmork- gquipment: --------------- ------------- Room Tota S': 91 21 13.8 77 77 "Sey C19 ben HT J :G a 0.125 3.5 148 1.9 U 81 0.068 1.0 93 1.0 0 93 0.390 5.9 123 5.9 0 123 1.080 30.2 417 39.5 0 545 0.049 1.4 106 2.0 0 151 0.035 1.0 75 0.4 0 27 962 0 1,020 1.369 230 0.339 143 57 318 193 300 0 1,510 443 1,270 C:\ ... \Rizk Saturday,January 24, 2015, 11:09 AM - Elite Software Development',,lnc:. RPM identlal &:UghtCommercial HVAC Loads; Resrdenttai nergy Calc's J Rik Residence t Port Saint• L "cie„FL .34983 . Pa 'e"14 Detaileo Room Loads - Room 7 - Master Bath (Peak Fenestration Gain Procedure) General Room is in,!zone 2, which peaks at 5 pm Calculatio Mode: Htg. & c1g. Occurrences: 1 Room Len the 14.0 ft. System Number: 1 Room Wid h: 9.0 ft. Zone Number: 2 Area: I 126.0 sq.ft. Supply Air. 48 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 2.9 AC/hr Volume: 4 1,008.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 1 CFM Runout Air '1 48 CFM Percent of Supply.: 3 % Runout Du t Size: 4 in. Actual Summer Vent.: 1 CFM Runout Air,Uelocity: 550 ft./min. Percent of Supply: 1 % Runout Air Velocity: 550 ft./min. Actual Winter Infil.: 7 CFM Actual Los 0.341 in.wg./100 ft. Actual Summer Infil.: 3 CFM Item '' Area U °Htg en Clg Lat ; `Sen _,..... _ .. Quanti ` ., Value ... =HTM . ; ° Loss - HTM :'.Gam ,`Gain. N -Wall-13t16n=5ocs 6 X 8 42 0.125 3.5 147 1.9 0 80 E -Wall-13 '1�5ocs 15 X 8 120 0.125 3.5 420 1.9 0 230 N -GIs-lA-c o shgc-0.7515%S 6 1.080 30.2 181 39.5 0 237 UP-Ceil-16 " 1 19 14 X 9 126 0:049 1.4 173 2.0 0 247 Floor-20P-3 . 9 X 14 126 0.035 1.0 123 0.4 0 44 Subtotals fo Structure: �5, 1,044 0 838 Infil.: Win.: Sum.: 3.4 168 1.369 230 0.339 143 57 Ductwork: 339 160 Equipment_300 0' Room Total !I I I �l 'I 'I it i it !I y I i i i I I I it 1,613 443 1,055 C:\ ...\Rizk Re 'idence.rh9 Saturday, January 24, 2015, 11:09 AM �jl I Rhvac es�dent�al & Light Commercial HVAG Loads ElrterSoflware D®velopment; Inc: Resrcient 't Energy Calc's - Rqk Residence Port3ain Lucie, FL 34983 ®etai ld Room Loads - Room 8 - Master Bedroom (Peak Fenestration Gain ' Procel � ure) [Ginoral . .-.. Room is n zone 2, which peaks at 5 pm Calc al ti'I n Mode: Htg. & clg. Occurrences: 1 Room Le'i gth: 17.0 ft. System Number. 1 Room W tlth: 16.0 ft. Zone Number: 2 Area: �I 272.0 sq.ft. Supply Air: 229 CFM Ceiling H' ight: 8.0 ft. Supply Air Changes: 6.3 AC/hr Volume: 11 2,176.0 cu.ft. Req. Vent. Clg: 0 CFM Number f Registers: 3 Actual Winter Vent.: 4 CFM Runout A Ir: 76 CFM Percent of Supply.: 2 % Runout D ct Size: 5 in. Actual Summer Vent.: 3 CFM Runout Aj'Velocity: 560 ft./min. Percent of Supply: 1 % Runout A'r Velocity: 560 ft./min. Actual Winter Infil.: 1.3 CFM 11 Actual Lo s: 0.258 in.wg./100 ft. Actual Summer Infil.: 6 CFM Item.. Area U Htg Sen C.Ig I Desen fio ," Quantit Value ; HTM, Loss HTIUI Gam_ =Gain• NE-Watt-1 A-5ocs 14 X 8 70 0.125 3.5 245 1.9 0 134 S -Wall-13 -5ocs 12.5 X 8 80 0.125 3.5 280 1.9 0 153 SE-Wall-1JE-Osw 11 X 8 88 0.068 1.9 168 1.2 0 104 NE-GIs-1Am-o shgc-0.75 0%S 42 1.270 35.6 1,494 47.2 0 1,984 S -GIs-1A--o shgc-0.75 0%S (2) 20 1.080 30.2 604 46.7 0 934 UP-Ceil-1-19 17 X 16 272 0.049 1.4 373 2.0 0 533 -Floor-20P16 X 17 272 0.035 1_0 267 0_4 0 95 Subtotals f 'r Structure: _ T _ 3,431 V_ 0 3,937 Infil.: Win.: 3.3, Sum.: 6.1 300 1.370 411 0.337 255 101 Ductwork: �I 1,023 765 People: 20 ;Ilat/per, 230 sen/per: 1 200 230 Equipment: ''I 300 0 ------ - - Room Total is .I I I �I q I II II III i I I I I i it I i I - - - - ----- -- -- 4,865 -- -..__ .._ .. 755 _ 5,033 � C:1... 1Rizk Re ! dence.rh9 Saturday, January 24, 2015, 11:09 AM C Rhv�c R sidenttal Ught Commercial HVAC Loads. Elite:Software Development; C. r Residerrtra Energy Calc s; Rizk Re"sidenci:: 'P.ort"Saint Pa'e 16 Detailtd Room Loads - Room 9 - Walk In Closet (Peak Fenestration Gain Proceure) General ; Roois zne 2, which peaks at 5 pm T;oode: Calcm ai tin Htg. & clg. Occurrences: 1 Room Le Igth: 7.0 ft. System Number: 1 Room Wi the 6.0 ft. Zone Number: 2 Area: it 42.0 sq.ft. Supply Air: 12 CFM Ceiling H fight: 8.0 ft. Supply Air Changes: 2.1 AC/hr Volume: jl 336.0 cu.ft. Req. Vent. Clg: 0 CFM -Number o,IRegisters: 1 Actual Winter Vent.: 0 CFM Runout Ai : 12 CFM Percent of Supply.: 3 % Runout D ct Size: 4 in. Actual Summer Vent.: 0 CFM Runout Ai !Velocity: 137 ft./min. Percent of Supply: 1 % Runout Ai Velocity: 137 ft./min. Actual Winter Infil.: 2 CFM Actual Los : 0.023 in.wg./100 ft. Actual Summer Infil.: 1 CFM Item .,:: Area U Ntg $en Clg Lat Sen. Desc�i do Quanti.'" Value.:: HTM - Loss HTM S -Waft-13 'L 5ocs 7 X 8 56 0.125 3.5 196 1.9 0 107 UP-Ceil-16-19 7 X 6 42. 0.049 1.4 58 2.0 0 82 Floor-20P-30 6 X 7 42 0.035 1.0 41 0.4 0 Subtotals for Structure: 295 _ 0 _15 204 Infil.: Win.: .5, Sum.: 1.1 56 1.375 77 0.339 48 19 U 99 40 Room Total I i� III I 'I ,I ii III II I l i i I III 471 ---- --- --- -- 48 ' , 240 63 I C:1... 1Rizk Res�ldence.rh9 Saturday, January 24, 2015, 11:09 AM q RhveC esidentyal Ltght Commercial HVAC Loadsr h Ebbe;Software Development, Inc. Res�denri Energy Calc's ? Rizk Residence. Port;Sain it ucie, FL 34983,- Pa a .17 Deta i ed Room Loads - Room 10 - Bedroom 2 (Peak Fenestration Gain Procedure) General Room is iin zone 2, which peaks at 5 pm Calculation Mode: Htg. & clg. Occurrences: 1 Room L "ngth: 14.0 ft. System Number. 1 Room idth: 13.0 ft. Zone Number: 2 Area: I 182.0 sq.ft. Supply Air: 151 CFM Ceiling eight: 8.0 ft. Supply Air Changes: 6.2 AC/hr Volume: 1,456.0 cu.ft. Req. Vent. Clg: 0 CFM Number f Registers: 2 Actual Winter Vent.: 2 CFM Runout 'ir. 75 CFM Percent of Supply.: 1 % Runout 'Iuct Size: 5 in. Actual Summer Vent.: 2 CFM Runout it Velocity: 553 ft./min. Percent of Supply: 1 % Runout �r Velocity: 553 ft./min. Actual Winter Infil.: 10 CFM Actual Loss: 0.252 in.wg./100 ft. Actual Summer Infil.: 4 CFM Item f Area U$en Glg Lat .- 5eri Descnpti n'; _.^ ` ` , .. Quaniity Vatue.. ;` , HTM.,, Loss . HTM , =Gain::: Gain: S -Wall-1 'A-5ocs 13 X 8 84 0.125 3.5 294 1:9 0 161 W -Wall-1 A-5ocs 14 X 8 106 0.125 3.5 371 1.9 0 203 S -GIs-1A . b-o shgc-0.75 0%S (2) 20 1.080 30.2 604 46.7 0 934 W -GIs-1A;!Icb-o shgc-0.75 5%S 6 1.080 30.2 181 131.5 0 789 UP-Ceil-1 6-19 14 X 13 182 0.049 1.4 250 2.0 0 357 Floor-2013- 013 X 14 182 0.035 1.0 178 0.4 0 64 Subtotals f r Structure: 1,878 0 2,508 Infil.: Win.:li9.6, Sum.: 4.4 216 1.370 296 0.338 184 73 Qucbuork: 579 504 People: 20 lat/per, 230 sen/per: 1 200 230 Equipment I - — --------- Room Tota �s: --------.�--- ------ -- _ 2,753 ------------300 684 - -- ---0 3,315 �I i i �I •� I` I� I d 'J i j i i I �II I C:\ ...\Rizk Relll idence.rh9 Saturday, January 24, 2015, 11:09 AM RhVac esident al ilk LIE COmmerdfaf HVAc Loatls Elite Software Development; lnc. Residen Calc's a Rizlc Residericei !LuEnergy Port:SaIn cie, FL, 34983 Pa a _18 ®etai bd Room Loads - Room I - Laundry (Peak Fenestration Gain Procedrare) I� General +which ! Room is in zone 2, peaks at 5 pm Calculati)n Mode: Htg. & clg. Occurrences: 1 Room L ngth: 9.0 ft. System Number: 1 Room dth: 6.0 ft. Zone Number: 2 Area: J 54.0 sq.ft. Supply Air: 7 CFM Ceiling eight: 8,0 ft. Supply Air Changes: 0.9 AC/hr Volume: 1 432.0 cu.ft. Req. Vent. Cig: 0 CFM Number f Registers: 1 Actual Winter Vent.: 0 CFM Runout ir: 7 CFM Percent of Supply.: 2 % Runout Duct Size: 4 in. Actual Summer Vent.: 0 CFM Runout A r Velocity: 77 ft./min. Percent of Supply: 1 % Runout A,r Velocity: 77 ft./min. Actual Winter Infil.: 0 CFM Actual Lo's: 0.008 in.wg./100 ft. Actual Summer Infil.: 0 CFM It Area _ U Htg Sen Clg Lat .. Sen. Desenpti _ n HTM Quanfi Value Gain. UP-Ceil-1 C-19 9 X 6 54 0.049 1.4 74 2.0 0 106 Floor-20P- 0 6 X 9 54 0.035 1.0 53 0.4 0 19 Subtotals f err Structure: 127 0 125 Infil.: Win.: 0.0, Sum.: 0.0 0 0 0 0 0 0 Ductwork: i 34 22 E ui ment:�l 600 0 Room Tota s: III I itI I ,II u I I I I II i i i I I I, i I i I i ,I I I 161 600 147 C:1... 1Rizk Res�'dence.rh9 Saturday, January 24, 2015, 11:09 AM IC1i RBvirC &" Light Commeecial HVAC Loatls , Elite Software Development, Inc: ,esidenttal Resident t Energy Calc's :. ence Rizk Reside Port:Sain ;Lucie, FL:34983 .-.! ,. _ " .: . ". Pa 19' Detai,ed Room Loads -Room 92 - Stairwa (Peak Fenestration Gain Procedure) General Room i*in zone 2,'which peaks at 5 pm Calculat on Mode: Htg. & clg. Occurrences: 1 Room L ''ngth: 10.0 ft. System. Number: 1 Room idth: 7.0 ft. Zone Number: 2 Area: I 70.0 sq.ft. Supply Air: 311 CFM Ceiling ,eight: 8.0 ft: Supply Air Changes: 33.3 AC/hr Volume: !I 560.0 cu.ft. Req. Vent. Clg: 0 CFM Number f Registers: 3 Actual Winter Vent.: 2 CFM Runout tr: 104 CFM Percent of Supply.: 1 % Runout luct Size: 16 in. Actual Summer Vent.: 4 CFM Runout Air Velocity: 528 ft./min. Percent of Supply: 1 % Runout 'ir Velocity: 528 ft./min. Actual Winter Infil.: 2 CFM Actual L 'SS: 0.178 in.wg./l00 ft. Actual Summer Infil.: 1 CFM ttem:: ! Area U Htg v Sen Clg Lat : Sen Descnpti ,, .. Quanta Value ;:.. HTM Loss HT,M, . Gain Gain: .n W-Wall-13A-5ocs 7 X 8 15.5 0.125 3.5 54 1.9 0 30 W -GIs-1 �, cm-o shgc-0.75 1 %S 40.5 1.270 35.6 1,440 137.8 0 5,581 UP-Cetl-1 C-1910 X 7 70 0.049 1.4 96 2.0 0 137 Floor-20P'30 7 X 10 70 0.035 1.0 69 0.4 0 25 Subtotals or Structure: 1,659 0 5,773 Infil.: Win. �2.5, Sum.: 1.1 56 1.375 77 0.339 48 19 Ductwork: i 462 __— 1,039 Room Tot Is: i I I !I .I I II II ii i I I 2,198 48 6,831 C:\ ...\Rizk R'Fsidence.rh9 Saturday, January 24, 2015, 11:09 AM Rhvsc 'es!dLhtial-&,Light jCommercial HVAC'LbadsElite Software Developmen'!t Im Residents E66rgy.CaldsRizk Risenc Lucle",FL,14983,z� a e2 Deta": d Room Loads - Room 13 - Den (Peak Fenestration Gain Procedure) Room is' ' in zone 2, which Calculat on Mode: Room L li ngth: Room Width: Area: I Ceiling eight: Volume: me. Number f Registers: Runout 1r: Runout ' uct size: Runout 'r Velocity: Runout Ar Velocity: Actual Lo:'s: 3 at 5 pm Htg. & c1g. 17.0 ft. 10.0 ft. 170.0 sq.ft. 8.0 ft. 1,360.0 cu.ft. 3 106 CFM 6 in. 537 ft./min. 537 ft./min. 0.185 in.wg./l 00 ft. -------------- Item E -Wall-1 3 �,-5ocs 10 X 8 SW-Wall-13A-5ocs 17 X 8 E -GIs-lA-'' b-o shgc-0.75 O%S SW-GIs-l'Lcb-o shgc-0.75 4%S SW-GIs-10,,-m shgc-0.53 4%S (2) UP-Cell-19 17 X 10 Floor-29?- 'P 10 X Subtotals f§T Structure: InaWin_:P.6, Sum.: 4.4 Ductwork: People: �!atfpe�, 2qqsqnjp r, ..20 0 Room Total Occurrences: System Number: Zone Number: Supply Air: Supply Air Changes: Req. Vent. Clg: Actual Winter Vent.: Percent of Supply.: Actual Summer Vent.: Percent of Supply: Actual Winter Infil.: Actual Summer Infil.: re ul-W-� -'.. -... .. Q am - tty Value '7 TLoss. 65 0.125 3.5 228 97 0.125 3.5 340 15 1.080 30.2 454 15 1.080 30.2 454 24 1.670 46.8 1,122 170 0.049 1.4 233 170 0.035 1.0 167 2,998 216 1.370 296 877 2 2 317 CFM 14.0 AC/hr 0 CFM 3 CFM I % 4 CFM I % 10 CFM 4 CFM Clg- At en* = 'H roll ain.--Gain —1.9 0 124 1.9 0 186 56.5 0 848 108.5 0 1,628 91.2 0 2,188 2.0 0 333 0.4 0 60 0 0.338 184 400 4,171 584 5,367 73 T,058 460 M-11M, - L C:\ ... \Rizk Resli ence.rh19 Saturday, January 24, 2015, . 11:09 AM ' Rhvac Residential Light Commercial liVAC Loads f late _Software Develo men Inc. P t, Residents `I Energy Calc's ! Rink Residence` `tLucie; P,ortfSain FL 34983.. ry" R Pa e21" y '', ' Room Load Summaiy 'Htg - Mm Run Run Clg: Clg Mm= Act; R om` Area Sens ` Htg Duct . Duct Sens`: ' Lat Clg ;8ys_ No, N ` ew .SF Btuh . CFM ., _ Size' Vel Btuh' .: Btuh .. CFM' �CFM . ---Zone 1i--- 1 Kit hen 320 7,745 101 5-5 647 9,690 875 441 441 2 Di ing 95 847 11 1-4 191 367 348 17 17 3 Living 176 4,740 62 2-5 610 3,657 480 166 166 rway 77 4 St�,Ier 5 Fo 817 11 1-4 170 327 48 15 15 57 Zo 1 866 11 1-4 238 456 339 21 21 e subtotal 724 ---Zone 2 it 15,014 195 14,497 2,090 660 660 6 Bat 2 77 1,510 20 1-4 662 1,270 443 58 58 7 Ma -ter Bath 126 1,613 21 1-4 550 1,055 443 48 48 8 Master Bedroom 272 9 Wal I, In Closet 4,865 63 3-5 560 5,033 755 229 229 42 10 Bed oom 2 182 471 6 2,753 36 1-4 137 263 48 12 12 2-5 553 3,315 684 151 151 11 Lau 'dry 54 12 Stai 161 2 1-4 77 147 600 7 7 ay 70 13 Den 2,198 29 3-6 528 6,831 48 311 311 - - ------ - - -170 Zon 12 subtotal 993 4,171 _ - 54 - -- 17,743 3-6 537 6,958 584 317 317 - 231 24,873 3,605 1,132 1,132 Vent! ation 769 412 1,038 Duct 1,437 System 'atent 1 total - _ -- 1,717 _ 33,526 _426 _ _ 33,783 8,170 1,518 1,518 System 1 ain Trunk Size: 14x18 in. ---- -- _ -- _ Velocity: I,� 868 ft./min Loss per 10 ft.: 0.094 in.wg Note: Sinc Ithe system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room nd zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which totals the glass se sible gain for the zone is at its peak. Sensible gains at the system level are based on the "Average Load Procedure +Excursion" method. Coolie S` m Surnma 1 Cogbng Sensible/Latent Sensible Latent - Total: Btuh :13tuh Btufi` Net Require . 3.50 ctul: 81%/ 19% 33,783 8,170 41,953 ! 3.64 �Equiam 80% / 20% 34,000 8,500 42,500 'eetaD to I Heating System Cooling System Type: Electric Resistance Standard Air Conditioner Model: Indoor Model RXBH24A10J OR EQUIVALENT RAPL042JEZ OR EQUIVALENT RHLLHM4021JA OR EQUIVALENT . Brand: PRESTIGE SERIES PRESTIGE SERIES Description: SPLIT SYSTEM SPLIT SYSTEM 16 SEER -Efficiency: 0% 16 SEER Sound' p 0 Capacity: 42,500 Btuh 42,500 Btuh Sensible Capa ity: n/a 34,000 Btuh Latent Capacity: n/a 8,500 Btuh AHRI Reference No.: i I i i I n/a 1283265 UA .. XKizK Resid11nce.rh9 Saturday, January 24, 2015, 11:09 AM III