HomeMy WebLinkAbout54635- BUILDING PLAN CHECK1 L'1 BUILDING PLAN CHECK ST. LUCIE COUNTY -FORT PIERCE FIRE PREVENTION BUREAU FORT PIERCE, FLORIDA TELEPHONE 465-6655 I,IICTION: JURIS St. Lucie County PLAN NUMBER #6108 PROJE,I T NAME: CHARLIE'S DODGE BUILDING DEPT. NO. 91-0314 CONTRI CTOR: Don Willems PHONE NUMBER 461-5532 ARCH I'ECT: Jack Jewell PHONE NUMBER OWNE Charles L. Floya DATE RECEIVED 2-19-91 LOCATIIPN: 4815 South U. S. #1 2-19-91 BUILDI G SIZE: Existing under roof NUMBER OF STORIES 1 OCCUP., NCY TYPE:, Mercantile BUILDING HEIGHT ACONST UCTION TYPE: SBCCI. IV un. 'a NFPA. III (000) FIRE PR I TECTION: Automatic Sprinkler Yes No „ I Occupancy Hazard N.F.P.A. #13 Requirements: Enclose Breezeway. 1. Proville approved illuminated exit lights above each exit doorway. 2. Recir,culating air systems with a fan capacity between 2000 CFM and 15,000 CFM shall auto- maticlly shut down when heat within the system (136°) becomes excessive. (Firestats shall be in'jthe returV air stream prior to any exhausting from the building or mixing with fresh air m keup.) An approved smoke detector may be used in lieu of the firestat or upon appro,,,al of the mechanical official. Southern Standard Mechanical Code 515.1 3. MasroAy walls furred with wood frame must be firestopped at the floor and ceiling with combusl'It_ible material. NOTE; Ps OVIDE A 40 BC. Rated Fare F.xfitngULGt F_R oar A 3A- 208C- For'ihts AY-ca. CONTRACTORS RESPONSIBILITY TO NOTIFY BUREAU ON ALL INSPECTIONS 24 OUR NOT)CE REQUIRED ON ALL INSPECTIONS REVIEWS II BY:DATE-�-4�— SI ATURE