Loading...
HomeMy WebLinkAboutICC-ES-REPORTOWNED - BY DIVISION: 06 00 00-WOOD, PLASTICS AND COMPOSITES SECTION: 0616 00-SHEATHING DIVISION: 07 00 00-THERMAL AND MOISTURE PROTECTION SECTION: 07 25 00-WATER-RESISTIVE BARRIERS/WEATHER BARRIERS SECTION': 07 27 00-AIR BARRIERS REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 EVALUATION SUBJECT: ZIP SYSTEM® WALL SHEATHING IN IC I�� c PRIG � LISTED Look for the trusted marks of Conformityl "2014 Recipient of Prestigious Western States Seismic Policy Councils (WSSPQ Award in Excellence" A Subsidiary of °� � ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implie4 as to any finding or other matter in this report, or as to any product covered by the report. ,„u„ Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. ,v IMES Evaluation Report ESR-1474 Reissued October 2016 This report is subject to renewal October 2018. vj w Jcc-es.ora 1 (800) 423-6587 1 (562) 699-0643 A Subsidiary of the International Code Council® DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES Section: 06 18 00—Sheathing DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 25 00—Water-resistive Barriera/Weather Barriers Section: 07 27 00—Air Barriers REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 (800) 933-9220 www.huberwood.com EVALUATION SUBJECT: ZIP SYSTEM WALL SHEATHING 1.0 EVALUATION SCOPE Compliance with the following codes: s 2015, 2012 and 2009 International Building Cade® (16C) e 2015, 2012 and 2009 International Residential Code° (IRC) 0 2015, 2012 and 2009 International Energy Conservation Code® (IECC) Properties evaluated: D Weather resistance e Air leakage 2.0 USES ZIP System® Wall Sheathing panels are used as combination wall sheathing, air barrier, and water -resistive barrier. This report recognizes the use of ZIP System® Sheathing, when installed with ZIP System'm flexible flashing seam tape, in walls of Type V construction (IBC) and dwellings under the IRC, and as an alternate to the water -resistive barrier required in Chapter 14 of the IBC and Chapter 7 of the IRC, and to,the air barrier required by Sections R402.4 and C402.5.1 of the 2015 IECC (Sections R402.4 and C402.4.1 of the 2012 IECC; Sections 402.4.1 and 502.4.3 of the 20091ECC). 3.0 DESCRIPTION 3.1 Sheathing Panel: The ZIP System® Wall Sheathing panel is an OSB wood structural panel having a laminated exterior facer. The Exposure 1 OSS complies with US DOC PS 2 for wood structural panels. The exterior facer is a medium -density, phenolic -impregnated, polymer -modified sheet material qualifying as a Grade D water -resistive barrier (required by Section 2510.6 of the 2012 and 2009 IBC). The panels are nominally 4 feet wide by 8, 9, 10, 11 or 12 feet long and have a square -finished -edge or machined -edge profile. When tested in accordance with ASTM E96 (water method), the polymer -modified sheet overlay has a minimum vapor permeance of 12 perms (68.6 X 10"' kg/(Pa-s-m2)1. Equivalent Water Vapor Transmission rate (WVT) of the polymer -modified sheet overlay is 83.4 g/(24h-rr12) when tested at 73.4°F (23°C). The water -resistive barrier and air barrier properties of the ZIP Systemm Wall Sheathing Panels are not affected when the panels are manufactured to comply as facing materials for SIPS in accordance with Section R610.3.2 and Table R610.3.2 of the 2015 IRC (Section R613.3.2 and Table R613.3.2 of the 2012 and 2009 IRC). 3.2 Seam Tape: The ZIP System"" seam tape is a self -adhering membrane tape consisting of acrylic adhesive laminated to a polyolefin backing. The tape is 0 012 inch (0.30 mm) thick with a minimum width of 3 /4 inches (95.2 mm), and comes in rolls of various lengths. 4.0 INSTALLATION 4.1 General: Installation of ZIP System® Wall Sheathing panels must comply with the applicable code, this report and the manufacturer's published installation instructions. The manufacturer's published installation instructions must be available at the jobsite during installation. 4.2 Application: 4.2.1 General: The ZIP System* Wall Sheathing panels must be attached to wall framing in accordance with the applicable code for wood structural panels, and in compliance with their panel span rating. The panels must be installed with the polymer -modified sheet overlay facing the exterior. In accordance with the manufacturer's published installation instructions, it is recommended that the square edges of the panels be installed with a gap ICC-ES Ewlnanan RrPortr arc nor ro be construed or represendng oesiheires or any other adnbuies not spec f tally addrmsed nor ore they to be construed as an endorsement of the subject o/the rgwt or a reeammendonon for its use There moo %orruney by ICC rvaluauon sentce, (I.C, erpmu or tlrtplied, as to any/lnding or orher matter in ihisrepan, or as to any produce covered by the report Copyright Z 2016 [CC Evaluation Service. LLC PJ1 rights reserved Page 1 of 6 ESR-1474 ) Most Widely Accepted and Trusted Page 2 of 6 between adjacent panels and between panels and dissimilar materials. All ZIP System Wall Sheathing panel seams must be sufficiently sealed with ZIP System seam tape. All overlay surfaces must be dry and free of sawdust and dirt prior to application of the ZIP System seam tape. The ZIP SystemTm seam tape must extend a minimum of 1 inch (25.4 mm) past the panel edge Tjoint intersections and must be centered within 1/2 inch (12.7 mm) over the middle of panel seams. The tape must be pressed firmly to adhere to the surfaces and seal the seams. Wrinkles in the ZIP SystemTra seam tape are acceptable unless they create a leak path to the panel seam. 4.2.2 Flashing: Flashing complying with the applicable code must be installed at the perimeter of door and window assemblies, penetrations and terminations of exterior wall assemblies, exterior wall intersections with roofs, chimneys, porches, decks, balconies, and similar projections, and at built-in gutters and similar locations where moisture could enter the wall. An adhesive -backed flashing tape recognized in a current ICC-ES evaluation report must be installed to seal all ZIP System® Wall Sheathing flashing joints. Penetration items must be sealed to the panels. The adhesive -backed flashing tape must comply with the ]CC -ES Acceptance Criteria for Flexible Flashing Materials (AC148) and must be installed in accordance with the manufacturer's published installation instructions. See Figures 1 through 7 of this report for typical flashing, water -resistive barrier and air barrier assembly installation details. 4.2.3 Air Barrier Assembly: ZIP System® Wall Sheathing fastened to maximum 24-inch-on-center (610 mm), wood wall Framing, using minimum 6d nails spaced at 6 inches (152 mm) around panel edges and at 12 inches (305 mm) in the field, leaving a '/a -inch (3.18 mm) gap between panels, forms an air barrier assembly when the gaps between panels and the perimeter of penetrations are sealed with ZIP SystemTm seam tape as required by Section 4.2.1. The assembly has demonstrated a maximum air leakage of 0,0072 cfm/e [0.037 U(s•m2)] infiltration and 0.0023 cfm/ft2 (0.012 U(s•m)) exfiitration at a pressure differential of 1.57 pst (75 Pa) when tested in accordance with ASTM E2357. 5.0 CONDITIONS OF USE The ZIP System® Wall Sheathing panel and tape system described in this report complies with, or is a suitable alternative to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 This evaluation report and the manufacturer's published installation instructions, when required by the code official, must be submitted at the time of permit application. 5.2 The ZIP System® Wall Sheathing panels must be manufactured, identified and installed in accordance with this report and the manufacturer's published installation instructions. In the event of a conflict between the instructions and this report, this report must govern. 5.3 The ZIP System® Wail Sheathing panels must be covered with a code -complying exterior wall covering, or one that is recognized in a current ICC-ES evaluation report. 6.4 The OSB sheathing must comply with US DOC PS-2. 5.5 Fire -resistance -rated construction is outside the scope of this report. 6.0 EVIDENCE SUBMITTED 6.1 Data in accordance with the ICC-ES Acceptance Criteria for Water -resistive Membranes Factory - bonded to Wcod-based Structural Sheathing, Used as Water -resistive Barriers (AC310), dated May 2008 (editorially revised August 2015). 6.2 Air leakage data in accordance with ASTM E2357 7.0 IDENTIFICATION Each ZIP System® Wall Sheathing panel described in this report must bear a label that includes the manufacturer's name (Huber Engineered Woods LLC), the product name, nominal panel thickness, the evaluation report number (ESR-1474), and the words "Mill 229, Crystal Hill, Virginia'; 'Mill 228, Easton, Maine', "Mill 227. Commerce, Georgia'; or 'Mill 290, Broken Bow, Oklahoma.' The OSB sheathing must also bear a label demonstrating compliance with US DOC PS 2 from an approved Inspection agency. The ZIP System TM seam tape roll must be labeled with the ZIP System logo and the evaluation report number ESR-1474 (see Figure 8) q1 tME 9omE Law-PREM VMVA?M"E kOLVT3 :7l1 muglG Pr FLCfA^LOICFD F % 1Ai ! INI,FA.CWfEF MMOA i ADHED FL' = FQtCH I ! �wiiT SILL SECTION HEADER SECTION FIGURE 1-TYPICAL CROSS SECTIONS OF FLANGED WINDOW I • ESR-1474 I Most Widely Accepted and Trusted Page 4 of 6 SILL SECTION HEADER SECTION MNOOW JAMa zp SY.'DJ` ACHME-agno WAU SHEATHING FLA-MG WE ou MOE aUJIVIG RWGH CMING IN90E LOSY-Pfi£5�lRE ' POL'A,KWHE FOAM JAMB SECTION FIGURE 2—TYPICAL CROSS SECTIONS OF INSTALLED BRICK MOLD WINDOW ESR-1474 { Most Widely Accepted and Trusted Page 6 04 6 TM ZIPL ZIPSYSTEMTLWAU STEMT"' SHEATHING SHEATHING . FRAMING RAMING BACIGD PLASHIPIG TAPE L SItiE-BACKED FLASHNG TAPE FASTENER L FLASHING FLASHING FLASHING FASTENER HING ADHESINSIRACKEO FLASHNG TAPE HING FASTENER ASADHESNBACi4 0 FLASHING TAPE G�` Ln / ROOF St -FAT NROOF (—�ROOF ROOF DEERL� NT BELT) `/-ROOFJOIST FIGURE 3—ROOF-WALL INTERSECTION (OPTION 1) '% '— ROOF JOIST FIGURE 4—ROOF-WALL INTERSECTION (OPTION 2) �k1 fl-4n u"-Ili=u� II II- !Lf (�li 11 jlclf tf )I IIf 11= IIi� ��L4 14-7r R= Ir=Ir- Ihill e��I�iiLUI . f r�d1I111B1 - FIGURE 6—TYPICAL WALL -SILL INTERSECTION AND FLASHING DETAILS FOR LAPPED SIDING ESR-1474 I Most Widely Accepted and Trusted Page 6 of 6 Adhesive -Backed Flashing. Tape FIGURE 7—INSTALLATION AT PENETRATION OPENING (NON -FIRE -RESISTANCE RATED) FIGURE 8—LABELING FOR THE ZIP SYSTEM SEAM TAPE ROLL IMES Evaluation Report ESR-1474 FEC Supplement Reissued October 2016 This report is subject to renewal October 2018. www.icc-es.ora 1 (800) 423-6587 ( (562) 699-0643 A Subsidiary of the /ntemational Code Council DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES Section: 06 16 00—Sheathing DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 25 00—Water-Reslstive BarrierslWeather Barriers Section: 07 27 00—Alr Barriers REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 (800) 933.9220 www.huberwood.com EVALUATION SUBJECT: ZIP SYSTEM® WALL SHEATHING 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaivation report supplement is to indicate that ZIP System® Wall Sheathing panels, recognized in ICC-ES master evaluation report ESR-1474, have also been evaluated for compliance with the codes noted below. Applicable code editions: to 2014 Florida Building Code —Building M 2014 Florida Building Code —Residential 2.0 CONCLUSIONS The ZIP System® Wall Sheathing panels, described in Sections 2.0 through 7.0 of the master evaluation report ESR-1474, comply with the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential, provided the design and installation are in accordance with the International Building Code® provisions noted in the master report. Use of the ZIP Systema Wall Sheathing panels for compliance with the High -Velocity Hurricane Zone provisions of the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential has not been evaluated, and is outside the scope of this evaluation report. For products falling under Florida Rule 9N-3, verification that the report holder's quality -assurance program Is audited by a qualify -assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official, when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, reissued October 2016. !CC -ES Evaluation Reports are not to be consnued as "presenting aesthetics or any other mtnbutes nor specy7cally addressed, nor are they to be construed as an endorsement of the subject of the "port ar a recommendalton for ru us„ Thercit no „armnty by ICC F,valumion Service, LLC, espress or imphed as so any finding ar aher mover m thts report, or as to any product covered by the report. ana.x _ Copyright C 2016 ICC Evaluation Service, LLC All rights reserved pagU7 or 1 1UU-h5 hnVironmente3 Report VAR-1012 Reissued September 2015 This report is subject to renewal September 2017. www,icc-es.orgiep ( (800) 423-6687 1 (662) 699-0643 A Subsidiary of the International Code Council® DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES Section: 06 12 00—Structural Panels Section: 06 16 00--Sheathing DIVISION: 07 00 00—THERMAL AND [MOISTURE PROTECTION Section: 07 21 00—Thermal Insulation Section: 07 25 00--Water-Resistive Barriers/Weather Barriers Section: 07 27 00—Air Barriers REPORT HOLDER: HUBER ENGINEERED WOODS, LLC 10925 DAViD TAYLOR DRIVE CHARLOTTE, NORTH CAROLINA 28262 (800) 933-9220 www,huberwood.com EVALUATION SUBJECT: ADVANTECH® (AT -SERIES) SHEATHING SPAN; ADVANTECH° (AT -SERIES) FLOOR SPAN; ZIP SYSTEMO ROOF SHEATHING; ZIP SYSTEM° WALL SHEATHING; ZIP SYSTEM" R-SHEATHING (INSULATING SHEATHING) 1.0 EVALUATION SCOPE Compliance with the following evaluation criteria: - ICC-ES Environmental Criteria for Determination of Sio- based Material Content (EC102), dated March 2012. • ICC-ES Evaluation Guideline for Determination of Source of Recovery, Extraction, Harvest and Manufacture for Materials or Products (EC114), dated March 2012 - ICC-ES Environmental Criteria for Determination of Formaldehyde Emissions of Composite Wood and Engineered Wood Products (EC108), dated March 2012. ICC-ES Environmental Criteria for Determination of Certified Wood and Certified Wood Content in Products (EC109), dated March 2012. Compliance eligibility with the applicable sections of the following green building rating systems, standards and codes: • 2012 International Green Construction Code (IgCC) (see'table 2 for details) • 2013 California Green Building Standards Code (CALGreen), Title 24, Part 11 (see Table 3 for details) • National Green Building Standard (]CC 700-2008) (see Table 4 for details) • National Green Building Standard (ICC 700-2012) (see Table 5 for details) • LEED for Homes 2008 (see Table 6 for details) • LEED v4 for Homes Design and Construction (see Table 7 for details) • LEED 2009 for New Construction and Major Renovations (see Table 8 for details) LEED 2009 for Schools New Construction and Major Renovations (see Table 9 for details) • LEED v4 for Building Design and Construction (BD+C) (See Table 10 for details) • ANSI/GBI 01-2010 — Green Building Assessment Protocol for Commercial Buildings (see Table 11 for details) 2.0 USES AdvanTeche (AT -Series) Sheathing Span, AdvanTech® (AT -Series) Floor Span, ZIP System Roof Sheathing and ZIP System® Wall Sheathing are used for a variety of inter'or and exterior framing and sheathing applications. ZIP System® R-Sheathing panels are used as combination wall sheathing and continuous insulation in conventional wood -framed wall construction. 3.0 DESCRIPTION AdvanTech® (AT -Series) Sheathing Span and AdvanTech (AT -Series) Floor Span wood structural panels are Exposure 1 oriented strand board (OSB) panels manufactured with strands from a single wood species or a combination of wood species blended with an exterior -type adhesive system to comply with U.S. DOG PS-2 and the applicable ICC-ES report as indicated in Table 1. ZIP System Roof Sheathing and ZIP System° Wail Sheathing wood structural panels are OSB panels with laminated, resin -impregnated, polymer -modified sheet material manufactured to comply with U.S. DOC PS-2 and the applicable ICC-ES reports as indicated in Table 1. The panels are installed with ZIP System® self -adhering membrane tape. The tape is outside the scope of this evaluation report. ZIP System® R-Sheathing is an insulated sheathing made by combining 7/la-inch-thick ZIP System° Wall ICC-ES Vmflrc lion ufAnnbu1a Reporlt = !maid umler the JCC.£S VAR 9­ironmentef Program There rrpunt atr nut to be canttrned ar reprmrnnrtg aetthelta or any other ahnbuter not rpeetftcaily addreped, nor an they to be crot rd ar an endurrement of the ntbJeet of the mpun or a mcommendotian for its eve There is as wVrr-ly by /CC FwhwW Servtee. LLC, vprssr or implied tss to any�nrhng or olhrr manrr to th1,r, «parr, -r to anypra(hr. r e ,t and by the report cyy Copyright $ 2016 ICC Evaluation Service, LLC. X tights reserved. Page t of 6 VAR-1012 I Most Widely Accepted and Trusted Page 2 of 6 Sheathing as described in ESR-1474 with a layer of 6.2 maximum 14nch-thick (25,4 mm) rigid foam plastic insulation laminated to the interior face with PVA adhesive. Refer to ESR-3373 for additional product description. 4.0 CONDITIONS 4.1 Code Compliance: AdvanTechs (AT -Series) Sheathin� Span, AdvanTechs (AT -Series) Floor Span, ZIP System Roof Sheathing, ZIP Systems Wall Sheathing and ZIP System R-Sheathing have been evaluated for compliance with the requirements of the International Codes as listed in Table 1 of this report. 4.2 Green Rating Systems, Standards and Code Eligibility: The information presented in Tables 2 through 11 of this report provides a matrix of areas of evaluation and corresponding limitations and/or additional project -specific requirements, and offer benefit to individuals who are assessing eligibility for credits or points. The final interpretation of the specific requirements of the respective green building rating system, standard and/or code rests with the developer of that specific rating system or standard or the Authority Having Jurisdiction, as applicable. Compliance with items noted as 'Verified Attribute' is subject to any conditions noted in the tables. Decisions on compliance with those items noted as 'Eligible for Points' in Tables 2 through 11 rests with the user of this report, and those items are subject to the conditions noted. The user is advised of the project -specific provisions that may be contingent upon meeting specific conditions, and the verification of those conditions is outside the scope of this report. Rating systems or standards often provide supplemental information as guidance. 5.0 BASIS OF EVALUATION The information in this report, including the "Verified Attribute,' is based upon the following supporting documentation: 5.1 ICC-ES EC102 [Evaluation applies to IgCC Section 505.2.4; CALGreen Sections A4.405 4 & A5.405.2; ICC 700-2008 Section 606.1(2); ICC 700-2012 Sections 606.1, 11.6061 8 12.1(A).606.1, ANSI/GBI 01-2010 Section 10.1.2.2] ICC-ES EC114. (Evaluation applies to IgCC Section 505.2.5; CALGreen Section A5.405.1; ICC 700-2008 Section 608.1; ICC 700-2012 Sections 609.1, 11.509.1 & 12.1(A).609.1; LEED Homes MR 2.2(c); LEED v4 Homes MRc3; LEED NC MR 5; LEED Schools MR 5; LEED v4 BD+C MR03; ANSI/GBI 01- 2010 Section 10.1.4.1]. 6.3 ICC-ES EC108 [Evaluation applies to IgCC Section 806.1; ICC 700-2008 Section 901.4(6); ICC 700-2012 Sections 901.4(6) & 11.901.4(6); LEED NC EQ 4.4; LEED Schools EQ 4.4; LEED v4 BD+C EQc2]. 5.4 ICC-ES EC109 [Evaluation applies to ICC 700-2008 Section 606.2; ICC 700-2012 Sections 606.2(2), 11.606.2(2) 8 12.1(A).606.2; ANSI/GBI 01-2010 Section 10.3.2.1]. 5.5 Documentation establishing and documenting all major .sources of primary manufacturing energy (Evaluation applies to ICC 700-2008 Section 606.3; ICC 700-2012 Sections 806 3 & 11.606.3]. 5.6 ICC-ES ESR-1474 documenting that ZIP System Wall Sheathing is equivalent to a code -prescribed water - resistive barrier (Evaluation applies to CALGreen Section 5.407.1; ICC 700-2008 Section 602.9; ICC 700-2012 Section 602.1.8]. 5.7 Refer to ICC-ES ESR-1474 for evaluation of the ZIP System Wail Sheathing as an air barrier assembly [Evaluation applies to IgCC Section 605.1.2.1.1, ICC 700-2008 Section 703.2.1; ICC 700-2012 Sections 701.4.3.2, 11.701.4.3.2 8 12.1.7014,31; LEED Homes EA 3; LEED v4 Homes EAc7]. 6.0 IDENTIFICATION AdvanTech (AT -Series) Sheathin% Span, AdvanTech`' (AT -Series) Floor Span, ZIP System Roof Sheathing, ZIP Systems Wall Sheathing and ZIP System® R-Sheathing products are identified with a stamp noting the manufacturer's name (Huber Engineered Woods, LLC) and address, the product name the manufacturing location, the ICC-ES evaluation report number (if applicable), and the name or logo of the inspection or grading agency. The report subjects are also identified on the product and/or packaging with the VAR Environmental Report number (VAR-1012) and the ICC-ES SAVE Mark, as applicable. TABLE 1—REFERENCE STANDARD OR EVALUATION REPORT NUMBER FOR HUBER ENGINEERED WOODS LLC PRODUCTS PRODUCT REPORT NUMBER/ REFERENCE STANDARD AdvanTech* (AT -Series) Sheathing Span AdvanTech* (AT -Series) Floor Span ESR-17a5 ZIP System* Roof Sheathing ESR-1473 8 ESR-2227 ZIP System® Wall Sheathing ESR-1474 $ ESR-2227 ZIP System® R-Sheathing IsSR 3373 VAR-1612 4 MaW Mdely Accepted and Misled Pago 3 of 6 Teo! ee eTuontrn_r-t . SCetlpn 'fSsUvn Man! Muraar PwtlEk Pdnm ___-•- •••, •••••v„ , Gaba7a=mdiW bOuvNT AdYcnTxn AdvanTrsR 'Ir �''fT'atm -Rod L'P SYitam 2-7 _ GJv.'-'p Wa0 TABLE 2—SUMMARY OF AREAS OF ELEGIBILITY WITH 2012 INTERNATIONAL GREEN CONSTRUC1iON CODE SOS]1 8a-cuntP� WA AIMu�et wove PmCu¢f ma quunM at bi.wsm • s pf Ptvtw:m YYR be rewyntd. � neia0, GRSCM f aYrutagtaed'a-a6n i NA Z',�o r� ;;msCg'tattui`r 26unitsJOrtu`i/aCw &^n O p i.4C PmM w- Mar R8 q 025. 5 sddsyty-- .rranwma ratInfnsan U¢:r!er Wtsptwt 'aA��. ryrm St accM— Ift GbtR5f21t .'�.( • • aa] F—Wly.....We VA H. .aooC sbyga8l P]nGkm i/Nlus DUG P52(r-I.N. tatvb repx Jne an aHmpf Ram M—er fA--'d ts7m a s • e pf TABLE 7-SUMMARY OF AREAS OF ELEGIBILRY WITH 2013 CALJFORNIA GREEN BUILDING STANDARDS CODE ASa05 t iJagbri r lMaa v` 1Y tt�cal pmd=1 Out arc a 9W, PORsatd and mYn ued t'a�mf4a of 50o Ran 1 G052m'dPcdslaa D O O O 3, ,.:.'•�.1� M JGii ASiLi2 PAminl nalC.iF! V1#.fiefwmaPxuv of El— 4A'm aCb-Cate • 0 a a pf M i05 i(31 Adf05 Kfl amemtla ec�'ren _. laa_bh Ranrarwab'e fcr:�Iuifa aryi'.ttfeS wncdi ._.._ O • a ® Of AS J0621 C.&.w Weed 1hCa r� by G6t 8'4Cq StenGnh C—m "—f WA —_ MA WA WA 17A Sa07t Wat>rskYrJ ta!80rr waa asset[/? Ibrbal Paa'atA PaYda t'+ateH 'vwa es4`riar wal enreCpG � . 1 O O i SOf S ' imta'+en1 YmiayY _ 5 SG PaC{f crrafbv EK7 Ik a 5 :aaaJPb So rG aPiy b mu mrPASa svN PfGV SeOntian' TABLE 4-SUMMARY OF AREAS OF ELEOIBILRY WITH THs NATIONAL GREEN y BUILDING STANDARD JICC 700.200E) 6022 W.^.o—"tw..N YiMatYJ h�J WWp esatitouW3taed uaa 3 - _ a d1n% bt malertx ivy trrory -�•' - -'s :- 6C0 1U] eltM PUMP prajxSaa Ci.rih]4+q 6 ezotf0GepfnMttsantI!t S<t«]p*ba PMOQ4] at i ni.Mc'emaJrJtanFatms vaaYc'+aaarnm Eamd'osx a o posV021 Two ¢ &d eood bnsw P dC xe tnal ter —� 6007(ti ar nxd.m of Na orYtrq s�:na sf-b ] Iv am 9 vaib a d rr.9.-e ume semnP.66d mw stm ba—daa,L �aat rael aamanf' 0 a O O Oa 7wa ca-f�boa7 �fW Paae aramylor ftb 8A .majv N d Pe ta:Jmri0 uitt a if waft' � Ta esmi osvom arh3td "aaef Ob+' Padud:nr3t aSv b t12f 5acf arroal f+=�+rt' a s a a O+ f. NY2ikh 7<0 triad fY (nijDr epctlpiCb of IRC ti+alig teal ua .naraeae-.ara ust0 a m'rnn ctE''.'eam 6C80 SalkaY0ma4rew; dme d—Wtmaryma�YlfaCatlpvwbMIt.61214N dilYfd icm R.'f.d tbYCeOertAnvadi171C9. 2iam5 met oa ta^N nealr t8id �P cadf nff� ®r'p� M. I$W, • • 0 a •J f foam. ptth atlf eaarl7! Ctdb 0 ap7H,+a, port' ,aT �aS1.Rv + fef P:Mslnf U. nq a>,yy W Uvs Croba Nda FoaV. c--a Im'M aSer fsbb to 1 VAR4012 I MOST NMdeN Accepted and T7Ddted Paps 4 of 8 Saetlpn NumDPr Soatlen L•dmd Poaa'Db Pdnb CatlRbna vt ibeb Oua:Ny AdyarTv71 AdvmT¢h LP 8 Rpol �WSan3 Slyme;,p Fbonfp Ora.-tictnd 6fmclhe+a R3hpa7dn n9 TABLE f—SUM#ARY DFAREAS OF ELEGIBILITY KITH THE NATIONAL GREEN BUILDING STANDARD JrCC 700.2000) (ConUrwod) £C81 IhDaerou rtahM1as 7Fg .neam per+.a.¢r. ar]ggro .9rov/ a 10aa eeoeru•, wPiA `-•,.7 m: 'Se5 ; ' � �. _ 7 LmS:bn card aY aeniYq b Da'a7ed h t¢ad]rxa u/Or at me RYdaeip a .._ _ _ _ -.7 J0721 tnWalnn amlrva<a4q 15 m ,�qpy' (fl^dro-art/vxXa� mfa^_oa 15 Q>. 0 O 121 ro Ofad wrf—.,e . amzd 30 SxnuTlpyawdsam ua azG+'rl r+cor ahaTh9 —PE..m COC PS 1 ardra DOC 98 2 OSD oaad A. P.m,.-4 aebb, nxl fK6T:ry 9C1 QI) rttj-1Mti DCC PS 2 Pe. aR m]da trth Mar O-Wv SO•.sxl:`b arrinanamda5%a008 a7yavm mOp:.fd a+p rt,rs, mrta4l ar 1 amrua,canhm aQabr] via tra namaa 1'i°r' pQC� m i i e g !TdCAG W lyr,e].Ytl a,e E]p— 1 a Ed i. 1P1�arra{ artl bpwme 1 tOSBI 201 K01 N'x"�+'Qn9 Quduaa, wNal e.a� 4b aYuqueal' " rwm rra*+ . A--d 25%It Qodu3 N 1ta bJUag arP Te 11eM:9sd I.A. Qeduaa TABLE 6-SUMMARY OF AREAS OF ELEGIBILITY MTN T14E NATIONAL GREEN BUILDING STANDARD (]CC 700.20i2j - w21a Wi'aaelsDru mme: µayr awatarcaymhxnw an<ia asnapa pan ayaen ova mmorvmrr !--- -�.t_T tlw r % Il Tvro.yya a auDxed r.�aleroa an fLet, nar ra ran l%ar tl'e QgeCrpajeaed tVkMyj 6. TP esm tl potla papsa � lb allaaal l c' W anaJspkn,naM.B aTa AM . _ ... _ _ _ i m 171 EWl JA86W) —tm marstblaas ardDa doGaed RaA><]#i%at ma'zha eea mvDn nad.la7Pirn ura • D e i Or 0w21f) asodw•eaddaW an um rof wclatlab Bata P.m 0.3%. II fiC8 7.11 1&, rtl,ri e!ar¢r2a dTe iNGg, tu<n xfal Tleti V. 7 TP-7 Po aseaaraf ana<d.ow av at]a ty a maammr Qa� m ]21Al=i am—k 'taaa� e i e e Oa iX9 ial 1f WS 2P Tve YrTd y MOOPisa1 Qodaa art IAA ra f mapr dlat5 a 7u?rld ay aKn a] at Wi], ( a to aam a 4a 3 ae<ortl C<M11Na'+aN as ny4t a5o x uaPO as a r. a' R 1 1Pr --- l7. 6tB1 taaaan<1 I Y.enunt' i O & i Or MT 4barPmeObrnyu eaTyM tj p(IAa �_ l 33 Dullrq an.narwhc'redNry a.ti+:+a:m N7]% IS 5057 al Pmnul rn3iM`6W%V Rrtaa—gy d'—d 7]ffit Torn OPODti MC�+ao—d De in<d (a al taast7rnaJa ctmfsr¢2t a.e Tan m+erotla a>talxe, For,DNJ'e vrsa emar ar7lty 2Po'.•.5 may be 9anvld'efgn ;aee'nier+n,jx m-pa+<n; • e g • p+ soucxa, a reteraye ]ne crtp fo eum2 Phn vMfy"W.1 b 0o 1 •d, q,oat ntuaty.aocsra na tty _ _ aatia 5rw mlojaCit Jana pD s<a aTaa�red Dy Tlad,u tSW noes 12af1 W91 Re�mxlmraAaS tax hnl t.Ta.�porlaq tan hml a0%el Qa tr �aa;araa Dy naaWaer P.•at:adn 9n 1 tons an asenElMa PerOxma dom.rst4" raa malabb;ua5ry lira+wknal O O O 0 a37o (Yl +•aeiMavaLmsl dlM ahtar'ms rrrnYa:sh esve Gear ! ._._.-�___ tranaiafq moel TC dbtarm etdedaa 7PIa72 TsTUSlvt and aY wn:g6!ma:edbadzrpanra Kn al U<foBPr,^S,b 1170 a72T1701171 i3 nw (17 9rn%tpnl'va:]-Jan Rda,n><a IS {y -' 1 OStuaua!mt.'»9 oxP0.b'.rn DOC PS 1 ana'aDecPS99fµ:1 T 205aV rOc!]Mxftilp1I901 µ11—a,iMh ODpa,vr3.P—h DOC PS2P madeA901 t{Ij na•raM,WpatS TRtlbtl3TeSCadevR I , M-W RPdub i A g tMt-'b U:e aaneahis Y] EaPTRea 10 E.alero, 1dr+oaal6 EaNnua 110981 OOt ya) lm.atlarq RDRsO.rNea+an' fAe F•M7VY 11 70l Y aaa a AmiiEmTof 654a pudael!n 9x Cidhy a:a T<bCaekV Nub pc tea i o +EY�exvFvaa H i A Oa �' Iris Qm']a]n dap,n 3PQa Io J'b QR1+1 Ma] Fearila are.k aw ]jar Tab4 It iz aRkl +aat i>i7A: are-q ,4 oKN zYtPPrj un o7 xCCs rw ta➢p a.3q.yc zuy � csr;. a ..n* PPR:rya PatztvA *; Y=-;-P t-ai'gcwca-n 4li 1. oP a..+PO4 I.C4.; Wa dN3 vM .slag-ezf�-I LD63 tzar"WcAa S,ar unlLub,M 1•` i` e r s i cot.0D9d acrwae wr u+mtr-➢fa voneueluww,00mD➢u� PP viR'a YN K bl-s [➢Nn tval:pe f1g ryAav w'PO C➢ iDr.Au:udal a,n Zv,:➢a.P tPepP{I L O 2 L i [ rage n PiIOGSt!..r£!1q' !LD Pa4WDa➢D(t1dlP•T➢aitwP➢a5•NAMO IIC➢]O t .�_. _..__._..,.. ta`DaC ri4 ptrgtaPJ.t•R[atgw nTJPLwuaS Call fo.48! N01,0nWXN03 QNv N01S30 oNiOline P• 0331 S.OeOSn H,IMunie10313 d0 SvaLV 10 AUVWWnS-01 3let'L ➢O O O b O zYnaf ��� ram PDWto] Wuaaaa 4aPD4 P➢av, krtsfam War. aV: Cell t wta ➢j t FCgICw Mz-afral 1603 t _ - e t c [ 1rr yDM IIW uD kqi xlu�:a'+'+: a Dtn 1%:qC wn a� z "tar WPW7 !NA O O O O tXPLw-awu--r w. RKs'Zua]Dy agu ggcF gbg Klmn zFlXOtI➢¢rwNY✓erol D:t aanPluq 5g4l z-w Z InazAa PX:OU 54sd Ir»5rtl 2441A - ' O O O O 7 i:+ax+m P XO:l I;&' -MOWN LSNA _ - Par.GRluAa P,rt Wtisra+d baPecn ale gultRmdamW,0:el a+ra O] NOUVAON3u u0i'VW QNV NO[fonuisN00 M3N S100HOS u0d BOOZ 0331 S.O9OSn mmAlilielo3'13 d0 sn", do AUMWn" 318VA LO O O & O mar "AwRw:al <a:rt Wii a+p;.xeilx tia"Wq D>e*➢1tW- P- am 4+De 1 wta Dj t te2,a7Lw Arapa -1 t r 03 1 ttlre-be,. 1?'!➢1 N'r W= .ILWa.- t [ z i .ppPr, A 1,..,m D➢ wLsal 1w'r.-rc-IrFa C ta: Y'ad l uua Dl i PXW W4v➢� ( NA kerr-zanad Z us]alLSNA z.Ti+➢>z'-gK�Plla'a A4: %4t :o wr-vpuaal art atlK lwt SWi i+'O4f .eq P➢TW:TJCw tt+k D-➢ a Wit .ba e:t Ma4Ye'gN Mn 55odl we oy G ' O D O D l .w JSIO XOtISakg-Imo'CaN Iv HA NOI,VADN3u uOfww QHV N0UonHLSN00 M3N }f0d DOOZ 0331 S:OeOSn Hi1M ALi1n319313 d0 SV3uV d0 Auvwwns-s Blew, 4o o O O O -...... wfx-,a 4w P]PwNu D4--WpaLa� P Ira F.61 wC➢oy 1 RC]a.w Du]tw'a AOi b[i3 bao-Slt-xns1q mile pal-=sN,d na A'La odo iw 4 SyyPav* r A^.' =. Ataga 4 rDtrtlg'az J C]NA - - O O O O ia(.We .q*4y-AC) "pw'ater.-t guar opP(aq L9ll Ai'a 00i Vtlpa titr➢SG 4Cz. yo➢+K t^+ af]W)td kYPrxuumAU3 pl. eMMIT-FIll. Fr4. N bF 'd-.D �riwiNeAr e ! i i 1 Wza06e'D605AgOSdM WFigo yD I�?oDNrsr Wr- Pa. tY orta➢IRnrd Pabswo-A mP mi NA C O _ __�_ .. 4S3WOH Wtp].zaiyrwcirr.]v G'u�a9rxs]iuwNzmw dZq�a �Z ureyryll,Y yap_ 6A 0331 S.02DSfl HRM kin isiorm d0 SV3uv d0 Ai vwWRS—L Blew, O MlDD WnWBaM bI%a zD w>_ Wa a A7; zit W p{'e SMI w4m GCS I&-Pl] WW-TM-M 1➢RLNP[ - - uflar.Wam4 ur 0.9 Damaaare'Pa�T;L ➢za taP Frpud aT: su,DdalWal axaPP 4r.+•B4,]i iw3 C z [ t x :InGnt P.T.:m-7'e Dm YaJz:tm W t+.'P450 wt: of Vu 5 U Ooazt .tadP➢ tnLi.a me t Z un O O J f. - 'zFiGiStc m P 14 -Aql A : opgaoil9 atPpw trrKd t+o Zf:rw oy R w rt`at wis.•r'u. IN LY3 eDDz s3wOH Hod Q331 6.0eosn Kum Ainisi0Bl3 d0 Sv3uv d0 AuwwWn S--S 91evt pi. fZ wRti6 dR p r" 6zM paP-kl /�}! p � pu( WS wuloe rW iPFCb as aaA is taCWPaDb RaPd �� uzu4 rDVurrtN wtyz6 dlZ c a+QU6dZ Vylua]Pv eP1ueMP tTFl�ad aoPaag 1Mv. nrN�v Jy F! y1:J11VL1H1 G li:i {tl 41 9 /o 9 013pcf Psi--L PusPOJ —V eP4M J6OiV I Zt01•MVA • • 0 VAR-1012 I Most Widely ACCepted and Tasted POAo 8 of 6 TA tri C:e n ruoni rn_u •a rn__.r_.._�. MIa /D] a2tbnfntonl pmalDb Panb Cmdldn aWeta QuW4 ru Mnb — A6.Tteh Ade0nTadr LP Byfam R-C LP Byalam WWI ZR$ya— $nmti:nq FimJq BnaMN $r..Mb B R-BIq IN - TABLE 11—SUMMARY OF AREAS OF PLEGIBILITY WITH ANSUGUI 01.2010 — GREEN BUILDING ASSESSMENT PROTOCOL FOR COMMERCIAL BUILDINGS 10122 ai:b—IPaax'f-b0.UM as]c:ride ?— ASRt v—d 0u0:uC are Prylb7 as tk[axd s a %7-7 o pe l0 1 a 1 P.e W:[ta!a- TO wm S6]y 1�C IYW:Rf ?il ]m wize''d• p—w 314 TinLfit y}�ytN �- t Ctlbiq as .O'a S,Ta/ Q .8e9 6]3 tr'f a W tla d i m'el'�un O! �CNI 'a U MN�r Oltlu S 1 O 0 p 3b-Y n }= Cclptm+opd drnaa Sdvx!n i0x vN sox armcr]al vcvOtiaMP aaMNOn ddbk'2 uo .rY,..rnaa 3Y.•, --,'�"'" 1032.1 o �x ]x poet =Ve...d elfb Ad 1.'.Y �.. cw'e] o 0 0 ® o o _ - . D. pmlibn d— rd apm W lb prak.l E02E$]: 'Cerc7a�a1 h rgrrW ama nivnhevn ]rq Yenxr Cl.ar q C+s`sy s rol «aaYa] aa�].y:a 10 port rfaexl tlAlHSO4axtb iGFn AYA r>s fBC aaquAc'yard!er 4TEDW n�urmi n9x/FSCa`.AGOWppwtl t�uM7da CadaQ USG3C.�.r ifai 0l i{yared M.rlvibr4 prt�rurrl 1GG85C remyr¢sf h:pWncu a a] a am3Cd (pr�1 podpCa /a.,mr a+o ipeA6: requtanerm ara a./crdy wda! ar:.elcpryri t] uv b xt fr mf]n<o van4'sl Ytwsbu d Ed i a'n TEED li;.::a iy �iauia ]ro C]uvNa /Ur riesri. m 8oad IC/RO) doo nci:�d9e errrneaed wood peeee un%iaM1! '�mT/ +ci'ea any a :x wppamaed s•.eav_r, pain a ae w-e 57gxrui nasr�1 aa:i/avem OxW on ypj_e b�th1 pmnam hi Fbttr �Rrl rcpv:Ht NA . N. ippg,'Wb DIVISION: 06 00 OD —WOOD, PLASTICS AND COMPOSITES SECTION: 0616 00—SHEATHING DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION SECTION: 07 30 OS —ROOFING FELT AND UNDERLAYMENT REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 EVALUATION SUBJECT: ZIP SYSTEMO AND ZIP SYSTEM+ym ROOF SHEATHING 1CC IGC IN PMG LISTED Look for the trusted marks of Conformityi vvvy' "2014 Recipient of Prestigious Western States Seismic Policy Council Iffia (WSSPQ Award in Excellence" A Subsidiary of � ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not °� specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ]CC Evaluation Service, LLC, express or implied, as to anyftnding or other matter in this report, or as to any product covered by the report.)I mmh��, _ Copyright © 2015 ICC Evaluation Service, LLC. All rights reserved ICC-ES Evaluation Report ESR-9473* Reissued September 2015 This report is subject to renewal September 2017. www.icc-es.ora 1 (800) 423-6587 1 (662) 699-0543 A Subsidiary of the International Code Council® DIVISION: 06 00 00—WOOD, PLASTICS, AND COMPOSITES Section: 06 16 00--Sheathing DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 30 06--Roofing Felt and Underlayment REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAViD TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 (800) 933-9220 www.huberwood.com EVALUATION SUBJECT: ZIP SYSTEM* AND ZIP SYSTEM+7' ROOF SHEATHING 1.0 EVALUATION SCOPE Compliance with the following codes: n 2015, 2012 and 2009 International Building Code° (IBC) El 2015. 2012 and 2009 lntemational Residential Code (IRC) ■ 2013 Abu Dhabi International Building Code (ADIBC)T 'TheADIBC is based on the 200918C. 2009 ;BC code sections referenced In this report are the same sections in the ADIBC Propertles evaluated: x Structural —wind uplift resistance m Nonclassified roof covering * Classified roof covering * Weather resistance 2.0 USES ZIP System and ZIP System+TM roof sheathing panels are used as combination roof sheathing and roof underlayment. 3.0 DESCRIPTION The ZIP System® and ZiP System+m roof Sheathing panels are wood structural panels having a laminated facer. The ZIP System+Tm panels are manufactured using a different resin than the Zip System® panels.. The panels are installed with a proprietary seam tape, which allows the systems to be used as an alternate to the underlayment required in Chapter 15 of the IBC and Chapter 9 of the IRC. The OSB substrate complies with U.S. DOC PS-2 for wood structural panels and is overlaid on one side with a medium -density, phenol -impregnated, polymer -modified sheet material. The standard -size panels are nominally 4 feet by 8 feet. Oversize panels, wider than 4 feet (1219 mm) or longer than 8 feet (2438 mm), or both, are also produced. The panels are available with either a square -finished -edge profile a tongue -and -groove edge profile or a machined edge profile. The proprietary seam tape is a self -adhering sheet -type membrane consisting of acrylic adhesive laminated to a polyolefin backing, and the face of the tape is labeled with ESR-1473. The tape is 0.012 inch thick (0.30 mm) with a minimum width of 3 inches (76.2 mm), and comes in rolls of varying length. 4.0 INSTALLATION 4.1 General: Installation of ZIP System® and ZIP System+TM roof sheathing must comply with the applicable code, this report and the manufacturer's published installation instructions. The installation instructions are to be available at the jobsite at all times during installation. The instructions within this report must govern if there are any conflicts between the manufacturer's published instructions and this report. 4.2 Application: The ZIP System® and ZIP System+TM roof sheathing panels must be installed with the longer dimension perpendicular to the roof framing and fastened to the roof framing in accordance with the applicable code for wood structural panels. The panels must be installed in accordance with the panel span rating as shown on the panels. All corners are to be securely fastened. Tongue - and -groove and machined edge panels are designed to provide the correct gap size at the panel edges during installation. Squared -edged panels must be spaced apart a minimum of '/a inch (3.18 mm) at the time of installation. End joints of adjacent panel runs must be staggered. The panel must be installed with the laminated phenol - impregnated polymer -modified sheet material facing to the exterior. All ZIP System® and ZIP System+TM roof sheathing seams must be sealed with the Zip System® tape. All overlay surfaces must be free of any significant presence of debris particles or sawdust prior to installation of the ZIP System tape. Overlay surfaces must be void of any free water prior to application of the ZIP System® tape. The ZIP System® tape edges must be sealed and the tape is to be centered within +/-'/2 inch �12.7 mm) of all panel edge seam centers. All ZIP System and ZIP System+T" 'Revised November 2015 ICC-ES Evaluation Reports ore not to be construed is reprueming a ithertcl ar arty other ailribwu not specifically oddresred, nor are they to be constrved as an endorsement of the subject of the report or a recommendation far its tore. Thera tr rw w rranry by ICC Evaluation Service, LLC express or implied, as to any finding or other matter in thu report, or ar to any product Covered by the report Copyright 0 2015 ICC Evaluation Senrica, LLC All rights reserved. Pagel of 2 ESR-1473 I Most WidelyAccepted and Trusted Page 2 of 2 roof sheathing surface defects, openings, cracks, etc., that completely penetrate the overlay and substrate, and caused by handling or construction work, must be covered with the ZIP System® tape. The ZIP System® tape must extend a minimum of 1 inch (25.4 mm) past the panel edge T-joint intersections. The ZIP System® tape must be adhered to the ZIP System® and ZIP System+TM roof sheathing. Wrinkles in the ZIP System seam tape are acceptable unless they create a leak path to the panel seam. 4.3 Roof Assemblies 4.3.1 Classified Roof Coverings 4.3.1.1 Class A: Underiayment is not required for a minimum 1/2-inch thick Zip System+Tm roof sheathing with Class A asphalt glass fiber mat shingles. 4.3.1.2 Class B: Underiayment is not required for a minimum 7/1e-inch thick Zip System® roof sheathing with Class A asphalt glass fiber mat shingles. 4.3.2 Nonclassified Roof Coverings: The ZIP System® and ZIP System+TM+ roof sheathing panels are limited to installation on buildings permitted to have nonclassified roof coverings using code -complying asphalt-riberglass shingles, metal shingles, metal panels, wood shakes, wood shingles, built-up roofing, slate and slate -type shingles, and clay and concrete tile roof coverings. Roof coverings may be applied directly to the taped ZIP System® and ZIP System+TM roof panels unless multi -layer underiaymenls are required. 4.4 Wind Uplift Resistance: Wind uplift design loads and ZIP System® and ZIP System+' roof wood structural panel allowable uplift resistance shall be determined in accordance with Sections 1609 and 2304.8.2 of the 2015 IBC or 2304.7.2 of the 2012 and 2009 IBC and Section R301.2.1 of the IRC. Roof coverings must be fastened to the sheathing with mechanical fasteners sufficient to resist the design uplift load. 5.0 CONDITIONS OF USE The ZIP System® and ZIP System+T14 roof sheathing panels described in this report comply with, or are suitable aitematives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 This evaluation report and the manufacturer's published installation instructions, when required by the code official, must be submitted at the time of permit application. 5.2 The ZIP System® and ZIP System+T11' roof sheathing panels must be manufactured, identified and installed in accordance with this report and the manufacturer's published installation instructions. 5.3 The ZIP System® and ZIP System+T" roof sheathing panels are limited to code -approved structural use for wood structural panels with either a 24/16, 32116 or 40/20 span rating. 6.4 In jurisdictions enforcing the IBC, the roof covering system incorporating the panels is limited to installations in the following construction types: Type 111-B and Type V-B • Type III -A or Type V-A under the conditions specified in footnoted of IBC Table 601 • Type III -A or Type V-A under the conditions specified in footnote b of IBC Table 601, for occupancies other than Group F-1, H, M and S-1 In jurisdictions enforcing the IRC, the roof covering system incorporating the panels may be installed on structures constructed in accordance with the IRC. 5.6 Enclosed attics and rafter spaces must be ventilated in accordance with the applicable code, except where unvented conditioned attic assemblies are permitted by 2015 and 2012 IRC Section R806.5 or 2009 IRC Section R806.4. 5.6 An ice barrier must be provided as required by Section 1507.2.8.2 of the IBC and Section R905.2.7 of the 2015 IRC and Section R905.2.7.1 of the 2012 and 2009 IRC. 6.7 installation is limited to roofs having a slope of 2:12 116.67% slope) or greater. 5.8 ZIP System° and ZIP System+- roof sheathing panels are manufactured by Huber Engineered Woods, LLC, in Crystal Hill, Virginia; Commerce, Georgia; Broken Bow, Oklahoma; and Easton, Maine, under a quality -control program with inspections by ICC-ES. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Wood Structural Panel Roof Sheathing Factory - laminated with an Alternative Roof Underiayment (AC266), dated May 2008 (editorially updated October 2016). 7.0 IDENTIFICATION Each ZIP System° and ZIP System+TM roof sheathing panel covered by this report must bear a label that includes the manufacturer's name (Huber Engineered Woods, LLC) and address; the product name; the evaluation report number (ESR-1473); and the grade, performance category and bond classification. The panel mill label and span rating, grade, performance category and bond classification label must be visible on the bottom face of panels, opposite the laminated facer. The ZIP Systeme tape roll is labeled with the product name and the evaluation report number (ESR-1473). IMES Evaluation Report ESR-1473 i°EC Supplement Reissued September 2015 This report is subject to renewal September 2017. www.icc-es.orA 1 (800) 423-6687 1 (562) 699-0543 A Subsidiary of the /ntemational Code Council® DIVISION: 06 00 00—WOOD, PLASTICS, AND COMPOSITES Section: 06 16 00—Sheathing DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 30 05—Roofing Felt and Underlayment REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE 10925 DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262 (800) 933-9220 www.huberwood.com EVALUATION SUBJECT: ZIP SYSTEM" AND ZIP SYSTEM+TM ROOF SHEATHING 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement Is to indicate that ZIP System® and Zip System+Tm roof sheathing, recognized in ICC-ES master evaluation report ESR-1473, has also been evaluated for compliance with the codes noted below. Applicable code editions: 41 2014 Florida Building Code —Building a 2014 Florida Building Code —Residential 2.0 CONCLUSIONS The ZIP Systeme and ZIP System+T," roof sheathing, described in Sections 2.0 through 7.0 of the master evaluation report ESR-1473, complies with the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential, provided the design and installation are in accordance with the international Building Code provisions noted in the master report, and with the condition that wind uplifting design loads must be determined in accordance with Section 1609 of the Florida Building Code —Building and Section R301.2.1 of the Florida Building Code —Residential. Use of the ZIP Systemm and ZIP System+TM roof sheathing for compliance with the High -Velocity Hurricane Zone provisions of the 2014 Florida Building Code —Building and the 2014 Florida Building Cade —Residential has not been evaluated and is outside the scope of the evaluation report. For products falling under Florida Rule 9N-3, verification that the report holder's quality -assurance program is audited by a quality -assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official, when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, reissued September 2015 and revised November 2015 ICC-ES Evaluation Reports arc not to be canrtrued as representing aesthetics or any other ounbutar nut spectfirally addressed nor are they to be eonsrraed Own as an endorsement ojthe subject of the report or a recommendation for its use. There is no warranty by iCC Evaluation Service, LLC. express or implied m ro any jendtng or other matter to this report, or = to any product covered by the repon Copyright 0 201S ICC Evaluation Service, LLC. All rights reserved. Page 1 of 1 I �; Florida Building Code Online Page 1 of 1 • Busees �,P�iofess` al egr��att r�r : � '���.� ,�.,� 4 � y�i�� P►1� - �. ��de.'{�yf�04F',fi` etas as'aat' de (f i11' 1 lu•i,5' C�.h t itUd�fi Or@ Search Criteria Reflne Search Code Version 2014 FLO 17142 Application Type ALL Product Manufacturer ALL Category ALL Subcategory ALL Application Status ALL Compliance Method ALL Quality Assurance Entity ALL Quality Assurance Entity Contract Expired ALL Product Model, Number or Name ALL Product Description ALL Approved for use In HVHZ ALL Approved for use outside HVHZ ALL Impact Resistant ALL Design Pressure ALL Other ALL Rearrh Rear, lie _ Annllr Min.... Eta Ix" M nufactursr `dalldated 8v Status FL17147- Revision Huber Engineered Woods LLC ICC Evaluation Service, Approved M Category: Structural Components LLC, HiSto Subcategory: Products Introduced as a Result of New (205) 599-9800 Technology c 259{ p-�ar1 5k:fna Raid T•')^h�s .. '2 an^^ Fhanr. 850-40-182d The State of F!orfda 13 an AVO�O employer, caayrlatt 1037.1Q:R- tt tg-r F1nr�a Ahnry 5jajZ nr :: �f��6yr!v cn v wit RPAmd Sal'! n under F)clda ta., email address are Quoik remrds. if you do not nant Vow e-mall addicts refused tr, rsspory to a pubJk-records mgmt, do not sand eletuonk ma!l to this anttty, !nr—d, contact the aMca by phase er by tndttive onaf mall, )ryou haaM 4u4sdon% P!easa wntxt 850.i87.1395. 'Pvnuant to 5=ton 455.275(1). Aor'da statutes, enact)va October 1, 2612, Ckensers :lwnsed under Ctvoter 455, F.S. must P mWe the Oeparment with an ltrrtal) address It they hire ono. Tha malls prov`dad may be used for ofklal ammunleatlan -1h the ¢cortseu- Ho,11 ema0 addresses era publ,c retort), If you do not w!sh to supply a cersoml address, pf: am prw-!de the Department wrath an e-all addr so whch can be rrrde available to the puelk, To detarrWm If you are a lkrr•.soe under Chaptef 455, F.S., please ock lim„ Product Apprvml Atsepia: Credit Card safe https://www.floridabuilding.org/pr/`pr_app_lst.aspx 4/ 12/2017