HomeMy WebLinkAboutICC-ES REPORT ESR-1473See— /4-r.3
DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES
SECTION: 0616 00—SHEATHING
DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
SECTION: 07 30 05—ROOFING FELT AND UNDERLAYMENT
REPORT HOLDER:
HUBER ENGINEERED WOODS, LLC
ONE RESOURCE SQUARE
10925 DAVID TAYLOR DRIVE, SUITE 300
CHARLOTTE, NORTH CAROLINA 28262
EVALUATION SUBJECT:
ZIP SYSTEM® AND ZIP SYSTEM+Tm ROOF SHEATHING
8CC ICC
C PMG c1cc
LISTED
Look for the trusted marks of Conformity! 'VVV• -
"2014 Recipient of Prestigious Western States Seismic Policy Council f
(WSSPQ Award in Excellence" A Subsidiary of
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not
specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to anyfinding or other matter in this report, or as to any product covered by the report.
Copyright © 2015 ICC Evaluation Service, LLC. All rights reserved
IMES Evaluation Report ESR-1473*
Reissued September 2015
This report is subject to renewal September 2017.
www.icc-es.org 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council®
DIVISION: 06 00 00—WOOD, PLASTICS, AND
COMPOSITES
Section: 06 16 00—Sheathing
DIVISION: 07 00 00--THERMAL AND MOISTURE
PROTECTION
Section: 07 30 05—Roofing Felt and Underlayment
REPORT HOLDER:
HUBER ENGINEERED WOODS, LLC
ONE RESOURCE SQUARE
10925 DAVID TAYLOR DRIVE, SUITE 300
CHARLOTTE, NORTH CAROLINA 28262
(800)933.9220
www.huberwood.com
EVALUATION SUBJECT:
ZIP SYSTEM® AND ZIP SYSTEM+Ta ROOF SHEATHING
1.0 EVALUATION SCOPE
Compliance with the following codes:
is 2015, 2012 and 2009 International Building Code' (IBC)
* 2015. 2012 and 2009 Intemattional Residential Codes
(IRC)
■ 2013 Abu Dhabi Intemational Building Code (ADISC)'
'TheADIBC is based on the 2009 18C. 2009 t8C cede sections referenced
In this report are the same sections in the ADIBC
Properties evaluated:
■ Structural —wind uplift resistance
i Nonclassified roof covering
v Classified roof covering
■ Weather resistance
2.0 USES
ZIP Systems and ZIP System+T" roof sheathing panels
are used as combination roof sheathing and roof
underlayment.
3.0 DESCRIPTION
The ZIP Systems and ZIP System+TM roof Sheathing
panels are wood structural panels having a laminated
facer. The ZIP System+Tm panels are manufactured using
a different resin than the Zip Systems panels.. The panels
are installed with a proprietary seam tape, which allows the
systems to be used as an alternate to the underlayment
required in Chapter 15 of the IBC and Chapter 9 of the
IRC. The OSB substrate complies with U.S. DOC PS-2 for
wood structural panels and is overlaid on one side with a
medium -density, phenol -impregnated, polymer -modified
sheet material. The standard -size panels are nominally
4 feet by 8 feet. Oversize panels, wider than 4 feet
(1219 mm) or longer than 8 feet (2438 mm), or both, are
also produced. The panels are available with either a
square -finished -edge profile a tongue -and -groove edge
profile or a machined edge profile. The proprietary seam
tape is a self -adhering sheet -type membrane consisting of
acrylic adhesive laminated to a polyolefin backing, and the
face of the tape is labeled with ESR-1473. The tape is
0.012 inch thick (0.30 mm) with a minimum width of
3 inches (76.2 mm), and comes in rolls of varying length.
4.0 INSTALLATION
4.1 General:
Installation of ZiP Systems and ZIP System+TM roof
sheathing must comply with the applicable code, this report
and the manufacturer's published installation instructions.
The installation instructions are to be available at the
jobsite , at all times during installation. The instructions
within this report must govern if there are any conflicts
between the manufacturer's published instructions and this
report.
4.2 Application:
The ZIP Systems and ZIP System+TM roof sheathing
panels must be installed with the longer dimension
perpendicular to the roof framing and fastened to the
roof framing in accordance with the applicable code for
wood structural panels. The panels must be installed in
accordance with the panel span rating as shown on the
panels. All corners are to be securely fastened. Tongue -
and -groove and machined edge panels are designed to
provide the correct gap size at the panel edges during
installation. Squared -edged panels must be spaced apart a
minimum of '/a inch (3.18 mm) at the time of installation.
End joints of adjacent panel runs must be staggered. The
panel must be installed with the laminated phenol -
impregnated polymer -modified sheet material facing to
the exterior. All ZIP Systems and ZIP System+TM roof
sheathing seams must be sealed with the Zip System®
tape. All overlay surfaces must be free of any significant
presence of debris particles or sawdust prior to installation
of the ZIP System tape. Overlay surfaces must be void of
any free water prior to application of the ZIP Systems tape.
The ZIP Systems tape edges must be sealed and the tape
is to be centered within +/-'/2 inch 112.7 mm) of all panel
edge seam centers. All ZIP System and ZIP System+T24
'Revised November 2015
ICC-ES Evaluatioa Reports are not to be comtrued as representing aesthetics or any other attributes nor specifically addrarsed, nor are they to be construed
as on endorsement of the subject of the report or a recammendotion far its use. There is no warranty by JCC Evaluation Service, LLC, empress or implied as,
to any finding or other matter In this report, or ar to any product coveted by the report -4 Owl
Copyright 0 2015 ICC Evaluaton Service, LLC. All tights reserved. Paqo7 of 2
ESR-1473 I Most Widely Accepted and Trusted Page 2 of 2
roof sheathing surface defects, openings, cracks, etc., that
completely penetrate the overlay and substrate, and
caused by handling or construction work, must be covered
with the ZIP System® tape. The ZIP Systeme tape must
extend a minimum of 1 inch (25.4 mm) past the panel edge
T-joint intersections. The ZIP System® tape must be
adhered to the ZIP System® and ZIP System+TM roof
sheathing. Wrinkles in the ZIP System seam tape are
acceptable unless they create a leak path to the panel
seam.
4.3 Roof Assemblies
4.3.1 Classified Roof Coverings
4,3.1.1 Class A: Underlayment is not required for a
minimum r/cinch thick Zip System+Tm roof sheathing with
Class A asphalt glass fiber mat shingles.
4.3,1.2 Class B: Underlayment is not required for a
minimum 7/,e-inch thick Zip System® roof sheathing with
Class A asphalt glass fiber mat shingles.
4.3.2 Nonclassified Roof Coverings: The ZIP System®
and ZIP System+T" roof sheathing panels are limited to
installation on buildings permitted to have nonclassified
roof coverings using code -complying asphalt -fiberglass
shingles, metal shingles, metal panels, wood shakes, wood
shingles, built-up roofing, slate and slate -type shingles,
and clay and concrete tile roof coverings. Roof coverings
may be applied directly to the taped ZIP System® and ZIP
System+Tu roof panels unless multi -layer underlayments
are required.
4.4 Wind Uplift Resistance:
Wind uplift design loads and ZIP System® and ZIP
System+T`^ roof wood structural panel allowable uplift
resistance shall be determined in accordance with
Sections 1609 and 2304.8.2 of the 2015 ISC or 2304.7.2 of
the 2012 and 2009 ISC and Section R301.2.1 of the IRC.
Roof coverings must be fastened to the sheathing with
mechanical fasteners sufficient to resist the design uplift
load.
5.0 CONDITIONS OF USE
The ZIP System® and ZIP System+TM roof sheathing
panels described in this report comply with, or are suitable
alternatives to what is specified in, those codes listed in
Section 1.0 of this report, subject to the following
conditions:
5.1 This evaluation report and the manufacturer's
published installation instructions, when required by
the code official, must be submitted at the time of
permit application.
5.2 The ZIP System® and ZIP System+TAB roof sheathing
panels must be manufactured, identified and installed
in accordance with this report and the manufacturer's
published installation instructions.
6.3 The ZIP System® and ZIP System+"4 roof sheathing
panels are limited to code -approved structural use for
wood structural panels with either a 24116, 32116 or
40/20 span rating.
6.4 In jurisdictions enforcing the IBC, the roof covering
system incorporating the panels is limited to
installations in the following construction types:
• Type III-B and Type V-B
• Type III -A or Type V-A under the conditions
specified in footnote d of IBC Table 601
• Type III -A or Type V-A under the conditions
specified in footnote b of ISC Table 601, far
occupancies other than Group F-1, H, M and S-1
In jurisdictions enforcing the IRC, the roof covering
system incorporating the panels may be installed on
structures constructed in accordance with the IRC.
6.6 Enclosed attics and rafter spaces must be ventilated
in accordance with the applicable code, except where
unvented conditioned attic assemblies are permitted
by 2015 and 2012 IRC Section R806.5 or 2009 IRC
Section R806.4.
5.6 An ice barrier must be provided as required by
Section 1507.2.8.2 of the IBC and Section R905.2.7
of the 2015 IRC and Section R905.2.7.1 of the 2012
and 2009 IRC.
6.7 Installation is limited to roofs having a slope of 2:12
(16.67% slope) or greater.
5.8 ZIP System° and ZIP System+m roof sheathing
panels are manufactured by Huber Engineered
Woods, LLC, in Crystal Hill, Virginia; Commerce,
Georgia; Broken Bow, Oklahoma; and Easton, Maine,
under a quality -control program with inspections by
ICC-ES.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Cnteria
for Wood Structural Panel Roof Sheathing Factory -
laminated with an Alternative Roof Underlayment (AC266),
dated May 2008 (editorially updated October 2015).
7.0 IDENTIFICATION
Each ZIP System® and ZIP System+TM roof sheathing
panel covered by this report must bear a label that includes
the manufacturer's name (Huber Engineered Woods, LLC)
and address; the product name; the evaluation report
number (ESR-1473); and the grade, performance category
and bond classification.
The panel mill label and span rating, grade, performance
category and bond classification label must be visible on
the bottom face of panels, opposite the laminated facer.
The ZIP System® tape roll is labeled with the product
name and the evaluation report number (ESR-1473).
IMES Evaluation Report ESR-1473 FEC Supplement
Reissued September 2015
This report is subject to renewal September 2017.
www.icc-es.org 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council®
DIVISION: 06 00 00—WOOD, PLASTICS, AND COMPOSITES
Section: 06 16 00—Sheathing
DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
Section: 07 30 06—Roofing Felt and Underlayment
REPORT HOLDER:
HUBER ENGINEERED WOODS, LLC
ONE RESOURCE SQUARE
10925 DAVID TAYLOR DRIVE, SUITE 300
CHARLOTTE, NORTH CAROLINA 28262
(800) 933-8220
www.huberwood.com
EVALUATION SUBJECT:
ZIP SYSTEM° AND ZIP SYSTEM+m ROOF SHEATHING
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that ZIP System° and Zip System+Tr" roof sheathing,
recognized in ICC-ES master evaluation report ESR-1473, has also been evaluated for compliance with the codes noted
below.
Applicable code editions:
0 2014 Florida Building Code —Building
1111 2014 Florida Building Code —Residential
2.0 CONCLUSIONS
The ZIP System® and ZIP System+T" roof sheathing, described in Sections 2.0 through 7.0 of the master evaluation report
ESR-1473, complies with the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential,
provided the design and installation are in accordance with the International Building Code® provisions noted in the master
report, and with the condition that wind uplifting design loads must be determined in accordance with Section 1609 of the
Florida Building Code —Building and Section R301.2.1 of the Florida Building Code —Residential.
Use of the ZIP Systemo and ZIP System+T" roof sheathing for compliance with the High -Velocity Hurricane Zone
provisions of the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential has not been
evaluated and is outside the scope of the evaluation report.
For products falling under Florida Rule 9N-3, verification that the report holder's quality -assurance program is audited by a
quality -assurance entity approved by the Florida Building Commission for the type of inspections being Conducted is the
responsibility of an approved validation entity (or the code official, when the report holder does not possess an approval by
the Commission).
This supplement expires concurrently with the master report, reissued September 2015 and revised November 2015
ICC-ES Evaluation Reports are not to be cmuarued as representing oestheties or any other ounbutar not spectrally addreved, nor are they to be construed
or an endorsement of the subject of the report or a recommendation for its ure. There is no warronry by ICC Evaluation Service, LLC express or tmpfied m
to anyfindrng or ather matter in this report, or ar to any product covered by the report plow
Copyright* 2015 ICC Evaluation Service, LLC. Al rights reserved. Page 1 of 1
• Florida Building Code Online
Page 1 of 1
Search Criteria Reflne Search
Code Version
2014
FL#
17147
Application Type
ALL
Product Manufacturer
ALL
Category
ALL
Subcategory
ALL
Application Status
ALL
Compliance Method
ALL
Quality Assurance Entity
ALL
Quality Assurance Entity Contract Expired
ALL
Product Model, Number or Name
ALL
Product Description
ALL
Approved for use In HVHZ
ALL
Approved for use outside HVHZ
ALL
Impact Resistant
ALL
Design Pressure
ALL
Other
C-F, ®oer,Na _ ennit..vliw,...
ALL
F�
7YD0rT
urar
Validated Sv
Status
FL17147_
Revisioneered
Woods LLC
[CC Evaluation Service,
Approved
al
Structural Components
LLC.
History
ry- Products Introduced as a Result of New
(205) 599-9800
comet Us : 7t019iart et-tn a W d Ulah'UCa Fl 121S: Frcnr. 850-4e7.1924
The State of Fonda Is an Mall 2,nDl yer. Ceawrfant 2007-2911 Ra,�FlarNa F.M:y malc nt ;; :: &2A m,.m.n
Urder. RcWL law, email address am pubix r,,ands. U you do not want your a fr6V] lddr. s released to responsa to a pub':ic-mcorde regvtst, do not Sand
eiectrantd ma9 to this antfty. Itd>pad, Contact the onfca by phone or by tradttlanal mall. If ycu have any Cuesdana, pleasx contact 850.467.1395. •P- rsuant to
SeRbn 455.275(1), Roma Statutes, of =iva ocwtxr 1, 2012, Omnse� ;mnsed under Chapter 455. F.S. must provlde the Depanment with an email address.r
they have ore. The emalta Pravbed may be wed for official CommunlcaVoa w.th the OLattsea. H-er mull addresus am publ-c remrd. It you do not wish to
aupph' a amonal address, please prwlda the Department w,.th an email) address whch Ctn ba eudo avallable to the publlc. To detvmtna It you am a licensee under
Chapter 45s, F.S., Cease cU* UM
Product Approval Ac ce,,92:
Credit Card
Safe
https://www.floridabuilding.org/pr/pr_app_lst.aspx
4/12/2017