NOTICE OF ACCEPTANCE (NOA) aiamidade eovlccunomy
Nichiha USA, Inc.
6465 E. Johns Grassing FILE COPY
Johns Creek, GA 30097
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction
materials. The documentation submitted has been reviewed and accepted by Miami Dade County RER
Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority
Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control
Section (in Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right
to have this product or material tested for quality assurance purposes. If this product or material fails to
perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHD may
immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. RER
reserves the right to revoke this acceptance, if it is determined by Miami -Dade County Product Control
Section that this product or material fails to meet the requirements of the applicable building code.
This product is approved as described herein, and has been designed to'comply with the Florida Building
Code, including the High Velocity Hurricane Zone.
DESCRIPTION: NichiProducts'rM Fiber -Cement Siding
APPROVAL DOCUMENT: Drawing No. ITS N1090403, titled "NichiBoard", sheets 1 and 2 of 2 and
Drawing No. ITS N2090403, titled "NichiPanel", sheets 1 and 2 of 2, both dated 03/16/2009, prepared by
Nichiha USA, Inc, signed and sealed by Carl D. Fussner, P.E. on 10113/2015, bearing the Miami Dade
County Product Control revision stamp with the Notice of Acceptance number and expiration date by the
Miami -Dade County Product Control Section.
MISSILE IMPACT RATING: Large and Small Missile Impact Resistant
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and
following statement: "Miami Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been
no change in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change
in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of
any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to
comply with any section of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed .
by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then
it shall be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its
distributors and shall be available for, inspection at the job site at the request of the Building Official.
This NOA revises NOA # 14-0715.03 and consists of this page 1 and evidence pages E-1 and E-2, as well as .
approval document mentioned above.
The submitted documentation was reviewed by Carlos M. Utrera, P.E.
NOA No.15-1102.14
MIAMMAdE COWITYM Expiration Date: July 22, 2019
Approval Date: February 18, 2016
��I►�?Alb Page 1
Nichiha USA, Inc.
NOTICE OF ACCEPTANCE: ' EVIDENCE SUBMITTED
A. DRAWINGS
1.. Drawing No. ITS N1090403, titled "Nichi.Board", sheets-1 and 2 of 2 and Drawing
No. ITS N20904035 titled "NichiPanel", sheets 1 and 2 of 2, both dated 03/16/2009,
prepared by Niclift USA, Inc, signed and sealed by Carl D. Fussner, P.E. on
10/13/2015..
B. TESTS "Submitted under NOA # 09-0511.01 "
1. Test reports on 1) Air Infiltration Test, per FBC, TAS 202-94
2) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94
3) Water Resistance Test, per FBC, TAS 202-94
4) Large Missile Impact Test per FBC, TAS 201-94
5) Cyclic Wind Pressure Loading per FBC, TAS 203-94
along with marked -up drawings and installation diagram of NichiProducts Fiber -
Cement Panels, prepared by Intertek Testing Services NA LTD, Report No.
3145127COQ-004A, dated 08107/08, signed and sealed by Rick Curkeet, P.E.
2. Test reports on 1) Uniform Static Air Pressure Test, Loading per FBC TAS .202-94
C 2) Large Missile Impact Test per FBC, TAS 201-94
3) Cyclic Wind Pressure Loading per FBC, TAS 203-94 -
along with marked -up drawings and installation diagram -of NichiBoards and
EcoPlanks, prepared by Intertek Testing Services NA LTD, Report No.
3145127COQ-004B, dated 10/24/08, signed and sealed by Rick Curkeet, P.E.
3. Test report on Standard Specification for Flat Non -Asbestos Fiber -Cement Sheets of
' NichiProducts Fiber -Cement Panels, per ASTM C1186-07, prepared by Intertek
j Testing Services NA LTD, Report No. 3145123COQ-005, dated 05/20/08, with a
revision dated 02/02109, signed and sealed by Rick Curkeet, P.E.
4. Test report on Surface Burning Characteristics of NichiPanel Fiber -Cement Panels,
per ASTM E84-08, prepared by Intertek Testing Services NA LTD, Report No.
3145123COQ-006, dated 06/25/08, with a revision dated 04/03/09, signed and sealed
by Rick Curkeet, P.E.
5. Test report on Standard Test Method for Behavior of Materials in a Vertical Tube
Furnace at 7500C of Nichiha M series unprimed cementitious, per ASTM E136-99,
prepared by Intertek Testing Services NA LTD, Report No. 3105885COQ-002, dated
! 10/20/06, with a revision dated 03/30/09, signed and sealed by Rick Curkeet, P.E.
oz�li��1G
Carlos M. Utrera, P.E.
Product Control Examiner
NOA No.15-1102.14
Expiration Date: July 22, 2019
Approval Date: February 18, 2016
E-1
i
Nichiha USA. Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBNIITTED
C. CALCULATIONS "Submitted under NOA # 14 0715.03"
1. Anchor calculations prepared by Progressive Engineering, Inc., dated
10/22/2014, signed and sealed by Carl D. Fussner, P.E.
"Submitted underNOA # 09-051L01"
2. Anchor analyses prepared by Category 5 Engineering Services, Inc., dated
04/03/2009, signed and sealed by Emma T. Mellinger, P.E.
D. QUALITY ASSURANCE
1. Miami Dade Department of Regulatory and Economic Resources (RER)
E. MATERIAL CERTIFICATIONS
1. None.
F. STATEMENTS
1. Drawing No. ITS N1090403 and ITS N2090403 statements of code conformance to
the 51 edition (2014) FBC issued by Nichiha. USA, Inc, dated 03/16/2009, signed and
sealed by Carl D. Fussner, P.E. on 10/13/2615.
2. Statement letter of no financial interest issued by Progressive Engineering, Inc., dated
10/13/2015, signed and sealed by Carl D. Fussner, P.E.
o2�ii �yp16 .
Carlos M. Utrera, P.E.
Product Control Examiner
NOA No.15-1102.14
Expiration Date: July 22, 2019
Approval Date: February 18, 2016
E2
53"
o/c S
I?
12" Panels Shown
/ 51/4" Panels Shown
�Iw>wo�
u �oiuw�.��u�r
r.o.�ac�i�rwo■v
W
wrv����1�1
U
4
U�0•�U�C
D��•O
J•�O��U���P
_ -
❑��n•�
����c.wro+waoovoo
•v��n�s.v���v��v
a
rlr1���1�i
O�O�U��.00■0dU
v
v �Q�
❑ u.�a�
v �..
v.�c��
ITS N1080409 �� '
o�March 16, 2000
o/c
�.�,�ySpacing
. (T yp-)
4" Panel Height
(Typ')
i" Overlap
(TYp•)
Fiber Cement Siding
DESCRIPTION and SPECIFICATION NichiBoard lap siding
material is a non -asbestos fiber cement product tested In
accordance with ASTM C-1185 & ASTM G1186 Type A
meeting the requirements of the 2014 Florida Building Code
(HVHZ). Boards are available in a variety of widths within
the maximum and minimum dimensions specified below.
I
Plank Dimensions
Width
Len h
Thickness
5 XW Min,
12'
5/l6"
12" Max.
12'
T Y6" .
Deslgn Pressure Ratina •126 psf
LIMITATIONS
1. All installation shall be done in accordance
with this Notice of Acceptance, the
manufacturer's installation recommendations,
and the applicable sections of the 2014
Florida Building Code including High Velocity
Hurricane Zone where Required.
2. Wood studs and plywood sheathing
supporting NlchiBoard and EcoPlank siding
shall conform to the 2014 Florida Building
Code (including the HVHZ where required),
and the requirements of this Notice of
Acceptance (See Note Sheet 2).
3. Siding installed as specified herein shall be
classified as Large Missile Impact
l?ftrtewa*an No 71907 ,
Il�� • $ r
�^p 0. STATE OF : QJ
6486 E. Johns Crossing. Johns Creek, GA; 3=7
F1 COA 27447
chiBoard Siding
ather•Resisont Harrier
ed x 2 W Common Nall @
5 %, o/o Verucaily. 9" o%
Horizontally. V4" Min.,
2" Max. Edge Distance.
2,lywood Sheathing
toned to Studs per 2014
ida Building Code
,hlBoard Siding
)ether6Restsent Banter
Bd x 2 V Common Nell Q
5 %" c/o Vertically, a- o/c
Horizontally. V4" Min.,
2" Max. Edge Distance.
Plywood Sheathing
toned to Studs per 2014
NICHIBOARD SIDING INSTALLATION
• The boards shall be applied horizontally commencing from the
bottom course of the wail.
• Each successive course shall overlap the prior course by 1 Y4%
• Any vertical joints shall be over framing members, with
fasteners either side of the joint.
• The planks shall be installed over V8" APA rated exterior -grade
plywood (SG - 0.50 min.) supported by 2" x 4" minimum wood
studs spaced a maximum of IS" O.G.
• The siding shall be fastened through over -lapping planks with
Sd x 2 Ya" long common nails over wood studs.
• A row of fasteners shall be placed in the overlap of each
course, spaced S" o!c in the horizontal direction.
• Successlve rows of fasteners shall be spaced not more than 5
%" o/c. (boards greater than 6 %" in width shall require an
additional row of fasteners'in the center of the plank).
• A distance of between %4" and 2" from the edges shall always
be observed.
PLYWOOD SHEATHING NOTE
NichlSoard Fiber -Cement Lap Siding is designed to be installed
to plywood sheathing. Such plywood shall be %" (5-ply)
minimum, APA rated sheathing, Structural 1 grade, with a
Specified specific gravity of 0.50 or greater (e.g. Douglas
Fir -Larch or Southern Pine). Use of other grade plywood shall
require a site -specific fastener design for the siding attachment,
signed and sealed by a Florida Registered Professional
Engineer.
2" X Stud
@ 16" of
(TYP•)
6" Max.
o% Spacir
(TYP-)
6" Max.
ofc Spacing
MP.)
48"`Panel .-Width
�48"Panel Width
�
C
Ig
. .
.
. .
. .
. .
. .
c
a
7.
. . .
. . .
. . ..
.'
. .
. . .
. . .
.
ITS N2MO3
DESCRIPTION and SPECiFICA71ON
NichiPanel siding material is a non -asbestos
fiber cement product tested in accordance
with ASTM C•1185 & ASTM CA 188 Type A
meeting the requirements of the 2014
Florida Building Code (HVHZ). Panels are
available in four -foot Widths within the
maximum and minimum dimensions
specified below.
Plank Dimensions
Width
Length
Thickness
48"
81
S"
48"
10,
6�ia"
48"
12'
Y16"
Design Pressure Rating .104 psi
LIMITATIONS
1. All installation shall be done in -accordance
with this Notice of Acceptance, the
manufacturer's installation
recommendations, and the applicable
sections of the 2014 Florida Building Code
Including High Velocity Hurricane Zone
where Required,
2. Wood studs and plywood sheathing
supporting NichiPenel siding shall conform
to the 2014 Florida Building Code
(including the HVHZ where required), and
the requirements of this Notice of
Acceptance (See Note Sheet 2).
3. Siding installed as specified herein shalI4111ltsy,1#4,
classified as Large Missile impact
Resistant. �� ��. .••���•�.��/ ,�I
% ,
a ift y No 71907
Ha�Goie � . • ••
� -r o2. � •* � a
STATE OF
40
~Wwr raw"
dro
X,
e Fiber Cement Siding I 6465 E Johns Crossing, Johns Creek, GA. 3DO27
Mm'h 16, 2909 r 1 COA 2r447
NICHIPANEL SIDING INSTALLATION
The panels shall be applied vertically, avoiding horizor
joints.
The panels shall be installed over %" APA rated
exterior -grade plywood (SG = 0.60 min.) supported by
2"x4" minimum wood studs spaced a maximum of 16"
Fasteners shall be placed at 6" o/c in the vertical direr
and 6"o/c In the horizontal direction.
A distance of between %4'
always be observed.
iehiPanel Siding
eather-Resisanti3arrler
PLYWOOD SHEATHING NOTE
6d x 2" Common Nail @
NichiPanei Fiber -Cement Siding is designed to be installed to
6" ok vertically, a" o/c
Horizontally. V" Min.,
plywood sheathing. Such plywood shall be %" (5-ply) minimum,
3" Max, Edge Distance.
APA rated sheathing, Structural 1 grade, with a specified
specific gravity of 0.50 or greater (e.g. Douglas Fir -Larch or
"Plywood sheathing
istened to Studs per 2014
Southern Pine); Use of other grade plywood shall require a
oride Building Code
site -specific fastener design for the siding attachment, signed
and sealed by, a Florida Registered Professional Engineer.
Such plywood sheathing shall be supported by framing
consisting of 2" x 4" minimum wood studs, or 2" x 6" 18ga metal
studs, each at 16" o/c. Plywood shall be attached to the framing