DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES
SECTION: 0616 00—SHEATHING --
s DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
SECTION: 07 30 05—ROOFING FELT AND UNDERLAYMENT
REPORT HOLDER:
HUBER ENGINEERED WOODS, LLC
ONE RESOURCE SQUARE
10925 DAVID TAYLOR DRIVE, SUITE 300
CHARLOTTE, NORTH CAROLINA 28262
EVALUATION SUBJECT:
ZIP SYSTEM® AND ZIP SYSTEM+"rm ROOF SHEATHING
ICC . , IC
0MG LISTED
Look for the trusted marks of Conformityl
"2014 Recipient of Prestigious Western States Seismic Policy Council
(WSSPQ Award in Excellence"
A Subsidiary of
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not
specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
�d
Copyright © 20151CC Evaluation Service, LLC. All rights reserved.
IMES Evaluation Report ESR-1473*
Reissued September 2015
This report is subject to renewal September 2017.
wwrwAcc-es.org 1 (800) 423-6587 j (562) 699-0543 A Subsidiary of the international Code Council®
DIVISION: 06 00 00—WOOD, PLASTICS, AND
COMPOSITES
Section: 06 16 00—Sheathing
DIVISION: 07 00 00—THERMAL AND MOISTURE
PROTECTION-
- Section:-07 30-05—Roofing Felt and Underlayment
REPORT HOLDER:
HUBER ENGINEERED WOODS, LLC
ONE RESOURCE SQUARE
10925 DAVID TAYLOR DRIVE, SUITE 300
CHARLOTTE, NORTH CAROLINA 28262
(800) 933.9220
www.huberwood.com
EVALUATION SUBJECT:
ZIP SYSTEM® AND ZIP SYSTEM+T" ROOF SHEATHING
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2015, 2012 and 2009 International Building Codee (IBC)
■ 2015, 2012 and 2009 International Residential Code®
(IRC)
■ 2013 Abu Dhabi International Building Code (ADIBC)l
'The ADISC is based on the 2009 IBC. 2009 !BC code sections referenced
In this report are the same sections in the ADISC.
Properties evaluated:
■ Structural —wind uplift resistance
■ Nonclassified roof covering
■ Classified roof covering
■ Weather resistance
2.0 USES
ZIP System® and ZIP System+TM roof sheathing panels
are used as combination roof sheathing and roof
underlayment.
3.0 DESCRIPTION
The ZIP System® and ZIP System+T"' roof Sheathing
panels are wood structural panels having a laminated
facer. The ZIP System+Tm panels are manufactured using
a different resin than the Zip System® panels.. The panels,
are installed with a proprietary seam tape, which allows the
systems to be used as an alternate to the underlayment
required in Chapter 15 of the IBC and Chapter 9 of the
IRC. The OSB substrate complies with U.S. DOC PS-2 for
wood structural panels and is overlaid on one side with a
medium -density, phenol -impregnated, polymer -modified
sheet material. The standard -size panels are nominally
4 feet by 8 feet: Oversize -panels, wider than 4 feet
(1219 mm) or longer-than-8-feet (2438 mm), or both, are
also produced. —The panels -are available with either a
square -finished -edge profile a tongue -and -groove edge
profile or a machined_ edge profile. The proprietary seam
tape is a self -adhering sheet -type membrane consisting of
acrylic adhesive laminated to a-polyolefin backing, and the
face of the tape is labeled with ESR-1473. The tape is
0.012 inch thick (0.30 mm) with a minimum width of
3 inches (76.2 mm), and comes in rolls of varying length.
4.0 INSTALLATION
4.1 General:
Installation of ZIP System® and ZIP System+TM roof
sheathing must comply with the applicable code, this report
and the manufacturer's published installation instructions.
The installation instructions are to be available at the
jobsite at all times during installation. The instructions
within this report must govern if there are any conflicts
between the manufacturer's published instructions and this
report.
4.2 Application:
The ZIP System® and ZIP System+TM roof sheathing
panels must be installed with the longer dimension
perpendicular to the roof framing and fastened to the
roof framing in accordance with the applicable code for
wood structural panels. The panels must be installed in
accordance with the panel span rating as shown on the
panels. All corners are to be securely fastened. Tongue -
and -groove and machined edge panels are designed to
provide the correct gap size at the panel edges during
Installation. Squared -edged panels must be spaced apart a
minimum of '/a inch (3.18 mm) at the time of installation.
End joints of adjacent panel runs must be staggered, The
panel must be installed with the laminated phenol -
impregnated polymer -modified sheet material facing to
the exterior. All ZIP System® and ZIP System+TA1 roof
sheathing seams must be sealed with the Zip System®
tape. All overlay surfaces must be free of any significant
presence of debris particles or sawdust prior to installation
of the ZIP System tape. Overlay surfaces must be void of
any free water prior to application of the ZIP System® tape.
The ZIP System® tape edges must be sealed and the tape
is to be centered within +/-'/2 inch 1e12.7 mm) of all panel
edge seam centers. All ZIP System and ZIP System+TM
'Revised November 2015
(CC -ES Evaluation Reports ore not to be construed as representing aenhbler or any other attributer not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation jar its ure. There dr no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter to this report, a," to any produes covered by the report
Copyright 0 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 2
ESR-1473 I Most Widely Accepted and Trusted
roof sheathing surface defects, openings, cracks, etc., that
completely penetrate the overlay and substrate, and
caused by handling or construction work, must be covered
with the ZIP System® tape. The ZIP Systeme tape must
extend a minimum of 1 inch (25.4 mm) past the panel edge
T-joint intersections. The ZIP System® tape must be
adhered to the ZIP System® and ZIP System+TH roof
sheathing. Wrinkles in the ZIP System seam tape are
acceptable unless they create a leak path to the panel
seam.
4.3 Roof Assemblies
4.3.1 Classified Roof Coverings
4.3.1.1 Class A: Underlayment is not required for a
minimum 1/2-anch thick Zip System+Tee roof sheathing with
Class A asphalt glass fiber mat shingles.
4.3.1.2 Class B: Underlayment is not required for a
minimum 7/18-inch thick Zip Systemoroof sheathing with
—Class -A asphalt glass fiber mat shingles.
4.3.2 Nonclassified Roof Coverings: The ZIP System®
and ZIP System+Tea roof sheathing panels are limited to
—installation on buildings permitted to have nonclassified
roof coverings using code -complying asphalt -fiberglass
shingles, metal shingles, metal panels, wood shakes, wood
shingles, built-up roofing, slate and slate -type shingles,
and clay and concrete tile roof coverings. Roof coverings
may be applied directly to the taped ZIP System® and ZIP
System+TM roof panels unless multi -layer underlayments
are required.
4.4 Wind Uplift Resistance:
Wind uplift design loads and ZIP System® and ZIP
System+TM roof wood structural panel allowable uplift
resistance shall be determined in accordance with
Sections 1609 and 2304.8.2 of the 20151BC or 2304.7.2 of
the 2012 and 2009 IBC and Section R301.2.1 of the IRC.
Roof coverings must be fastened to the sheathing with
mechanical fasteners sufficient to resist the design uplift
load.
5.0 CONDITIONS OF USE
The ZIP System® and ZIP System+TM roof sheathing
panels described in this report comply with, or are suitable
alternatives to what is specified in, those codes listed in
Section 1.0 of this report, subject to the following
conditions:
5.1 This evaluation report and the manufacturer's
published installation instructions, when required by
the code official, must be submitted at the time of
permit application.
5.2 The ZIP System® and ZIP System+TM roof sheathing
panels must be manufactured, identified and installed
in accordance with this report and the manufacturer's
published installation instructions.
5.3 The ZIP System® and ZIP System+TM roof sheathing
panels are limited to code -approved structural use for
Page 2 of 2
wood structural panels with either a 24/16, 32/16 or
40/20 span rating.
SA In jurisdictions enforcing the IBC, the roof covering
system incorporating the panels is limited to
installations In the following construction types:
• Type 111-13 and Type V-B
• Type III -A or Type V-A under the conditions
specified in footnote d of IBC Table 601
• Type III -A or Type V-A under the conditions
specified in footnote b of IBC Table 601, for
occupancies other than Group F-1, H, M and S-1
In jurisdictions enforcing the IRC, the roof covering
system incorporating the panels may be installed on
structures constructed in accordance with the IRC.
-5;5 Enclosed attics and rafter spaces must be ventilated
in accordance with the applicable code, except where
unvented conditioned attic assemblies are permitted
by 2015 and 2012 IRC Section R806.5 or 2009 IRC
Section R606.4.
5.6 An ice barrier must be provided as required by
Section' 1507.2.8.2 of the IBC and Section R905.2.7
of the 2015 IRC and Section R905.2.7.1 of the 2012
and 2009 IRC.
6.7 Installation is limited to roofs having a slope of 2:12
(16.67% slope) or greater.
5.8 ZIP System® and ZIP System+m roof sheathing
-panels are manufactured by Huber Engineered
Woods, LLC, in Crystal Hill, Virginia; Commerce.
Georgia; Broken Bow, Oklahoma; and Easton, Maine,
under a quality -control program with inspections by
ICC-ES.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria
for Wood Structural Panel Roof Sheathing Factory -
laminated with an Alternative Roof Underlayment (AC266),
dated May 2008 (editorially updated October 2015).
7.0 IDENTIFICATION
Each ZIP System and ZIP System+TM roof sheathing
panel covered by this report must bear a label that includes
the manufacturer's name (Huber Engineered Woods, LLC)
and address; the product name; the evaluation report
number (ESR-1473); and the grade, performance category
and bond classification.
The panel mill label and span rating, grade, performance
category and bond classification label must be visible on
the bottom face of panels, opposite the laminated facer.
The ZIP System® tape roll is labeled with the product
name and the evaluation report number (ESR-1473).
1CC-ES Evaluation Report ESR-1473 FSC Supplement
Reissued September 2015
This report is subject to renewal September 2017.
vwvw.icc-es.org 1 (800) 423-8687 1 (562) 699-0543, A Subsidiary of the Intemational Code Council®
DIVISION: 06 00 00—WOOD, PLASTICS; AND COMPOSITES
Section: 06 16 00--Sheathing
DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
Section: 07 30.05—Roofing Felt and Underiayment
REPORT HOLDER: —
HUBER ENGINEERED WOODS, LLC
ONE RESOURCE SQUARE
10926 DAVID TAYLOR DRIVE, SUITE 300 i
CHARLOTTE, NORTH CAROLINA 28262
(800) 933-9220
www.huberwood.com
EVALUATION SUBJECT:
ZIP SYSTEM° AND ZIP SYSTEM+w ROOF SHEATHING
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that ZIP System® and Zip System+rm roof sheathing,
recognized in ICC-ES master evaluation report ESR-1473, has also been evaluated for compliance with the codes noted
below.
Applicable code editions:
■ 2014 Florida Building Code --Building
■ 2014 Florida Building Code —Residential
2.0 CONCLUSIONS
The ZIP System® and ZIP System+sM roof sheathing, described in Sections 2.0 through 7.0 of the master evaluation report
ESR-1473, complies with the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential,
provided the design and installation are in accordance with the International Building Code® provisions noted in the master
report, and with the condition that wind uplifting design loads must be determined in accordance with Section 1609 of the
Florida Building Code —Building and Section R301.2.1 of the Florida Building Code —Residential.
Use of the ZIP System® and ZIP System+TM roof sheathing for compliance with the High -Velocity Hurricane Zone
provisions of the 2014 Florida Building Code —Building and the 2014 Florida Building Code —Residential has not been
evaluated and is outside the scope of the evaluation report.
For products failing under Florida Rule 9N-3, verification that the report holder's quality -assurance program is audited by a
quality -assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the
responsibility of an approved validation entity (or the eade'officiai, when the report holder does not possess an approval by
the Commission).
This supplement expires concurrently with the master report, reissued September 2015 and revised November 2015
ICC-ES Cvaluation Reporu are not to be contrued as representing aesthetms or any other attributes not tpeefcally addressed nor are they to be construed
as on endorsement of the subleci o%the report or o recommendation for as use. There Gr no wornmry by ICC Evaluation Service, LLC. esprvs or implied as
to any/lnding or other matter in Afs report, or ar to any product covered by the report.
Copyright 0 2015 ICC Evaluation Service, I.I.C. All rights reserved. Page 1 oF1
Florida Building Code Online
Search Criteria
Page I of 1
Code Version
2014
FL#
17147
Application Type
ALL
Product Manufacturer
ALL
Category — _ — -
ALL
Subcategory
- ALt_
Application Status
ALL
Compliance Method
ALL
Quallty Assurance.fntlty — -.
ALL
Quality Assurance Entity Contract Expired
ALL —
Product Model, Number or Name
ALL
Product Description
ALL
Approved for use In HVHZ
ALL
Approved for use outside HVHZ
ALL
Impact Resistant —
ALL
Design Pressure
ALL
Other
Se—!.
ALL
Eta
Type
fdanufacti�re_r
Validaked By
$�S
FL17147-
Revision
Huber Engineered Woods LLC
ICC Evaluation Service,
Approved
EU
Category: Structural Components
LLC.
Hlsto
Subcategory: Products Introduced as a Result of New
(205) 599.9800
Technology
nr tact U :: 2601 Blair Stone Read- Tanaha.wn Fl aZno pnane: R50-�7-1924
The State of Florida Is an AVE EO employer. CoovriaM 2007.2013 sraL of Florida_ :; Prtnry eatem!nC :: ACftSiibPIN StatnrMn! •: RetL d o-, enr
Under Florida Law, email addresses are pubix records. It you do not want your e•mall address refused In resporrsa to a public -moms request, do not send
eleMnic mail to this entity. tnMd, contact the office by phone or by tradittonaf mall. If you have any questions, please contact 9 0.487.1395. *Pursuant to
Section 455.175(1), Florida Statutes, effective October 1, 2012, kensaes flrsnsed under Chapter 455. F.S. must provide the Department with an emaill address It
they have one. The emalb provided may be used for official communlmtian w7h the (Ions". However emaill addresses are publ'c record. tfyou do not wish to
supply a personal address, please pruvido the Department wlth an email address which con be made available to the publk. To determine If you are a Itcensee under
Chapter 455. F.S., please mac hire.