HomeMy WebLinkAboutEVALUATION REPORTSCANNED r
BY
C-BUCK Engineering
Florida Certificate ofAuthorization # 8064
Specialty Structural Engineering
Evaluation Report
Of
J.V. Metals
"1 Inch Nailstrip"
Metal Roof Assembly
for
Florida Product Approval
# FL 5985.1
Florida Building Code 2004
Method: 1- D
Category: Roofing
Sub - Category: Non Structural Metal Roofing.
Product:
1"Nailstrip Panel
Material:
Steel
Panel Thickness:
24 gauge Minimum
Panel Width:
16" Maximum
Support Type:
Wood Deck
Prepared for:
J.V. Construction
1952 S.W. Hayworth Ave.
Port St. Lucie, FL 34953
Prepared by:
James L. Buckner, P.E.
Florida Professional Engineer # 3124
Contents:
Evaluation Report Pages 1— 3
Installation Method Pages 4 — 5
2
1334 S. Killian Drive, Suite 4, West Palm Beach, Florida 33403
Phone: (561)491-9927 Fag: (561)491-9928 Email: cbuck@cbuckinc.net
C-BUCK Engineering
FL #:
FL 5985.1
Date:
12/19/05
Report No.: 05-2934NS-16-S4W
Page
2 of 5
Florida Certificate of Authorization # 8064
Specialty Structural Engineering
nufacturer: J.V. Metals
Pi oduct Name: 1" Nailstrip
Pi oduct Category: Roofing
P oduct. Sub -Category: Non -Structural Metal Roofing
l; aluation Method: 1-D
P nel Type: Steel, minimum 24 gauge, minimum yield strength 50'ksi
P Pel Material Material shall comply with Table 1507.4.3
Standards:
'nel Width(s)
16" Maximums (Net Coverage Width),
pport Type:
Wood Deck
(Design of support system is not included in this evaluation) '
pport Description:
5/8" or greater CDX plywood, or wood plank, per Section 2308.10.8
o e Range:
2 : 12 or greater ,
esign Uplift Pressure:
52.5 psf (Safety Factor of 2:1)
ttachment To Support:
Panels shall be attached to the deck, with minimum #10 x minimum
penetration through deck 3/1619, pancake -head, self -tapping,
corrosion resistant, wood screws, per ANSI/ASME B18.6.4.
nderlayment:
Minimum underlayment shall be per Section 1507.4.5
ire Classification:
Fire Classification is outside the scope of Rule 913-72, and is therefore not
fincluded
in this evaluation. Additional approved substrates may be added
for Fire Classification purposes.
[ stallation:
Install the "1 in. Nailstrip Panel' to the deck with screw rows spaced 3"
from all,ends and maximum 16" o.c. thereafter along the length of the
panel, located at each rib. Within rows, screws shall bespaced,
maximum 16" o.c. across'the width of the panel. Install system in
compliance with the attached installation method.
1 FL M FL 5985.1
Date: 12/19/05
Report No.: 05-293-INS-16-S4W
Page 3 of 5
C-BUCK Engineering ,
Specialty Structural Engineering Florida Certificate of Authorization # 8064
Q ality Assurance: Manufacturer has demonstrated compliance of roof panel products in
accordance with the Florida Building Code and Rule 9B-72.070 (3) for
manufacturing'under a quality assurance program audited by an approved
quality assurance entity through Keystone Certifications, Inc.
Pi Irformance Standards: The roof assembly described herein has been tested in accordance with:
• UL580-94 — Test for Uplift Resistance of Roof Assemblies —with
Revisions through February 1998
de Compliance: The product described herein has demonstrated compliance with the
Florida Building Code 2004, Section 1507.4.
Report Scope: This product evaluation is limited to compliance with the structural wind
load requirements of the Florida Building Code, as related to Rule 913-72.
Limitations: The required design wind loads shall be determined for each project. The
maximum fastener spacing listed herein shall not be exceeded. All
rational analysis computations shall be prepared by a qualified design
professional, as required by Florida Building Code, Section 105 or 106.
This product is not approved for use in the High Velocity Hurricane Zone.
Data: 1. UL580-94 with 1998 Revisions Test
By Underwriters Laboratories, Inc. (TST ID: 1740)
File R21264, Project 02NKI 1243, Date: 4/24/03
2. Quality Assurance
By Keystone Certifications, Inc. (QUA ID: 1824)
3. Certification of Independence
By,James L. Buckner, P.E. @ C-Buck Engineering (ANE ID: 1916)
6
i
- FL #: FL 5985.1
Date: 12/19/05
Report No.: 05-293-INS-16-S4W
Page 4 of 5
C-BUCK Engineering
Specialty Structural Engineering Florida Certificate of Authorization # 8064
Installation Method
J.V. Metals
"1 in. Nailstrip" Attached to Wood Deck
16" Coverage
q ee
Panel Profile
Assembly Profile
1
�- FL #: FL 5985.1
Date: 12/19/05
Report No.: 05-293-INS-16-S4W
Page 5 of 5
C-BUCK Engineering
Florida Certificate ofAuthorization # 8064
Specialty Structural Engineering
Installation Method (Continued)
J.V. Metals
461 in. Nailstrip" Attached to Wood Deck
Fasteners -
#10 Pancake; -Head 1" Nailstrip Panel
Self -Tapping Screws �-
Ir.
�— Deck - Minimum 518" Wood
Assembly Isometric View