UES Project No.: 0310.1700455.0000
Date Typed: September 11, 2018
Construction Materials Testing Services I Kt(,tiVtU.
FIELD AND LABORATORY REPORT COVER PAGE SEP 19 2018
Ryan Homes
1450 Centrepark Blvd Suite 340 ST. Lucie County, Permltting
West Palm Beach, FL 33401
Oakland Lake Estates Subdivision House Lot Investigation Lot 3 16 08 ^ 0003
5206 Oakland Lake Circle, Ft. Pierce, St. Lucie County, FL^
requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction materials testing and/or
Id inspection services on the above project. Testing results and/or inspection observations are reported on the attached
eets. The contents of this package are summarized below:
Scope of Work
Work Order No. Date Type of Report
66331-1 1 10/11/2017 In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
REVIEWED 0 REVIEWED AS NOTED
REVISE &RESUBMIT ❑ REJECTED/RESUBMIT
NOT REVIEWED 0 FOR YOUR INFORMATION
bmittals are reviewed for conformance with design intent
d general compliance with the Contract Documents only
stations Do Not Authorize Changes to Contract Sum.
views, Comments and/or corrections does, not relieve the'
ntractor from compliance with the Contract Documents. The
ntractor is responsible for confirming and correlating all
antities, dimensions, tolerances, clearances, fabrication
Dcesses, techniques and sequences of construct n.
mpati6ility of materials and materials coordination then
A with other trades and subcontractors, perfo ance of
rk in a safe and satisfactory manner and for fuJ omphance
h the Contract Documents.
/ DATE/ REV ED BY
A. $'. DESIGN UP This item has been electronically signed and sealed by
_ Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be veriFed on any electronic
copies.
ICC Email: jomcalli@nvdnc.com: tridley@nvrinc.com
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 00000549
Richard E.
Hoaglin, P.E.
2018.09.11
17:19:12
-04'00'
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
FILE COPY
c 3 C414 eA 0 y1fli1wr U11 11:1
WA IA"I ffy 11-11 PC ( 'AIN El I.P11
Ir'llai 4w—.-
zjg-"#cxO 1xiij.'s) SO Cim 6 5 i 1 N io i -,) Gvs
its 37-10104 r, �":matql 10
VuD
11001 ta
TO eznss,3015p, , 'c—
swi,40F,"i 4N'i nI bm
Ya m 'A
r.
A"A
UES Project No: 0310.1700455.0000
- UNIVERSAL UES DOGS No:
UES Report No: 66331-1 ARC 101117
ENGINEERING SCIENCES On -Site Time (hrs): 0.26
Consultants In: Qotklinical Engirieenng *,Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services MaterialsTesting Thieshold Inspection Travel Time (hrs): 0.25
Building Code Administration, Compliance:lnspection& Plan Review Total Time (hrs): 0.60
820 Brevard Avenue, Rockledge, FL 32965 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Estates Subdivision House Lot Investigation
Oakland Lake Circle, Ft. Pierce, St. Lucie County, FL
Date of Activity: Wednesday, 11 October, 2017
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the
purpose of earthwork testing for Lot 3.
DENSITYTEST
While on site, the technician observed the general condition of the areas to be tested and performed 1 density test for Lot 3
at 5206 Oakland Lake Cir. This test was performed in accordance with the ASTM D-6938 Nuclear Gauge Method and found
to meet the project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
BEARING CHECK
Technician also hand augered to a depth of 5' and no organic material was found.
The fill soils appear to be suitable granular materials without expansive clays and are in accordance with
the assumed building code soil conditions of 2,000 psf that the designer noted was used for design of the foundations.
r�
U.N.'l-VERSAL
.ENGINERING, 6CIEN"CES
'.Consultants Iri Geotechnical Engineering'•.Environmental•Sc'iences
6660.hysical Setvices'• MatdrialsTesting %Thtesh:old,lrispection
`Buildinkode Aaminlstra416n,'Cornpliance inspection & Plan Review
20 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
UES Project No: 0310.1700455.0000
UES DOCS No:
UES Report No: 66331-1 DT 101117
lient: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
roject: Oakland Lake Estates Subdivision House Lot Investigation
Oakland Lake Circle, Ft. Pierce, St. Lucie County, FL
Area Tested: Lot 3
of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 10/11/2017
Lab: ASTM D1557 Modified Proctor
echnician: Cliff Cherrnay
rements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlvinq soils below the tested depths.
Field Dry
Field
Test
Depth
Proctor
Density
Moisture
%
Comments
No.
Location of Test
Range
(inch)
(2)
(PCF)
%
Compaction
(3)
1 1
Lot 3
0-1 ft
12.00
7492
116.6
13.4
104
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
7424
115.0
12.0
This test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
r'
UNIVERSAL
ENGINEERING SCIENCES
I= Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Ins pectlon & Plan Review
820 Brevard Avenue,, Rockledge, FL 32966 - P: 321.638.0808 - F: 321.638.0978
UES Project No.: 0310.1700455.0000-
Date Typed: September 11, 2018
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401 FILE COPY
Project: Oakland Lake Estates Subdivision House Lot Investigation Lot 3
5206 Oakland Lake Circle, Ft. Pierce, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No.
Data
Type of Report
66331-1
10/11/2017
In -Place Density Test Report w/Activity Record
We hope this information
the undersioned.
Is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
Qf REVIEWED 0 REVIEWED AS NOTED
(] REVISE & RESUBMIT O REJECTED/ RESUBMIT
0 NOT REVIEWED ❑ FOR YOUR INFORMATION
Submittals are roviowed far conformance with design intent
and.genoral compliance with the Contract Documents only
Flotations Do Not Authorize Changes to Contract Sum.
Reviews, Comments and/or corrections does not relieve the
Contractor from compliance with the Contract Documents. The
Contractor' is responsible for confirming and correlating all
quantities, dimensions, tolerances, clearances, fabrication
processes, techniques and sequences of Ionstruc n
compatibility of materials and materials coordination hell
Mork with other trades and subcontractors, perfo ance of
work.in a safe.and satisfactory manner and for fu omphance
with the Contract Documents. t
[CC Email: jomcalll®nvdnacom; tridley®nvdnc.com
Richard E.
Hoaglin, P.E.
2018.09.11
17:19:12
04'00'
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 00000649
%CEeVs •. t1 ��
\.
�r
• o.48796
n •. �srATE of '
��//1J11iltttil%% Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and sealed by
Richard E Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verUled on any electronic
copies.
UNIVER L UES Project No: 0310.1700455.0000
UES DOCS No:
UES ReportNo: 66331-1 ARC 101117
ENGINEERING SCIENCES On -Site Time (hrs): 0.25
Consultants In: Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing • Threshold Inspection Travel Time (hrs): 0.26
E9 Building Code Administration, Compliance Inspection & Plan Review Total Time (hrs): 0.50
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Estates Subdivision House Lot Investigation
Oakland Lake Circle , Ft. Pierce, St. Lucie County, FL
Date of Activity: Wednesday, 11 October, 2017
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the
purpose of earthwork testing for Lot 3.
DENSITYTEST
While on site, the technician observed the general condition of the areas to be tested and performed 1 density test for Lot 3
at 5206 Oakland Lake Cir. This test was performed In accordance with the ASTM D-6938 Nuclear Gauge Method and found
to meet the project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
BEARING CHECK
Technician also hand augered to a depth of 5' and no organic material was found.
The fill solls appear to be suitable granular materials without expansive clays and are in accordance with
the assumed building code soil conditions of 2,000 psf that the designer noted was used for design of the foundations.
r
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32966 - P: 321.638.0808 - F: 321.638.0978
UES Project No: 0310.1700455.0000
UES DOCS No:
UES Report No: 66331-1 DT 101117
In -Place Density Test Report
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Estates Subdivision House Lot Investigation
Oakland Lake Circle, Ft. Pierce, St. Lucie County, FL
Area Tested: Lot 3
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 10/11/2017
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
onlv and do not address the condition of the underlvina soils below the tested depths.
Field Dry
Field
Test
Depth
Proctor
Density
Moisture
%
Comments
No.
Location of Test
Range
(inch)
(2)
(PCF)
%
Compaction
(3)
1
Lot 3
0-1 ft
12.00
7492
116.6
13.4
104
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
7424
115.0
12.0
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTM procedures.
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
t
UNIVE kSAL
ENGINEERINGSCIENCES
Consultantsln: Geotechnical Engineering • Environmental Sciences
Geophysical Services -Materials Testing'- Threshold Inspection
Building Code Administration, Compliance'Inspection & Plan Review
Brevard Avenue, Rockledge, FL 32966 - P: 321:638.0808 - F: 321.638.0978
UES Project No.: 0310.1700251.0024
Date Typed: September 06, 2018
SCANNED
BY
St. Luds CCU*
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE 7
Client: Ryan Homes . I
1450 Centrepark Blvd Suite 340 4ejrpl,rJ �
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 3
5206 Oakland Lake Circle, Fort Pierce, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No. Date IType of Report
100185-1 1 08/29/2018 In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate !to contact
the undersigned.
J�
Attachments (1)
Sincerely, e`
UniversaiIvEngine'ering Scien6bs, Inc.
Certifica'2 c4Av7thvization, No. 00000 49
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
ICC Email: cbugg@nvrinc.com; elibdhi@nvrinc.com; Imhoff, Bryan (BIMHOFF@nvrinc.com]; jomcalli@nvrinc.com; rofingar@nvrinc.com; sign/seal MAIL to
ryan homes at 1777 Willows Square, Vero Beach, FL 32966
Revised May 2015
UNIVERSAL
ENGINEERING .SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing Threshold Inspection
Building Code Administration, Compliance Inspection&Plan Review
820 Brevard Avenue, Rockledge, FL 32966 - P: 321.638.0808 - F;
r
UES Proje6sJr 0310.1700261.0024
UES DOCS No:
UES Report No: 100186-1 ARC 082918
On -Site Time (hrs): 1.00
Lab Time (hrs): 0.00
Travel Time (hrs): 1.00
Total Time (hrs): 2.00
321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 3
5206 Oakland Lake Circle, Fort Pierce, St. Lucie County, FL
Date of Activity: Wednesday, 29 August, 2018
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
UNIVERSAL LUES IES DOCS Noo: 0310.1700251.0024
ENGINEERING SCIENCES UESReport No: 100185-1 DT082918
Consultants In: Geotechnical Engineering � Environmental_ Sciences
Geophysical Services • Materials Testing-e Threshold. ln'spection
Building Code Ad ministration,.Compliance Inspection& Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 3
5206 Oakland Lake Circle, Fort Pierce, St. Lucie County, FL
Area Tested: House pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 08/29/2018
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
onlv and do not address the condition of the underivinq soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
N/W Test
0-1 ft
12.00
21143
112.3
11.2
98
A
2
N/E Test
0-1 ft
12.00
21143
114.4
11.7
99
A
3
S/E Test
0-1 ft
12.00
21143
112.2
11.5
98
A
4
1 S/W Test
0-1 ft
12.00
21143
111.0
1 12.2
97
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21143
115.0
12.0
This test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
�
U
a v SAL
Date Typed:
Sep emb0e 11, 20018
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
Brevard Avenue, Rockledge, FL 32966 - P: 321.638.0808 - F: 321.638.0978
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
lient: Ryan Homes fif1450
Centrepark Blvd Suite 3401
West Palm Beach, FL 33401
roject: Oakland Lake Estates Subdivision House Lot Investigation Lot 3
5206 Oakland Lake Circle, Ft. Pierce, St. Lucie County, FL
s requested, Universal Engineering Sciences, Inc. (LIES) representative(s) performed construction materials testing and/or
geld inspection services on the above project. Testing results and/or inspection observations are reported on the attached
heets. The contents of this package are summarized below:
Scope of Work
Work Order No.
Date
Type of Report
66331-1
10/11/2017
In -Place Density Test Report w/Activity Record
i
I We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
I
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Autho0zation No. 00000549
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
ICC Email: jomcalli@nvrinc.com; tridley@nvrinc.com
UES Project ),,pl0310.1700455.0000
UNI
Vt-k-SAL
UES ROCS No:
UES Report No: 66331-1 ARC 101117
ENGINEERING -SCIENCES On -Site Time (hrs): 0.25
Consultants: In: Geotechnical Engineering • linvironmental Sciences Lab Time (hrs): 0.00
Geophysical Services,-k IMateriafs,Tesiing i Thf.eshb.ld Inspection Travel Time (hrs): 0.26
Building.CodeAdministration;Compliancelnspection&Plan`Review Total Time (hrs): 0.50
820 Brevard Avenue, Rockledge, FL 32965 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Estates Subdivision House Lot Investigation
Oakland Lake Circle , Ft. Pierce, St. Lucie County, FL
Date of Activity: Wednesday, 11 October, 2017
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the
purpose of earthwork testing for Lot 3.
DENSITY TEST
While on site, the technician observed the general condition of the areas to be tested and performed 1 density test for Lot 3
at 5206.Oakland Lake Cir. This test was performed in accordance with the ASTM D-6938 Nuclear Gauge Method and found
to meet the project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
BEARING CHECK
Technician also hand augered to a depth of 5' and no organic material was found.
The fill soils appear to be suitable granular materials without expansive clays and are in accordance with
the assumed building code soil conditions of 2,000 psf that the designer noted was used for design of the foundations.
UN-IVEi S L
-ENGINEERING SCIENCES
Consultants In: Gedtechnical Engineering • Environmental, Sciences
Geophysical,Services •;Mater'ials Testing -iThreshold Inspection
Building Code Administration; Compliance. Inspection & Plan Review
20 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
UES Project No: 0310.1700455.0000
UES DOCS No:
UES Report No: 66331-1 DT 101117
I
In -Place Density Test Report
II lient: Ryan Homes
1450 Centrepark Blvd Suite 340
i West Palm Beach, FL 33401
roject: Oakland Lake Estates Subdivision House Lot Investigation
Oakland Lake Circle, Ft. Pierce, St. Lucie County, FL
Tested: Lot 3
�Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 10/11/2017
Lab: ASTM D1557 Modified Proctor
echnician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlying soils below the tested depths.
Field Dry Field
Test Depth Proctor Density Moisture % Comments
No. Location of Test Range (inch) (2) (PCF) % Compaction (3)
1 Lot 3 0-1 ft 12.00 7492 116.6 13.4 104 A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
7424
115.0
12.0
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTM procedun:s.
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.