HomeMy WebLinkAboutGENERATOR CONCRETE PAD1 2
I
AMERICAST GENERATOR CONCRETE PAD
` \ \ GENERATOR
H
PAD \ ��
THICKNESS
G'tH
ISOMETRIC VIEW
PAD DIMENSIONS: GENERATOR TABLE:
CONCRETE PAD GENERATOR
= GENERATOR UNIT BY
o SEPARATE SUBMITTAL
(SEE SCHEDULE FOR
MINIMUM WEIGHT '
REQUIRED)
�- 54"LENGTH }
PLAN VIEW
CONCRETE
ROAD MESH -
MAC100
GROUND
50"
54"
3" MIN s4" MIN
(ON -GRADE APPLICATIONS ONLY)
AMERICAST
wnvr Omer gagna Cam
'MADH IN AACMUCAI'
FED TAX A 20.8232762 LICENSE iIS99.10050151
nW Pdnetlu Ave. 'n PICW%FL 34982
Td. 772-971-102 Fmc 772�64050D
EmsiL• ule.QMerLyy,{ifrt.comar eh�.Indtt2001f�inMo,n
HVHZ OR NON-HVHZ
RISK
EXPOSURE (EXP)
RISK
EXPOSURE (EXP)
RISK
EXPOSURE (EXP)
COUNTY
I
C
I D,
II
C
D
III, IV
C
I D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
BROWARD
156 MPH
32.92 Psf
39.95 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
165 MPH
136.83 Psf
44.69 Psf
175 MPH
41.43 Psf
50.28 Psf
186 MPH
46.80 Psf
56.80 Psf
BRAND &MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
,
Generac 005871 & 005883
10 KW
25.00 "
48.00 "
29.00 "
387 Ibs
41.43 Psf
EXP C 175 MPH & 6156 MPH
Generac 005872 & 005884
14 KW
25.00 "
48.00 "
29.00 "
439 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00 "
48.00 "
29.00 "
513 Ibs
47.44 Psf
Generac 006721
16 KW
1 25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00 "
48.00 "
29.00 "
455 Ibs
47.44 Psf
Generac 005874 & 005886
17 KW
25.00 "
48.00 "
29.00 "
421 Ibs
47.44 Psf
Generac 005875 & 005887
20 KW
25.00 "
48.00 "
29.00 "
451 Ibs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00 "
48.00 "
29.00 "
516 Ibs
47.44 Psf
Generac 006551 & 006552
22 KW
25.00 "
48.00 "
29.00 "
526 Ibs
47.44 Psf
Kohler 14RES & 20RES
14-20 KW
26.00 "
48.00 "
29.00 "
500 Ibs
47.44 Psf
GE 40323GE & 40324GE
13 KW
35.00 "
39.40 "
39.00 "
540 Ibs
39.09 Psf
EXP C 170 MPH & D 156 MPH
GE 040382 15KW
15 KW
33.00 "
48.00':
30.50 "
484 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
GE 04037817KW
17 KW
33.00 "
48.00 "
30.50 "
484 Ibs
43.83 Psf
GE 40330GE & 40331GE
20 KW
33.00 "
48.00 "
30.50 "
600 Ibs
43.83 Psf
Briggs & Stratton 040243-0
10 KW
31.00 "
32.00 "
34.00 "
430 Ibs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
50.00 "
31.60 "
507lbs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Briggs & Stratton 040303-1
15 KW
33.75 "
49.00 "
31.60"
562 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75"
49.00 "
31.60 "
568 Ibs
44.00 Psf
Briggs & Stratton 040305-1
20 KW
33.7S "
49.00 "
31.60 "
570 Ibs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00 "
48.00 "
29.00 "
4061bs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 007038 & 007039
20 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 007042 & 7043
1 22 KW
25.00 "
48.00 "
29.00 "
466 Ibs
47.44 Psf
GENERATOR MOUNTING CONFIGURATION:
ANCHOR TO PAD SCHEDULE
SUBSTRATE
DESCRIPTION
CONCRETE:
(2)-3/8"0 TITEN HD
(6000 PSI
OR EQUIVALENT,
MIN.)
2-3/4" FULL EMBED
O CONCRETE, 3" MIN
EDGE DISTANCE, 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
NOTES:
1. ANCHOR QUANTITY PER LONG SIDE
2. EMBEDMENT AND EDGE DISTANCE
EXCLUDES FINISHES, IF
APPLICABLE.
3. ENSURE MINIMUM EDGE DISTANCE
AS NOTED IN ANCHOR SCHEDULE.
4. ENSURE MINIMUM SPACING TO
ANY ADJACENT ANCHORS.
5. FOLLOW MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO
INSTALL ANCHORS.
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
GENERATOR %e' SIMPSON TITEN HD,
GENERATOR ATTACHMENT BASE SEE ANCHOR SCHEDULE
OR SIMPSON A24 ANGLE BRACE 2"x3"x%" GALV. STEEL
W/ (4) #10 SS 316 SELF -DRILLING WASHER
SCREWS RUBBER VIBRATION PAD
_ TO GENERATOR
(SEE GENERATOR SPECS)
V THICK GALVANIZED
F GENERATOR WASHER& RUBBER
= (SEE CONCRETE PAD VIBRATION PAD CONCRETE PAD � M
f W SCHEDULE FOR 6,000 PSI n -
DIMENSIONS & WEIGHT LIGHTWEIGHT �I1
REQUIRED) CONCRETE PAD X CONCRETE MIX
6,000 PSI
4 LIGHTWEIGHT \ _ MASTERFIBER MAC 100
iCONCRETE MIX & ROAD -MESH
NOTES: FOAM CORE 211
+---32" WIDTH '-tENGTii , v
DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2".
2. X DISTANCE 3-FROM-UNIT-EOGE T0-CI TP
SIDE VIEW FRONT VIEW 3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS
ANCHOR REQUIREMENTS
VK L. BENNA0, P.E.
0046549
037U12018
' [GORDON M. fIIdATTISTO. P.E.
NOT CONTAIN AN ORIGINAL
SIGNATURE & ENGINEER SEAL
IF THERE IS A DIGITAL
tG1�)
�"'(i7 �7
SIGNATURE ON SHEET 1, THIS
GM
! _
SHEET IS PART OF A DIGITALLY
SIGNED FILE, SHALL REMAIN IN
DIGITAL FORMAT, &PRINTED
COPIES OF THIS DOCUMENT
ARE NOT CONSIDERED SIGNED
AND SEALED. IF THERE IS NO
WIND DESIGN REQUIREMENTS-
OR SHEETDOEONSHEETI
THISITAL
OR THIS SHEET DOES NOT
CONTAIN AN ENGINEER'S
ORIGINAL SIGNATURE & SEAL,
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
(2017))
THIS SHEET IS A COPY/DRAFT.
AT -GRADE SIGN METHOD
rrnnto
N
ULTIMATE DESIGN WIND SPEED Vult = 186 mph
U p
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
-1
Ou
RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A
fZ ® W m M i
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd=
LL ff1 w M m o w C)Ln
0.85
W� 2D-LjLA i'
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H = 77.56
W LL U) "x N �
W p ='
qh
Ce x
Z ��
Ib/ft2
c w W U X='s
FORCE COEFFICIENT Cf = 1.44
n QW l? � Q" W LULL
Q ow
WIND PRESSURE:
lJ<l
U
or m o gE z 0
l.-
P= qh G Cf = 56.80 Ib/ft2 (ASD)
N� W u
-w
W W O �
GENERAL NOTES
O LU t;; .Z-i
W a=W
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
/ O W w
/ k 0
SIXTH EDITION (2017).
n
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH
THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A
JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE.
N O N
SITE -SPECIFIC LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
IvJ Q z
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR EQUAL TO THE
O O. O
DESIGN PRESSURE "ASD" CAPACITY VALUES LISTED HEREIN FOR ANY
J
ASSEMBLY AS SHOWN.
W
.~-.
U
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
(/�
STATED HEREIN.
4. UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES HAVING EQUAL
v, Q LL Ln
O,
Y N=
ry
CLEARANCE. A MINIMUM DISTANCE FROM UNIT TO PAD EDGE IS SPECIFIED.
CALCULATIONS MADE USING LIGHTWEIGHT CONCRETE 125 PCF
�O' ILIS.
U u ti
W
W r,
of
U,VEGETATION,
6. THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE ALL
I��.�/l 2: W
O
GO x
STUMPS, ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
I..L J a
r, U) p
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
Q N
LU O- C
" z U
7. RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
N
M O
C) LL
VO' g (.D
Z
Y
8. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
< In
W
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
r, m
EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
a0
9. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS
SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al.
INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES
0
INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL
iL
FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
LU
^
N o
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM
DEVIATIONS OF THIS PLAN.
? r
10. WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
CI
o 0
0
RESPONSIBILITY OF THE INSTALLING CONTRACTOR. CONTRACTOR SHALL
�
13
Y
LL m
m
ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS
RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE
w z
PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
0
1 LL
LL
Z
O 0
0
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING
w F
0 o
CONTRACTOR.
O
g g
g
U
w
11. THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY
c� w ��zZZq o
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL
BE COORDINATED BY THE PERMITTING CONTRACTOR.
a o w
w o-
12. THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY SPECIFIC
w
a
a
-PROJECFSITF--MEORMATION-CONTAINED HEREIN IS BASED ON
uJ
Y
w
>
> c4 0
CONTRACTOR -SUPPLIED DATA AND NISI 1REMENTS=ENGINEERINGfX aS-
w
LL
g EO 1-=
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
o
_ °•E2
OR INACCURATE DATA OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO
ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY VARY
ui
z 0
-
a
'
COPYRIGHT ENGINEERING EXPRESS
SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN.
WORK SHALL BE FIELD VERIFIED BY OTHERS PRIOR TO CONSTRUCTION.-�
ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
_ REEVALUATE OUR WORK UPON DISCOVERY OF ANY INACCURATE
.
INFORMATION -PRIOR -TO, MODIFICATION OF EXISTING FIELD CONDITIONS
SCALE: NTS UNLESS NOTED
AND FABRICATION AND INSTALLATION OF MATERIALS.-ALTERATIONS-OR-
aF_
ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR
CERTIFICATION.
0
13. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS
OR AFFIRMATIONS ARE INTENDED.