HomeMy WebLinkAboutGENERATOR CONCRETE PADI
Alvi'-RICAST GENERATOR CONCREI t PAD
GENERATOR
I
PAD
THICKNESS
PAD DIMENSIONS:
CONCRETE PAD
GENERATOR -
= GENERATOR UNIT BY
o SEPARATE SUBMITTAL
3 (SEE SCHEDULE FOR
M MINIMUM WEIGHT
REQUIRED)
54" LENGTH
PLAN VIEW
CONCRETE PAD
ROAD MESH
ASTERFIBER 3" MIN
MAC10o __C 4" MIN
50"
54"
Ntt
I } -32" WIDTH
v
o SIDE VIEW
GENERATOR TABLE:
(ON -GRADE APPLICATIONS ONLY)
AMERI AST
5 9•mc&aaaba mm
-'MAD11INxmmu0A1•
FEDUXP20425170 LICIIrMN5991=0110
M Fde►'ao Ave. Pan PWM, PL 34982
T.I. 772-971-19M I- 7724644MR
Email: Igs%`G uuj9AcRatav ner eh•Aeedtt2101riaahooeen
I
RECEIVED
vwSI "1
� AUG 0 2 2018
�- i7`,, g11�
ST. Lucie County, Permitting
I
I
HVHZ OR NON-HVHZ
COUNTY
RISK
EXPOSURE EXP
RISK
EXPOSURE EXP
RISK.'
EXPOSURE EXP
I
C
I D
II
C
D
III, IV
C
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf 1170
MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
BROWARD
156 MPH
32.92 Psf
39.95 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
1 165 MPH
136.83 Psf
44.69 Psf 1175
MPH
41.43 Psf
50.28 Psf
186 MPH
46.80 Psf
56.80 Psf
BRAND &MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005883
10 KW
25.00 "
48.00 "
29.00 "
387 lbs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Generac 005872 & 005884
14 KW
25.00 "
48.00 "
29.00 "
439 lbs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00 "
48.00 "
29.00 "
513 lbs
47.44 Psf
Generac 006721
16 KW
25.00"
48.00"
29.00"
448 lbs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00"
48.00"
29.00 "
455 lbs
47.44 Psf
Generac 005874 & 005886
17 KW
25.00 "
48.00 "
29.00 "
421 lbs
47.44 Psf
Generac 005875 & 005887
20 KW
25.00 "
48.00 "
29.00 "
451 lbs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00 "
48.00 "
29.00 "
516 lbs-
47.44 Psf
Generac 006551 & 006552
22 KW
25.00 "
48.00 "
29.00 "
526 lbs
47.44 Psf
Kohler 14RES & 20RES
14-20 KW
26.00 "
48.00"
29.00"
500 lbs
47.44 Psf
GE 40323GE & 40324GE
13 KW
35.00 "
39.40 "
39.00 "
540 lbs
39.09 Psf
EXP C 170 MPH & D 156 MPH
GE04038215KW
15KW
33.00"
48.00"
30.50"
484lbs
43.83 Psf
EXP C 180 MPH & D 156 MPH
GE 04037817KW
17 KW
33.00 "
49.00 "
30.50 "
484 lbs
43.83 Psf
GE 40330GE & 40331GE
20 KW
33.00 "
48.00 "
30.50 "
600 lbs
43.83 Psf
Briggs & Stratton 040243-0
10 KW
31.00 "
32.00 "
34.00 "
430 lbs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
50.00 "
31.60 "
507 lbs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Briggs & Stratton 040303-1
15 KW
33.75 "
49.00 "
31.60 "
562 lbs
43.83 Psf
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75 "
49.00 "
31.60 "
568 lbs
44.00 Psf
Briggs & Stratton 040305-1
20 KW
33.75 "
49.00 "
31.60 "
570 lbs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00 "
48.0 "
29.00 "
406 lbs
47.44 Psf
EXP C 186 MFH & D 156 MPH
Generac 007038 & 007039
20 KW
25.00 "
48.00 "
29.00 "
448 lbs
47.44 Psf
Generac 007042 & 7043
22 KW 1
25.00"
48.00 "
29.00"
466 lbs
47.44 Psf
i
L
WIND DESIGN REQUIREMENTS-
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
(2017))
AT -GRADE SIGN METHOD
ULTIMATE DESIGN WIND SPEED Vult = 186 mph
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd=
0.85
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H qh = 77.56
Ib/ft2
FORCE COEFFICIENT Cf = 1.44
ANCHOR TO PAD SCHEDULE: WIND PRESSURE:
P = qh G Cf = 56.80 Ib/ft2 (ASD)
SUBSTRATE
DESCRIPTION
CONCRETE:
(2)-3/8"0 TITEN HD
(6000 PSI
OR EQUIVALENT,
MIN.)
2-3/4" FULL EMBED
O CONCRETE, 3" MIN
EDGE DISTANCE, 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
NOTES:
1.
ANCHOR QUANTITY PER LONG SIDE
2.
EMBEDMENT AND EDGE DISTANCE
-
EXCLUDES FINISHES, IF
APPLICABLE.
3.
ENSURE MINIMUM EDGE DISTANCE
AS NOTED IN ANCHOR SCHEDULE.
4.
ENSURE MINIMUM SPACING TO
ANY ADJACENT ANCHORS.
S.
FOLLOW MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO
INSTALL ANCHORS.
GENERATOR
ATTACHMENT BASE,
GENERATOR MOUNTING CONFIGURATION:
VARIES WITH MODEL
SEE GENERATOR SPECS
GENERATOR
V SIMPSON TITEN HD,
GENERATOR ATTACHMENT BASE
SEE ANCHOR SCHEDULE
OR SIMPSON A24 ANGLE BRACE
2"x3"x3/e" GALV. STEEL
W/ (4) #10 SS 316 SELF -DRILLING
WASHER
€
SCREWS
TO GENERATOR
RUBBER VIBRATION PAD
(SEE GENERATOR SPECS)
I
THICK GALVANIZED
WASHER& RUBBER
H GENE TOR
=
VIBRATION PAD
ZCONCRETEI -
(SEE CONCRETE PAD
-W
- - - OR
DIMENSIONS & WEIGHT
6 0 0 PSI
=
- - - --
-- LIGHTWEIGHT
REQUIRED)
CONCRETE PAD
- - NCR-
4"
6,000 PSI
LIGHTWEIGHT `
MASTERFIBER MAC 100
CONCRETE MIX
& ROAD MESH
2'
---
FOAM CORE
54" LENGTH
1. -y-i
Y-DISTANCE-DEPEND-ON GENERATOR BASE LENGTH, NO LESS THAN 2".
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
FRONT VIEW
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO
LESS THAN
ANCHOR REQUIREMENTS
GENERAL NOTES
'ANK L. B54
E# 0046NARDO, P.E.
03 u nn
018
lu 0EMS), NG P.E. APPEARS BaDW
UkRDON M. ATTISTO, P.E.
SIGNATURE ON SHEET 1, THIS
SHEET IS PART OF A DIGITALLY
SIGNED FILE, SHALL REMAIN IN
DIGITAL FORMAT, & PRINTED
COPIES OF THIS DOCUMENT
ARE NOT CONSIDERED SIGNED
AND SEALED. IF THERE IS NO
DIGITAL SIGNATURE ON SHEET 1
OR THIS SHEET DOES NOT
CONTAIN AN ENGINEER'S
ORIGINAL SIGNATURE & SEAL,
U
ID N
Z®
O
M
LL rj�nJ
W e yx
fn Q En O
Wfll
Ul I~i J W m
U�LL�ay-
ZLU
'�`z0-
0
zX�QLus
O=m"ZZof
a C?of
Ai
WW
OND wwu
UriW
,eo-
Lc -�(7
W
�Wa=
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
O LU w
SIXTH EDITION (2017).
. n
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH
THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A
JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE.
N ry
SITE SPECIFIC LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR.EQUAL TO THE
C)a 0
DESIGN PRESSURE "ASD" CAPACITY VALUES LISTED HEREIN FOR ANY
LU
ASSEMBLY AS SHOWN.
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
STATED HEREIN.
,� //��
V/ Q
U O
Z LU
Y
4. UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES HAVING EQUAL
LLco
Q O M
W
►.
N U)
CLEARANCE. A MINIMUM DISTANCE FROM UNIT TO PAD EDGE IS SPECIFIED.
S. CALCULATIONS MADE USING LIGHTWEIGHT CONCRETE 125 PCF
+-I
( ,
v U
M
.6 W
6. THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE ALL
1- 1 W n
w
co =
VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
J a
N N p
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
¢ N
W O. F_
M Z L)
7. RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
I,
C7
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
C O O ,
LL
Z
8. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY
L CD
Y cc
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
Ln
W
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
ti H on
EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
LU
f Q
9. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS
p
SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al.
"aJ
INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES
O
INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL
FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
W
m
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM
DEVIATIONS OF THIS PLAN.
Q
?
10. WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
o
o
RESPONSIBILITY OF THE INSTALLING CONTRACTOR. CONTRACTOR SHALL
12
ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS
mm
RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE
X
V
O J
LL
[0
LL
im
W
PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
i s N
W
2
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING
O O
O
o = coo t
CONTRACTOR.
11. THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY
O
g g
g ,
o
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
I-"
ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
agm q
INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL
BE COORDINATED BY THE PERMITTING CONTRACTOR.
F
12. THIS DOCUMENT IS GENERIC
u}
AND DOES NOT PERTAIN TO ANY SPECIFIC
PROJECT SITE. INFORMATIOWCONTAINED HEREIN IS BASED ON
CONTRACTOR -SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EXPRESS
ON
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
OR INACCURATE DATA OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO
K
z 0
-
o
c"
'
ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY VARY
COPYRIGHT ENGINEERING EXPRESS®
SYSGfIT£Y,'BITEMUSIl2EMATN-WITHINTHELIMITATIONS SPECIFIED HEREIN.
WORK SHALL BE FIELD VERIFIED BY OTHERS PRIbWTTtONSTRV --
ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
-
17-39 �-
REEVALUATE OUR WORK UPON DISCOVERY OF ANY INACCURATE
INFORMATION PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS
SCALE: NTS UNLESS
NOTED
AND FABRICATION AND INSTALLATION OF MATERIALS. ALTERATIONS OR
OF
,
ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR
CERTIFICATION.
13. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS
I�