GENERATOR
W I ry
AMERICAST GENERATOR CONCRETE PAD
PAD
THICKNESS
PpD LENGPN
ISOMETRIC VIEW
PAD DIMENSIONS: GENERATOR TABLE:.
CONCRETE PAD
GENERATOR -
I
= I GENERATOR UNIT BY
o SEPARATE SUBMITTAL
3 (SEE SCHEDULE FOR
M I MINIMUM WEIGHT
REQUIRED)
}-- 54" LENGTH
PLAN VIEW
CONCRETE PAD
ROAD MESH
MASTERFIBER 3" MIN
MAC100 -f4e MIN
GROUNDS ,, „ , „ , „,,, ,
50"
54"
SCANNED
t) BY
(ON -GRADE APPLICATIONS ONLY)
AMERICAST
=hflmcE,m ina wm
•NADIR IN ANMMC1A:'
FEDTAXp394252M2 LICENSEL+59R206f0163
sm P-Wow A- Pm Maros. FL 740p
Tal: 772-971-19M I= 7724644=9
Email; aal .ancrlcnN�.crm er eha.lexdfQtOlr�whe
HVHZ OR NON-HVHZ
COUNTY
RISK
EXPOSURE EXP
RISK
EXPOSURE EXP
RISK
I EXPOSURE EXP
C
I D
11
C
D
III, IV
C
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19'Psf
BROWARD
156 MPH
32.92 Psf
39.95 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
165 MPH
36.83 Psf
44.69 Psf
175 MPH
41.43 Psf
50.28 Psf
186 MPH
146.80 Psf
156.80 Psf
BRAND &MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005883
SO KW
25.00 "
48.00 "
29.00 "
387 Ibs .
41.43 Psf
EXP C 175 MPH & D 156 MPH
Generac 005872 & 005884
14 KW
25.00 "
48.00 "
29.00 "
439 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00 "
48.00 "
29.00 "
513 Ibs
47.44 Psf
Generac 006721
16 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00 "
48.00 "
29.00 "
455 Ibs
47.44 Psf
Generac 005874 & 005886
17 KW
25.00 "
48.00 "
29.00 "
421 Ibs
47.44 Psf
Generac 005875 & 005887
20 KW
25.00 "
48.00"
29.00 "
451 Ibs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00 "
48.00 "
29.00 "
516 Ibs
47.44 Psf
Generac 006551 & 006552
22 KW
25.00 "
48.00 "
29.00 "
526 Ibs
47.44 Psf
Kohler 14RES & 20RES
14-20 KW
26.00 "
48.00 "
29.00 "
500 Ibs
47.44 Psf
GE 40323GE & 40324GE
13 KW
35.00 "
39.40 "
39.00 "
540 Ibs
39.09 Psf
EXP C 170 MPH & D 156 MPH
GE 04038215KW
15 KW
33.00 "
48.00 "
30.50 "
484 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
GE 04037817KW
17 KW
33.00 "
48.00 "
30.50 "
484 Ibs
43.83 Psf
GE 40330GE & 40331GE
20 KW
33.00 "
48.00 "
30.50 "
600 Ibs
43.83 Psf
Briggs & Stratton 040243-0
10 KW
31.00 "
32.00 "
34.00 "
430 Ibs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
50.00 "
31.60 "
507 Ibs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Briggs & Stratton 040303-1
15 KW
33.75 "
49.00 "
31.60 "
5621bs
43.83 Psf
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75 "
49.00 "
31.60 "
568 Ibs
44.00 Psf
Briggs & Stratton 040305-1
20 KW
33.75"
49.00 "
31.60"
570 Ibs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00 "
48.00 "
29.00 "
406 lb!
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 007038 & 007039
20 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 007042 & 7043
22 KW
25.00 "
48.00"
29.00 "
466 Ibs
47.44 Psf
GENERATOR MOUNTING CONFIGURATION:
GENERATOR
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/ (4) #10 SS 316 SELF -DRILLING
SCREWS
T
I
-Q
(SEE.GENERATOR GENERATOR
S)
1kA
6 IC�`AL3fANIZEGENE-
WASHER& RUBBER
I
(SEE CONCRETE PAD
VIBRATION PAD
SCHEDULE FOR
DIMENSIONS & WEIGHT
REQUIRED)
CONCRETE PAD -
�
6,000 PSI
4
n
I LIGHTWEIGHT—
n
CONCRETE MIX
ANCHOR TO PAD SCHEDULE:
SUBSTRATE
DESCRIPTION
CONCRETE:
(2)-3/8"0 TITEN HD
(6000 PSI
- OR EQUIVALENT,
MIN.)
2-3/4" FULL EMBED
O CONCRETE, 3" MIN
EDGE DISTANCE; 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
NOTES:
1. ANCHOR QUANTITY PER LONG SIDE
2. EMBEDMENT AND EDGE DISTANCE
EXCLUDES FINISHES, IF
APPLICABLE.
3. ENSURE MINIMUM EDGE DISTANCE
AS NOTED IN ANCHOR SCHEDULE.
4. ENSURE MINIMUM SPACING TO
ANY ADJACENT ANCHORS.
S. FOLLOW MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO
INSTALL ANCHORS.
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
%" SIMPSON TITEN HD, -
SEE ANCHOR SCHEDULE
2"x3"x3/a" GALV. STEEL
WASHER
RUBBER VIBRATION PAD
CONCRETE PAD
6,000 PSI
LIGHTWEIGHT X
CONCRETE MIX
MASTERFIBER MAC 100
NOTES: FOAM CORE
2" WIDTH 54" LENGTH 1 Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2".
ISTANCL3TROM-UNFT-EDGE Tn rl ry
SIDE VIEW FRONT VIEW 3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
-�-ze--t
FRANK L. B NARDO, P.E.
PE# 004654
I
�il
03u `1,' 0.1.8
n I
RECEIVED
6OEO,D, '3 P.E. aPPELR`5 BMW
2328 N M. BAITISTO, F-
VALID FOR I FIERMI
NOTICE: IF THIS SHEET DOES
AUG)j n
U 23
NOT CONTAIN AN ORIGINAL
SIGNATURE & ENGINEER SEAL:
IF THERE IS A DIGITAL
- I
i
SIGNATURE ON SHEET 1, THIS
ST. Lucie County, Permitting
SHEET IS PART OF A DIGITALLY
SIGNED FILE, SHALL REMAIN IN
DIGITAL FORMAT, & PRINTED
COPIES OF THIS DOCUMENT
ARE NOT CONSIDERED SIGNED
I- _ __ _ _ _
AND SEALED. IF THERE IS NO
WIND DESIGN REQUIREMENTS_
DIGITAL SIGNATURE ON SHEETI
OR THIS SHEET DOES NOT
CONTAIN AN ENGINEER'S
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
(2017 ))
ORIGINAL SIGNATURE & SEAL,
THIS SHEET IS A COPY DRAFT.
AT -GRADE SIGN METHOD
rrnn
p fV
ULTIMATE DESIGN WIND SPEED Vult = 186 mph
U
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
Z �qT o
RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A
® W Cn , u i
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd=
a: w ►.- M ui OwU
CO
U LL cc w
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
GUST EFFECT
W 1L N X N
LV
FACTOR = 0.85 PRESSURE AT HEIGHT H qh = 77.56
O 2
Ib/ft2
¢ w UJ U "� X
~ > Q " w
FORCE COEFFICIENT Cf = 1.44
c� a � Q LLI L.0 LD
WIND PRESSURE
O
Orm'??Z H
P= qh G Cf = 56.80 Ib/ft2 (ASD)
11, N O A
W O W w
W 0'-1 W v@z
GENERAL NOTES
3 LL vtu"
U) U
O W 1U
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
.
to in
SIXTH EDITION (2017).
14
-
n
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH
THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A
JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE.
N O CD
SITE -SPECIFIC LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
d
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR EQUAL TO THE
O 0
DESIGN PRESSURE'ASD" CAPACITY VALUES LISTED HEREIN FOR ANY
ASSEMBLY AS SHOWN.U.
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
/ /�
LU
O O
STATED HEREIN.
4. UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES HAVING EQUAL
V 4 Q. U_ Ln
Q GI
Y H=
r4 F-
CLEARANCE. A MINIMUM DISTANCE FROM UNIT
O W
M
TO PAD EDGE IS SPECIFIED.
S. CALCULATIONS MADE USING LIGHTWEIGHT CONCRETE 125 PCF
/ � V
�.! .,�
of LLJ W U)
6. THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE ALL
[ -1 W f\
11.I
VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
rt-4 a CA
N En O
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
7. RESISTANCE
Q N
LU O_ �
P1 (,
O
TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
n
S M O
M U_
:5
J (D8.
ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY-
`.
Y
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
Lr)
LLI
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
.ni CO
EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
U)
W
9. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS
U. <
SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al.
INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES
O
INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL
LL
FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
B
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM
DEVIATIONS OF THIS PLAN.
10. WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
C1
RESPONSIBILITY OF THE INSTALLING CONTRACTOR, CONTRACTOR SHALL
0 z
o
m
w
LL m
m
ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS
RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE
rc x
PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
V
LL
LL ,
z w
6
Z
3
O O
O
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING
- � I I
CONTRACTOR.
p
S g
g ,
z
11. THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY
.q� �
�.� z
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
N
a $
ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
INTEGRITY
��++ w p
OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL
RES0913D_IN_AT_ ED_ B_Y THE PERMI.TRNG CONTRACTOR.
`12 m
- __
12. T - ERI - E�BT=PERTAIN TO ANv-c9Ft�rt7t=
C'Q
_
o
PROJECT SITE. INFORMATION CONTAINED HEREIN IS BASED ON
CONTRACTOR -SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EXPRESS
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
o
OR INACCURATE DATA OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO
z
N
ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY VARY
COPrtiIGHT ENGINEERING EXPRESS
SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN.
WORK SHALL BE FIELD VERIFIED BY OTHERS PRIOR TO CONSTRUCTION.
J-��� J1
--ENGEXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
REEVALUATE OUR WORK UPOWDISCOVERY-OF-ANYYNACCURATE
1INEERING
.
_
INFORMATION PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS
SCALE: NTS UNLESS NOTED
AND FABRICATION AND INSTALLATION OF MATERIALS. ALTERATIONS OR
of
ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR
CERTIFICATION.
13. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS
\ \ GENERATOR
_ \ I ' II
PAD �\
THICKNESS
�PPOI.EN'�
PAD DIMENSIONS: CONCRETE
GENERATOR
Fa
= GENERATOR UNIT BY
o SEPARATE SUBMITTAL
3 (SEE SCHEDULE FOR
M MINIMUM WEIGHT
REQUIRED)
54" LENGTH
PLAN VIEW
CONCRETE
ROAD MESH-
MAC100
GROUND -
50"
54"
32" WIDTH
3" MIN
4„
ISOMETRIC VIEW
4" MIN
F
AMERICAST GENERATOR- CONCRETE
GENERATOR TABLE:
(ON -GRADE APPLICATIONS ONLY)
AMA ST
'B ADR INI AMEMOA-
FEDTAXOZD4252362 LICENSa7599306i0113
9W;Wma0 Alv. Fen Dbm, FL 7067
T.I. 772-9714M F- 777J64-0SOD
EmdL-
HVHZ OR NON-HVHZ
COUNTY
RISK
EXPOSURE EXP
RISK
EXPOSURE EXP
RISK
EXPOSURE EXP
I
C
D
II
C
I D
III, IV
C
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
110 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
BROWARD
156 MPH
32.92 Psf
39.95 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
165 MPH
36.83 Psf
44.69 Psf
175 MPH
41.43 Psf1
50.28 Psf,
186 MPH
46.80 Psf
56.80 Psf
BRAND &MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005883
10 KW
25.00 "
48.00 "
29.00 "
387 Ibs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Generac 005872 & 005894
14 KW
25.00 "
48.00 "
29.00 "
439 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00 "
48.00 "
29.00 "
513 Ibs
47.44 Psf
Generac 006721
16 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00 "
48.00 "
29.00 "
455 Ibs
47.44 Psf
Generac 005874 & 005886
17 KW
25.00 "
48.00 "
29.00 "
421 Ibs
47.44 Psf
Generac 005875 & 005887
20 KW
25.60 "
48.00 "
29.00 "
451 Ibs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00"
48.00 "
29.00 "
516 Ibs
47.44 Psf
Generac 006551 & 006552
22 KW
25.00 "
48.00"
29:00 "
526 Ibs
47.44 Psf
Kohler 14RES & 20RES
14-20 KW
26.00 "
48.00 "
29.00 "
500 Ibs
47.44 Psf
GE 40323GE & 40324GE
13 KW
35.00 "
39.40 "
39.00 "
540 Ibs
39.09 Psf
EXP C 170 MPH & D 156 MPH
GE 04038215KW
15 KW
33.00 "
48.00 "
30.50 "
484 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
GE 04037817KW
17 KW
33.00 "
48.00 "
30.50 "
484 Ibs
43.83 Psf
GE 40330GE & 40331GE
20 KW
33.00 "
48.00 "
30.50 "
600 Ibs
43.83 Psf
Briggs & Stratton 040243-0
10 KW
31.00 "
32.00 "
34.00 "
430 Ibs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
50.00 "
31.60 "
507 Ibs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Briggs & Stratton 040303-1
15 KW
33.75 "
49.00 "
31.60 "
562 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75 "
49.00 "
31.60 "
568 Ibs
44.00 Psf
Briggs & Stratton 040305-1
20 KW
33.75 "
49.00 "
31.60 "
570 Ibs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00 "
48.00 "
29.00 "
M lbs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 007038 & 007039
20 KW
25.00 "
48.00-
29.00 "
448 Ibs
47.44 Psf
Generac 007042 & 7043
22 KW
25.00 "
4___'.
29.00 "
466 Ibs
47.44 Psf
GENERATOR MOUNTING CONFIGURATION:
(SEE CONCRETE PAD
SCHEDULE FOR
DIMENSIONS & WEIGHT
REQUIRED)
54" LENGTH
GENERATOR
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/ (4) #10 SS 316 SELF -DRILLING
SCREWS
TO GENERATOR
(SEE GENERATOR SPECS)
THICK GALVANIZED
PAD
i
kEGEIVED
AUG0;22018
I
ANCHOR TO PAD SCHEDULE
SUBSTRATE
DESCRIPTION
CONCRETE:
(2)-3/8"0 TITEN HD
(6000 PSI
OR EQUIVALENT,
MIN.)
2-3/4" FULL EMBED
O CONCRETE, 3" MIN
EDGE DISTANCE, 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
NOTES:
1. ANCHOR QUANTITY PER LONG SIDE
2. EMBEDMENT AND EDGE DISTANCE
EXCLUDES FINISHES, IF
APPLICABLE.
3. ENSURE MINIMUM EDGE DISTANCE
AS NOTED IN ANCHOR SCHEDULE.
4. ENSURE MINIMUM SPACING TO
ANY ADJACENT ANCHORS.
S. FOLLOW MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO
INSTALL ANCHORS.
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
3/D" SIMPSON TITEN HD,
SEE ANCHOR SCHEDULE
2"x3"x3/8' GALV. STEEL -
WASHER
RUBBER VIBRATION PAD -
6,000 PSI
LIGHTWEIGHT
CONCRETE PAD X CONCRETE MIX E 6,000 PSI `
LIGHTWEIGHT MASTERFIBER MAC 100 J
CONCRETE MIX & ROAD MESH C
NOTES: FOAM CORE
1. Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2".
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
-a
L. BERNARDO, P.E.
037JV,20 18
oa ED, :r. v.E, APKN;5,,OHDY!
DON M: IBI, TTISTO; P. E. '
i p rt
SIGNATURE ON SHEET 3, THIS
} 1 1,}�,._.��y
WOO. ���101�
SHEET IS PART OF A DIGITALLY
_
SIGNED FILE, SHALL REMAIN IN
DIGITAL FORMAT, & PRINTED
COPIES OF THIS DOCUMENT
ARE NOT CONSIDERED SIGNEI
L - - - - - - - - - - - - - - - - -
AND SEALED. IF THERE IS NO
WIND DESIGN REQUIREMENTS_
DIGITAL SIGNATURESHEET
H DOES
EST NOT
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
CONTAIN AN ENGINEER'S
(2017 ))
ORIGINAL SIGNATURE & SEAL,
THIS SHEET IS A COPY DRAFT.
AT -GRADE SIGN METHOD
rrnn
0 N
ULTIMATE DESIGN WIND SPEED Vult = 186 mph
U
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
Z .-) V
RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A
® IL fn 'n V f
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd=
a: )ii f- M 4 In 0
0.85
W O5JA-vim
LL
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR
LL U) �^ O. V) C,
W W
Lu
= 0.85 PRESSURE AT HEIGHT H qh = 77.56
O 2 �'�' x
Ib/ft2
FORCE
_Z w W U '-' z 0- In
COEFFICIENT Cf = 1.44
a <' Q W w L7 LLO
WIND PRESSURE
U g
Or m Q�Z
P= qh G Cf = 56.80 Ib/ft2 (ASD)
N 0� u
W W O W w
0 N
GENERAL NOTES
rnOz
W a=W
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
0 w w
10
SIXTH EDITION (2017).
n
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH
THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A
JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE.
SITE -SPECIFIC LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
0.
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR EQUAL TO THE
O 0
DESIGN PRESSURE "ASD" CAPACITY VALUES LISTED HEREIN FOR ANY
Lq
ASSEMBLY AS SHOWN.
oe
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
STATED HEREIN.
;
� U w
4. UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES HAVING EQUAL
Q LL Ln
Q O Ol
U!
Y ,Z., =
ry N It
CLEARANCE. A MINIMUM DISTANCE FROM UNIT TO PAD EDGE IS SPECIFIED.
5. CALCULATIONS MADE USING LIGHTWEIGHT CONCRETE 125 PCF
+•-�
( ,
V L
M F-
-
6. THE AREA UNDER CONCERETE SLAB ON GROUND
N
w uj
SHALL HAVE ALL
W
0
r,
VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
p'-',
U) 0
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
7. RESISTANCE
Q N
W O- H
M z U
O
TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
��
MO �
B. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED &INSTALLED BY
M
Y O
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
N
Lu
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
.^-1 m
EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
W N Q
-- 9. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS
<
SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al.
INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES
O
INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL
-1
u
FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
W
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM
DEVIATIONS OF THIS PLAN.
10. WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
G
RESPONSIBILITY OF THE INSTALLING CONTRACTOR. CONTRACTOR
o
S o
u'Sg a
. SHALL
• ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS
G
RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE
S U
9 111
1 o �g R '
PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
iU -
II. LL
z
�+ O
0 3
O O
3 3
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
WATER -TIGHTNESS SHALL.BE THE FULL RESPONSIBILITY OF THE INSTALLING
CONTRACTOR.
o €o q
Li
pZ
11. THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
$ ? o
ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
INTEGRITY OF ALL SUPPORTING SURFACES
a �"
TO THIS DESIGN WHICH SHALL
BE COORDINATED BY THE PERMITTING CONTRACTOR.
12. THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN SPECIFIC
w o
o z
TO ANY
- - -
y
�-
z o
kWEcT-.iFE=4NFORMATFON=C-0NTmNEQHEREIW4S:BASED-0 - - ----
CONTRACTOR -SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EXPRESS
�.
-
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
OR INACCURATE DATA OR MEASUREMENTS.
M 2
Lu
�
DIMENSIONS ARE SHOWN TO
z
0 N
'
ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY VARY
COPYRIGHT ENGINEERING EXPRESS
SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN.
WORK SHALL BE FIELD VERIFIED BY OTHERS PRIOR TO CONSTRUCTION.
ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
1 %-3961.1
REEVALUATE OUR WORK UPON DISCOVERY OF ANY INACCURATE
INF6RMATION-PRIORT6-MODIFICATION-OF-EXISTING-FIELD-CONDIRONS-
-SCAIFNTSUNCESSTJOTEO
AND FABRICATION AND INSTALLATION OF MATERIALS. ALTERATIONS OR
OP
ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR
CERTIFICATION.
13. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS
^
OR AFFIRMATIONS ARE INTENDED.