HomeMy WebLinkAboutFIRE PREVENTIONT)
BUILDING PLAN CHECK. LLJCie ,()op /
;,'-SST, �UCIE COUNTY- FORT PIERCE FIRE PREVENTION BUREAU
FORT PIERCE, FLORIDA
TELEPHONE 465-6655
i
i
i
PLAN NUMBER #1934
DATE RECEIVED 10-16-89
CONTRAC IOR: Haile -Dean Seed Co. PHONE, NUMBER: 461-8335
ARCHITEC J. A. Falsone PHONE NUMBER: 813-971-3030
OWNER:
HAILE-DEAN SEED CO.
LOCATION:' 4100 Glades Cut Off Rd
TYPE OF 'CCUPANCY: Mixed: Storage TYPE OF CONSTRUCTION: IV unprotected
Factory/Industrial
SIZE OF B ILDING: 12,000 Storage NUMBER OF FLOORS: 1 —
1. 3,074 Factory/Industrial
REQUIREMNTS:
1'. -Bag sA rage: empty new bags (paper) stored or handled in quantities in excess of 1000
cubic fleet shall be classified as hazardous materials and a three (3) hour separation
and fi'e protection such as an automatic sprinkler protection will be required. All
openin s shall be protected with Class "A" three (3),,,hour protective devices. _
2. Providl a 4A-40BC rated fire extinguisher for each 75' of travel distance of 1,000 square
feet of floor area.
3. If in he process, dust is accumulated or is blown into the atmosphere, the building
classification will have to be changed to hazardous and all the requirements for that
occupancy will nave to be met.
4. The wall separating the storage building from the processing building will require a
three (II;) hour separation and any opening or openings shall be protected with a Class
I "A" three (3) hour rated door assembly. This wall should be constructed of a material
REVIEWED
n the
construction.
CONTRACTORS RESPONSIBILITY TO NOTIFY BUREAU ON ALL INSPECTIONS
24 HOUR NOTICE REQUIRED ON ALL INSPECTIONS
DATE Cti
`r� SIGNA7 RE
BUILDING PLAN CHECK
LUCIE COUNTY- FORT PIERCE FIRE' PREVENTION BUREAU
FORT PIERCE, FLORIDA
i TELEPHONE 465-6655
'CONTRACTOR:
ARCHITE T:
OWNER:
LOCATIO II:
TYPE OF , CCUPANCY:
SIZE OF UILDING: —
REQUIRE ,II' ENTS:
PLAN NUMBER _
DATE RECEIVED -
PHONE NUMBER:
PHONE NUMBER:
TYPE OF CONSTRUCTION:
NUMBER OF FLOORS:
#1934
). lne W i1111
SePULUL.LLL6 LUC: jJLUI:Cbb.LLlr, ULL1J_LL 1LLr, t1 UUL L.aac
threej,(3)
hour separation and any opening shall be
protected with a Class "A" three (3)
hour
'a.ted door assembly.
i
F
c
REVIEWED'
CONTRACTORS RESPONSIBILITY TO NOTIFY
24 HOUR NOTICE REQUIRED ON
BY: --'�y'-' DATE
SIGNAT R
i
BUREAU ON ALL INSPECTIONS
ALL INSPECTIONS