HomeMy WebLinkAboutALUMINUM SCREEN DESIGNALUMINUMSCREEN DESIGN 3" C CHANNEL IS ATTACHED TO 3" INSULATED ROOF WITH (6) #1 1" PER
ROLL FORM GUTTER IS ATTACHED TO
3" INSULATED ROOF WITH #10 1" 6"
FROM ENDS 24" O.C. /
ROOF IS ATTACHED TO FRONT WALL
WITH (4) #14 4" PER PANEL
KICKER DETAIL
KNEE BRACE 2X3 45" MAX 25" MINRvIUM ON A 45 DEGREE
SCREWED INTO C CHANNEL WITH (3) #10 1" SMS ON EACH SIDE
PER END, C CHANNEL IS ATTACHED TO BEAM & POST WITH
(3) 910 1 " PER END
BRACKET FROM 3X3 IS ATTACHED
TO CONCRETE WITH 2 1/4" X 2"
ALU ENUMSCREENDESIGN.COM
ALUMNUMSCREENDESIGN
@YAHOO.COM
PHONE: 407-734-1470
FAX: 407-734-1790
ROLL FORM FASCIA IS ATTACHED TO
3" INSULATED ROOF WITH #10 1" 6"
FROM ENDS 24" O.C.
3X3 POSTS ARE ATTACHED
TO 2X6 BEAM 2 3/8" X 3 1/2"
3X3 POST IS ATTACHED TO
BRACKET WTTH (2) 3/8" X 3
1 /9 f l h A U T T A n r. "l T TO
DESIGN STATEMENT
METAL IS .046 THICKNESS OR GREATER, ALLOY IS 6005-T5
ALL TAPCONS SHALL PROVIDE MINIMUM OF 1 1/8" CONCRETE EMBEDMENT DEPTH
THIS STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE TO MEET THE REQUIREMENTS OF THE 2017 (6TH EDITION)
FLORIDA BUILDING CODE FOR OPEN AND SEMI -OPEN STRUCTURES AND SHALL WITH STAND ULTIMATE WIND SPEEDS OF 150 MPH
(FOR 3 SECOND GUSTS) NOMINAL SPEED 117 MPH UP TO A 15FT ROOF HEIGHT, FACTOR OF 1.0, AND EXPOSURE B, RISK CATEGORY 1.
CONTRACTOR SHALL FIELD VERIFY ALL PLANS DIMENSIONS PRIOR TO MATERIAL PURCHASE, FABRICATION AND CONSTRUCTION
CONTRACTOR SHALL NOTIFY THE ENGINEER IMIv1EDLATELY SHOULD SITE CONDITIONS DIFFER FROM CONSTRUCTION PLANS
3" C CHANNEL IS ATTACHED
THRU FASCIA INTO RAFTER
TAILS WI17 #10 2" 6" FROM
ENDS 24" O:G.
f"
MICHAEL Tl-10
4401 VINELAND ROAD
SUITE A6
ORL ?DO, FL 32811
P.E.'# 47509
CA#30930