HomeMy WebLinkAboutBUILDING PLANSElectrical Load Calculations 2118 Living S.F. at 3 VA 6354 watts Two 20 Amp Appliance Ckts. 3000 watts One Laundry Cir. @ 1500 watts 1500 watts One Range 8000 watts One Dishwasher & One Disposal @ 1500 watts each 3000 watts One Microwave @ 2000 watts 2000 watts One Water Heater @ 4.5 kw 4500 watts One Dryer @ 5 kw 5000 watts One Ref. @ 1500 watts 1500 watts Three Baths @ 1500 watts each 4500 watts Well Pump 2050 watts Water Softner 2500 watts Total 43,904 watts First 10 KVA at 100% 10,000 watts Remainder at 40% 13,562 watts Total 23,562 watts One AC Heat at 100% 10,000 watts Total 33,562 watts 32,562 W / 240 V =139.8 Amps Use 200A Service Smoke detectors wired to 120V Bathroom lights Non Switchable, Non GFI Electrical contractor to verify all equipment loads prior to start of construction. Electrical contractor to recalculate electrical schedule if loads are to be modified (3) #2/0 ('HW) copper and (1) #4 round (pTHW) copper in 2' galy. conduit Pane]:200 AM.C.B• 200Amp 1,o, 3W 40 Circuit Panel 120n40 Volt disc. 5/8" dia. x 10 (� long ground I od 3/4" copper water pipe Wall (3) #2/0 (THW) cc and (1) #4 ground copper in 2" galy. F.P.L. service 1 9'-7 13/64" 1L tie ground wire to footing rebar Electrical Riser Diagram 3 1/2" Door Casing is being installed throughout Provide wood backing at all TV Locations for Mounting (2) Phone Jacks (6) Telephone Jacks (6) Outside GFI Owner to confirm locations at Rough {k r— — — — — — Master Bdrm. I -I I I I I I I I Fan & Light I I I I I I - r T 1 1 I \11 pc in tc 1 1 Porch Great Room Fan & Light 1 y I / � I \ Dining r ;;? ­T_ 4t THESE PLANS AND ALL PROPOSED WORK I ARE SUBJECT TO ANY COIRRECTIONS REQUIRED BY FIELD INSPECTORS TIIR`T NIAY BE NECESSARY IN ORD2R TO \ COr0PLY WITH ALL APPLICABLE CODES, ELECTRICAL LEDGEND RECESSED LIGHT WITH LENS @ EXTERIOR & WET LOCATIONS SURFACE MOUNTED LIGHT FIXTURE F--- ��---� SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE UNDER CABINET FLUORESCENT FIXTURE RECESSED INCANDESCENT LIGHT FIXTURE WITH EXHAUST FAN ,Gi—(mil//J CEILING FAN O\v EXHAUST FAN OUTLET DOOR CHIMES bTHERMOSTAT SMOKE & CARBON MONOXIDE DETECTOR $ DUPLEX OUTLET -SWITCHED �+ TELEVISION $ DUPLEX OUTLET -Q TELEPHONE 220 V OUTLET _W SWITCH [] PUSH BUTTON _W THREE WAY SWITCH -to DIM1%1ER SWITCH NOTE: RECEPTACLES IN KITCHEN & BATH AREAS TO BE 46" A.F.F. ALL 120V SINGLE PHASE 15 & 20 AMP BRANCH CIRCUITS SUPPLYING OUTLETS THAT ARE NOT GFCI MUST BE AFCI. TAMPER PROOF RECEPTICALES MUST BE INSTALLED IN 120 VOLT, SINGLE PHASE 15 & 20 AMP BRANCH CIRCUITS / / 3W Fan & Light gill, FF V afl gfi I II _ I II Kit. I—� N M �+I � w rrp Z �..J oc N ct a� •� Q E� Q,� o � v 1 ------- gf------f------ Bly 6 mtr gfi Bdrm.2 µI' c9-223 [ \ U c1 E COUNTY BUILD REVIEWED FOR COMPLIANCE REVIEW BY DATE � - PLANS AID PERMIT MUST BE K SITE OR NO INSPECTIONS) W] Fan & Light AV � qp �ECE`�eo OePa�ty �t 1 1 / ve(mac,�nU4`e COO' I 3W , Office tt disc. (D FF___ r I Pump pc in VT (t attic gp r \ f----Ca---- I Water I \ wp Softer. I f I t GDO r A.C.0011d. disc. 16 SEER r Trane Unit 1 ri Garage \ E.P. Meter BE MADE O W U N � con � Q 1 U O U drawn S.I. checked s.l. date 6/26/18 scale as nmrd jab number 18034 sheet A-5 tierevso SEQ,o1010 t Pecnttd�0pepa Amer FIBERGLASS SHINGLES ON 30# ROOFING FELT OVER 5/8" C.D.X. PLYWI SEE CONNECTOR PRE ENG. WD. TRUSSES 24"c.c. ALUM, DRIP EDGE ON Ix2P.T.ON2x6 CEDARFASCIA-,, STUCCO SOFFIT - LEVEL RETURNS BY TRUSS MFG.J 0 12 R30 BATT INSULATION 1/2" D.W. 1 x 4 P.T. BOARD FIRESTOP (2) COURSE BOND 2' 0" REBAR FILLED WITH —H GROUT EACH COURSE PROVIDE "CASTCRETE" PRECAST LINTELS ABOVE ALL OPENINGS TWO COAT STUCCO FINISH - OVER CBS SIDES AND REAR HARDIE PLANK SIDING OVER 1 x 3 P.T. 16"o.c. FASTEN FURRING WITH 1 3/4" LONG PIN NAIL WITH .145 DIA. COVER WITH HOUSE WRAP ON FRONT ELEVATION GRADE 8x16x8C.M.U. WITH #5 VERT. DOWEL IN GROUT FILLED CELLS 1 x 2 P.T. FURRING 16"o.c. 3/4" INSULATION IiRD. ON C.B.S. AND 1 x 2 FURRING 16"o.c. 1/2" GYP. D.W. 1 x 4 P.T. LF-1 4' 0(i0# FIBERMDC CONC. OVER .006 VAPOR BARRIER ON CLEAN, COMPACTED, — — — — — — TERMITE TREATED FILL Typical Wall Section scale:3/4" = P-0" 2 x 4 16"c.c. with (2} top plate with 2 x 4 sill plate & d 1/2" cAx. pisyh and ext. fin pre eng. trusses wall section see typ• wall sect. for roof sheathing and gosh H3 with (8)10d at each truss truss brng. eave detail as per typ. wall section O 2 x 2 cunt. o cv 16d 8"c.c. see t .wall sect. for ext. 1/2" c.d.x. plywd. finish soffit, painted 5'-0" concealled flashing 2 x 4 stud at (4) corners, from (2) top plate to bottom cord of truss, (3) 16d at all framing intersections truss btm. cord Cupoula Detail OPTIONAL �c K 00 00 - o ------------------------ ------------------------ NFL 25 s.h. Egress L-4 E 10'-4" g 11'-8" I I I Bdrm. 3 Porch 10'-0" Ceiling lo'-0" Ceiling o0 L-9 i from FFE 0 0 0 ti I I I I I I I I 1 6080 (2) 26 s.h. L 3 L-6 Egress I 0 000 00 •• 0° = N El 0 0 ° H36 12080 SGD is s.h. 2680 2880 r----- 1�8 _1 4 „ „ 3 4 , „ 8 11 „ ElI 1 10'-0" iii-a" ; Master d 1 ° ° e 1 10'-0" Ceiling I 34 1/2 Frame & 12" Coffer Great Room Wall Below o ❑ 1 1 3/12 Vault Cing. 11 (Garbage ~ 1 I 1 Can 1 i ❑• Kit ' ' I 1 L-1 15'-9" 3'-4" 5'-11"1 16'-9" 3'-0" 8'-4"rod) " L---- -- ---J 11 dw O¢ f7 H36 LL- - Range & s.h. 3/12 Vault : Exh. Hood �O Ceiling 2680 2680 �0 1 ` * 10' 0" °O 10' o" Clrig. = Ref. = ___mil I __________J 0 N❑ ~ Cing. ° __ -, N .41 line 22.5 jx 36 1 2680 Access ; 1 M 2'_9" 2680 rn Pocket _ 4Wallll rn M Bdrm- 2 0 L-1 208 10' 0" Ceiling 25 s.h. H'34 I JC004 Egresss.h.44"Tall Dining 0 0 0 l. -------- L-4 r� Wall 3/12 Vault Cing. ❑ " T-5" 3'-0" T-5" 1 3'-0" 7'-4" 8 4 8 Y-5" 5' " 6'_4" " 4'-0" 8 10'-0" TE 0 Clag. L-3 2980 �' 10'-0" Pocket o 0 0• O O 0 p Tub o Cing. r� N N Unit In (2) 26 w �t 10 -0 El v 1 s.h. 7r Chtg. 10'-0" Ceiling " T-5" -5" 2680 2, vtr 0 0 • ❑ p from FFE O r d p ❑ Roll in ap ----- ------------- ------------ o ---- N ---- Shower L-1 • • o N rr LIP b Office p H34 s.h. 20' �� x 28 Non Structural (obi Fix Frame Beam 16" Deep 10'-0" Ceiling (3) placasses I ❑ L-2 r.a.g 1 X HB Typ 11 U 48" o'-o" " 2'-4" 2'-4" 2' " 5' 4" 5' 4' RI hisulatlon 50 g w.h. • N at Adj. Walls Pump 8 2'-4" 8 8 2 4 10 -8 4'-8 3'-5 3' 10" 12 -9" ° Ballard 8 r-----------, x • - o 3 1/2" Door Casing 36" Tall Alum. Guard Rail with Vert. 4"o.c max. with 4 x 4 Alum, i I I i c Attic Access 1 Attic with Ladder -- I `------- --J Water is beinginstalled Deco. Columns Softnr. throughout 1 i Provide Plywood Decking in Attic J I i � A GarageCD _El 10 N I 1 I -� i 10'-o" Ceiling 1 1 from FFE r`t A.C.Cond. 16 SEER 28'-8" 1 2 F-4" Trane Unit Floor Plan 8 20 ° 8 a.c. cond. on 4" 6 4 T-4" 6-4" cone, pad. Fasten scale: 1/4" = 1'-0" unit to concrete using die metal anchor flange by manufacturer with -, 25 s.h. L-4 25 s.h. EL -typical 1/4" x 3" tapcons (4) places 0 0 0 0 0 Proiect Data Project Name: Cannon residence Street Address: XXXX Dyer Road City: Port St. Lucie County: St. Lucie State: Florida Scope of Work New one level CBS single family residence Design Loads Roof Live Load: 20.0 p.s.f. Floor Live Load: 40.0 p.s.f. Wind Speed: 160 MPH Wind Importance Factor: 1.0 Building Category: II Wind Exposure: B Internal Pressure Coefficent: .18 Structure Designed: Enclosed Soil bearing capacity: 2000 p.s.f. Building Data Occupancy Type: Group R Construction Type: V Number of Stories: One Project Area: 2969 s.f. Building Code 2017 Florida Building Code: Residential 2014 National Electric Code NFPA 70 Area Tabulation Living 2118 Garage 472 Porch 264 Entry 115 Total 2969 Total Cubic Volume: 23,171 Climatic & Geo2ranhic DesiLin Criteria Weathering: Negligible Termite Area: Very Heavy Flame Spread Index & Smoke Developed Index Insulation Flame Spread: Not to exceed 25 Insulation Smoke Developed Index: Not to exceed 450 Wall Finishes: Not greater than 200 Ceiling Finishes: Not greater than 200 Ceramic Tile Shall be installed in accordance with ANSI A108.1, A108.4, A108.5 A108.6, A108.11, Al1&1, Al18.3, A136.1, & A137.1 Ceramic Tile Backer Board Material used as backers for wall the in tub & shower areas shall be Glass Mat gypsum backing panel, Fiber reinforced gypsum panels, Nonasbestos fiber cement backer board, or Nonasbestos Fiber mat reinforced cementitious backer units installed per manufacturers specs. Gypsum Board &Gypsum Panel Products Materials and accessories shall conform to ASTM C22, C475, C514, C1002 C1047, C1177, C1178, C1278, C1396 or C1568 and shall be installed in accordence with the provisions of Section R702.3.1 FBC. Adhesives for the installation gypsum board & Panel products shall conform to ASTM C557. Bottom Cord of Truss 0.00'�F plate yp. d.w. is 24"o.c. ad Grade �3.L sill plate base 1 Hard Coil 12"o.c. max. Concrete Foundation Interior Wall Section 2" dia. Galy Pipe Set ballard 12" from appliance Galy. (4) 1/4" x 2 1/4" Tapeons Galy. Cap Typical Cone. Foundation Bollard Detail scale: 1" = F-0" U O 24 w i--I W Z CJ Ln W w • rl �D •rI � � U CCi W ay Ull Q H 0 Poo w � � o ty O F� N U�z O� 00 N n/ M O w r„ cu W N � z W � � Q � W � � U � O t/1 U drawn s.l. checked s.l. date 6/26/18 scale as noted job number 18034 sheet A-1 2 0 50'-0" 15'-0" 35'-0" 4'-9" 6-10" 3'-5" 22'-0" 13'-0" 9'-8" 4'-10" 4'-Y 3'-11" ❑ a IUD F-1 .. F-1 10 ° F-1 - - - - - - -------- ------- -----1 I I 1 I 5'-6" 12'-4" F-5100 I 1 0I r. F-lI I I r, - 11'-1 I _ I I I I t7 I ] 1 0 0 0 00o ao 00 0 l F-1 F-5 F-5 o --------- -------------- -_ ------l— Recess 7 for Sl. Gl. Dr.- 1 W'-2" CD � I I � I 1 21 F-11 I I G F:J] I 4" 3000# FIBERMIX CONC. I ,� OVER .006 VAPOR BARRIER ON CLEAN, COMPACTED, I 1 TERMITE TREATED FILL O # ASSUMED F.F.E. 0.00 I _ I F-100 . 00 ih C cn a ; I 0o I 5' 1" 11'-10" h `i s I o 7 1 r' rlI -- � I I o F-5-Ell 1 0 00- L— — — — — — — - F-11 1 F-5 I I I I I C)_-------J D I o t7 O t7 F -5 MOM I o I I I I I F-5 I F-51 - f-1 f-5 ; I I N o o o ' I I = - o r I F-1 Rollin -- ------ F-) I I o Shower L - F-4 - J q I o 3'-2" 2'-4" 3'-2" 15" 7'-10" 1'-7" - 2'_4„ 8'-8° 2'-4" 10'-8" 4'-8" I I L--- — — — — — — — — — — — — — — --------I �o �o F- i 48' o F� 2 r. 8 1 I I I I I o 14" I 4"2500# c I I conc. pad -4. 1 0 Slope for We 2" I Garage Dr. w N I _ I Fit I I Foundation & Footing Plan S I ')0,_0„ I scale: 1/4" = F-O" I 4-5" 3'-10" 3'-6" 3'-10" 4'-5"RT I • I I - F12 -------- -F-2 - -- ----� No F-1 F-2 F-5 18" x 16" mono. footing 18" x 16" mono. footing with (2) #5 rebar Cont. with (2) #5 mbar cunt. and curb 18" x 16" mono. footing with (2) #5 rebar cont. 8 4" to 6" ---- 4„ 16" 4" 4., 16" 8„ 18" 18" 18" MONO. EDGE FOOTING CURB FOOTING INTERIOR STEP FOOTING AT GARAGE F-3 F-4 8" x 8" mono. footing Recess 4" at Shower with (1) #5 rebar cont. 8" 4„ 4, 4" 4" ' H" 16" 18" TYP. SHOWER THICKENED EDGE RECESS GENERAL FOUNDATION NOTES Concrete shall be a minimum of 4" thick over clean, compacted, termite treated fill and 6 mil polyethylene vapor barrier. If concrete slab contains 6" x 6" 10/10 W WM provide 1" coverage Concrete shall have at minimum compressive strength of not less than 3,000 p.s.i. AU 90% hooks are to be extended 10" minimum beyond the turn. Field bends are to be done cold and the diameter of the bend, measured on the inside of the bar, is not to be less than six bar diameters. Minimum coverage for rebar shall be 3" in footin$,s and 1 1/2" in bond beams. Hooks may be rotated horizonitally if required to achieve minimum coverages. Rebar overlap shall be 48 bar diameters. 30" for #5 rebar The foundation design assumes that the soil has a minimum load carrying capacity of 2000 p.s.f. In the event the soil bearing capacity falls below 2000 p.s.f. This foundation plan may be superceded by Foundation Design Engineer. Satisfactory compaction test of fill does not verify lower soils are adequate. All specifications and dimensions to be verified by contractor. All exterior slabs shall slope a minimum 1/8" per foot for drainage 2" v.t.r. I I 1 I I 2" v.t.r. 1 1/2: a ! 4" ,. 4" i�� ~ewer C stem SHWR. W.C. LA T l is Plumbing contractor to provide a water hammer & shut off valve at each fixture Insulate all hot wafer lines Plumbing Riser Diagram FORMWORK & SHORING No structural concrete shall be stripped until it has reached at least 80% of the 28 day design strength. Design, Erection, & Removal of all formwork, shores, & reshores shall meet meet the ACI Standards 347 and 301 Contractor to verify all building setbacks prior to the start of construction. A formboard survey shall be submitted to the building department for approval prior to pouring concrete. SOIL STATEMENT: Foundation has been designed for a soil bearing capacity of 2000 p.s.i. Fill shall be laid in layers of 6". Each layer to be compacted to 95% compaction. If the contractor encounters, while digging the foundation, any discrepancy to suggest the soil may be inadecuate, he must immediately- report it to the owner and the Architect or Engineer so as to order a soil boring test. Dowel Rod Repair Note In the event vertical steel has been omitted from the down pour locations, drill 5" into concrete (no closer than 3 3/4" from edges and 5" from ends of cap walls) Remove dust per manufacturers instructions and use Two part TO" to anchor the #5 rebar in place. Use either "Hilts C-100" or Simpson Epoxy -Tie. PLUMBING NOTES: Plumber to consult with contractor and equipment ordered for rough in dimensions. Verify all dimensions with the floor plan. The floor plan dimensions dictates all other dimensions on other sheets. Do not scale drawings, if any conflicts arise, contact the Architect or Engineer for clarification prior to construction. All sanitary lines 2" or less shall have a slope of 1/4" per foot Minimum. r. rIL� COPY All sanitary lines above 2" shall have a slope of 1/8" per foot minimum. Provide Anti -Scalding Valve in all showers. Lowest living area floor elevation (refered as 0.00') to be set by a professional land surveyor to the required building department elevation, but not less than 18" above the crown of the road. U I N 00 M C) W J z C7 °; w • w r v1 A w N •� � 6 U H -C: $ z A o W A 7.4 > Q� O let ct r� E- W �U�ZN r1I 00 M x O W � U •� •b _ 1 z A � � C W � � U O rn U drawn s.l. checked 0. date 6W18 scale as noted job number 18034 sheet A-2 Roof Wind Zones Gross pressures are for windows, doors, framing, roofing, and other building components and cladding. Roof Zones: 1 thru 3 Wall Zones: 4 and 5 Rear Elevation scale: 1/4" = 1'-0" Wind Zones -Walls Right scale: 1/4" = 1 Left scale. 1 W ■ 0 1+0 M.42.1 Hardie Plank 6" x 2" Smooth Stucco Elevation Siding /% Bands at corners and Two Coat Stucco Finish over CBS levation 1'-0" I4+38.7 +38.7 21 42.1 Optional i U — ►� � Optional p � w � a oc N � n � -- z o W U rC� V Q M•�1 � O Two Coat Stucco Finish over CBS M T� v L 7t ct ctW�Z; ✓' 4 � N U�z� - -- c Q 00 n/ M El +38.7 r®�®®®® +38.7 +38.7 ®0®®®® O -50.5 42.1 ry U t 20.4 W �" 22.7 U 7� Q � U Hardie Plank F I L E C 0 Py" Siding 6" x 2" Smooth Stucco U Bands Typical at corners, windows, doors and Freize Bands along Soffit I' �� �� ■ � � I Ill ® � ■ I ■ � ... = ... ,_.. _ _ ��� ��� _ ■ MEN] ® • I,I ���l�lil,li'Il� I I illl : ■ fill ".� 1 ■ ■ ® 1 III I�Illllll�llllllilillll IIIIII IIIIIIIIIIII IIIIII�i��■ ■ Front Elevation scale: 1/4" = 1'-0" drawn sJ. checked s,1. date 6/26/18 scale as noted job number 18034 sheet A-3 `J STRUCTURAL NOTES: All reinforcing steel shall be high strength billet steel and shall conform to ASTM A-615 grade 60 specifications. Lap continuous reinforcing 48 bar diameters or 30" in beams and in slabs. Lap bottom steel over supports and top steel at midspan. Hook discontinuous ends of all top bars. Reinforcing steel shall have a minimum of 1" concrete cover, or as follows: BOTTOM TOP SIDES Beams: 11/2" 11/2" 11/2" Slab on Grade: 1 1/2" 1" _ Structural Poured: 3/4" 3/4" Poured Walls: _ _ 3/4' Slabs exposed to the weather 3/4" 1" _ Reinforcing steel shall be detailed and fabricated in accordance with the "Manual of Standard Practice of Detailing Reinforcing Concrete Structures" and the current "ACI Building Code 318' All structural steel shall conform to current ASTM Specification A-36 All wood in contact with masonry shall be pressure treated or approved seperating material. All dimensions shall be verified in field by the contractor. If there are any discrepancies the Architect or Engineer shall be notified before proceeding. No slump over 5" shall be permitted for any structural concrete without the Architect or Engineer approval. All Design and Construction shall be inaccordance with the current American Concrete Institute (ACI). and the American Institute of Steel Construction (AISC), The Florida Building Code and all applicable local codes. Structural Concrete shall attain a minimum ultimate compressive strength (Fe') in 28 days as follows: Column Footing and Wall Footing: 3000 .s.i. Column and walls from foundation to roof see column schedule. All other concrete: 3000 p.s.i. Footing sizes and reinforcing are based on allowable soil bearing capacity of 2000 p.s.i. All footings shall bear in virgin soil. If this is not the case, the Architect or Engineer shall be notified before proceeding with the work. Timber (Heavy Timber Construction) (a) Truss manufacturer shall submit a signed and sealed shop drawings by a registered Engineer. (b) Wood rafters to have a Stress Grade of Fb 1200 p.s.i. (c) Roof members should be secured to the beams or other structural components with hurricane anchors for wind uplift. All wood members shall have a minimum fiber stress in bending of 1200 p.s.i. with 1/360 max. deflection. All bolted connections shall be 1/2" Cadmium plated or better. Lag bolts to be used only in shear connections with minimum 4' threaded penetration past steel plate. Lag bolted conditions shall be drill tapped no larger than the internal thread diameter and shall not be hammer driven. Under Girder Trusses provide equal number of studs as girder plys at frame bearing locations GENERAL REQUIREMENTS All work to be as per the current edition of the Florida Building Code and meet or exceed all applicable local requirements. General contractor is responsible for all labor, materials, utilities, testing, waste removal, storage, securing of site, accomodation, transport/freight, and all other cost related to the completion of this project., unless explicitly identified here. Owner is responsible for all municipal related charges such as impact fees, and water connection, except building permit fees, which are to be included in the construction bid. General contractor to check all drawings for errors and ommissions and bring them to the attention of the architect prior to starting any work, or ordering any materials of the respective division of work. If such errors and ommissions are not reported in writingto the architect, any resulting damages or costs shall be born entirely by the general contractor. Architect is not responsible for the contractors method or means of construction. General contractor is to keep the site in a clean and safe state through out the course of construction. On building turnover, general contractor to clean all surfaces so as to be free of dust, grease, stains, scuffs, etc. Unless otherwise noted, the installation of specified hardware shall conform to the manufacturers instructions and standard practice. All plans and drawings are not considered complete until they have been reviewed and approved by the St. Lucie County Building Department and the building permit has been issued. EXTERIOR CEILING & SOFFIT NOTE 7/8" Stucco finish over 3/8" high ribbed galv. wire lath fastened to framing members with No. 11 guage nails with 1 3/4" embed. with 3/8" dia. head 6"o.c. max. edges to be tied and nailed at 9"o.c. Install one layer of 15# felt to framing prior to installing ribbed lath INTERIOR WALL FRAMING NOTE Interior non bearing walls to be 2 x 4 studs 24"o.c. Spruce, Pine, Fir (SPF) #3 Grade lumber or better or metal studs (25 Ga.) Crimper may be used in lieu of screws. GENERAL ROOFING NOTES Roofing to be composed of and attached to pre manufactured wood trusses as follows: Felt underlayment (min. ASTM 0 226 Type B) with 4" min. side and end laps, fasten with coorosion resistant annular ring shank nails at 6"o.c. in laps and in stag ered rows spaced 12"o.c. in field. If roof pitch is < 4/12 install (2) layers 15# felt. If roof pitch is 4/12 or greater, install (1) layer 30# felt. 5/8" cAx. sheathing or equal installed with staggered joints & GI clips, nailed to trusses with 8d corrosion resistant annular ring shank nails spaced max. 6"o.c. throughout, except max. 4"o.c. at gable ends. All roof trusses are to be pre -manufactured assemblies provided by a licensed wood truss fabricator with seperate drawings and data prepared for actual project conditions by a Florida registered professional engineer certified for truss design. Any deviation from the proposed plans as shown regarding placement or bearing shall be brought to the attention of the truss engineer prior to fabrication of the trusses, The truss manufacturer's car ' lied layout shall govern after fabrication. The handling, erection, and fixing of wood trusses shall be in accordance with the specifications contained on the certified mfgr's drawings and data. All engineered headers and truss hangers to be provided by the truss manufacturer. Splitting or cracking of structural components due to installation of hardware is not permitted. Unless otherwise noted, the installation of specified hardware shall conform to the truss manufacturers installation instructions and standard practice. BUCK ATTACHMENT NOTES AT DOORS USE P.T. PINE OR SPRUCE AND ATTACH TO BLOCK WITH 1/4" DIA. TAPCONS INTO C.S.S. SET AT 6" FROM CORNERS AND AT 12"o.c. MAX. AT WINDOWS USE P.T. PINE OR SPRUCE AND ATTACH BUCKS TO BLOCK WITH 8d CASED HARD COIL NAILS OR "T" NAILS" 4" FROM ENDS AND 12"o.c. USE WOOD SHIMS MINIMUM DURING DOOR INSTALLATION SHEATHING NAILING NOTES Nailing Pattern Zone 1: 8d at 6"o.c. Geld & 4"o.c. edges Zone 2: 8d at 4"o.c. edges & field Zone 3: 8d at 4"o.c. edges & field Pneumatic Nails Pneumatic or:mechanical driven nails will be accepted under the following conditions: Min. nails size 8d or largger ring shank with Min. shank diameter:.I 3 Min. Length: 2" Min. Head Diameter:.280 Full Round Min. Ring Diameter .012 over shank dia. Min. 16 to 20 Rings per Inch Note Gun nails shal bejiermitted as an acceptable fastenex from any manufacturer Wood screws meeting the same size requirement may be used in lieu of nails without comment Nailing Schedule ROOF & FL(kOR DIAGRAM Use sheathing with #8 gun nails at 6"o.c at supported panel edges and #8 gun nails at 6"o.c. at intermediate supports. ROOF SHEATHING TO GABLE END FRAME Use #8 gun nails at 4"o.c. EXTERIOR SHEATHING Use #8 gun nails at 4"o.c. at panel edges and #8 gun nails at 4"o.c. at panel top and bottom and 6"o.c. in field THRESHOLD NOTE At egress door (see floor plan) the max. hgth. of the threshold shall be 1/2" S" x 16" C.M.U. WITH CELLS FILLED WITH GROUT & (1) #5 VERT. E :. DOWEL P.T. 2 x 6 AT (3) SIDES OF OPENING, FASTEN TO BLOCK A5 NOTED. j DOOR SIDES I I i 1/2" x 6" REDHEADS WITH MIN. 2" x 1/8" WASHER 12" FROM ENDS AND 16"o.c. MAX. I � y DOOR HEAD 1/4" x 2 3/4" TAPCONS STAGGERED 24"o.c. Garage Door Buck Detail Connector Schedule Truss Bearing Truss Connector Qnty. Connector Fasteners Point Uplift ID Uplift 1 2472 (1) 5/8" ATR with 12" min. A01 MGT 1 39654 embedment and (22) 1Oil 13 3134 PLY to girder. Drill and epoxy ATR in bond beam. B08 17 1166 RETA16 1 1810# (10) 10d x 1 1/2" S 1152 HY COl 5 1764 HHETAI6 1 22350 (10) 10d x 1 1/2" 2 986 HETA16 1 1810# (10) 1Od x 1 1/2" Ply 2 299 HEFA16 1 1810# (10)1Od x.11/2" C04 t3 1848 HHETAI6 1 2235# (10) 10d x 1 1/2" 1 Ply 8 798 HETA16 1 1810# (10) 10d x 1 1/2" 8 2477 (1) 5/8" ATR with 12" min. DOl MGT 1 3965# embedment and (22) 1Od 2 2161 !,Ply to girder. Drill and epoxy ATR in bond beam. FGl 6 1469 HHETAI6 1 2235# (10) 10d x 1 W" Ply 4 1007 HETA16 1 1810# (10) 10dx 1 1/2" Alother tr sses ALL <1000 MTS18 1 1000# (14) 10d x 1 1/2" to rrarne A other In sses ALL <1810 HETA20 1 1810# (9) 1Oil x 1 1/2" to CBS Supporting (4) lOd alley Framing <250# VTCR 1 370# Valley (3) I Oil x 1 1/2" T asses Truss Notes: Do not substitute connectors Do not sheath trusses before all straps are in place Ati ach valley trusses and piggy back trusses, if present, to inain trusses per truss manufacturer drawing. Tri iss to truss connection by truss company, installed pei manufacturers specs. La oral forces perpendicular and parallel to wall has been considered ,(less than 300 p.l.f.) Co itractor to approve temporary bracing to prevent toppling of russes, see HIB-9. Oter specs, if different from above, have priority. A. .R. = All Treaded Rod D 11 and Epoxy Set all A.T.R. Us either "Hilti" C-100 or Simpson Epoxy Tie Epoxy q 4i 3/8" contim caulk (back buck to Drei is bead of dding) behind It liquid passage set flange i4 continuous bead of caulk across the entire face dif buck -. CBS Min. 1 1/4" embedment a at windows and min. o a ° : 1 1/2" embedment at ',• ° d sl. gl. doors Cal O° a E o e U L y ° b° ` 1/2" drywall A ro= c I / tucco finish / pe imeter caulk At ch .t. bucks wi 8dpcoil nails at 12' o.c. Typ. Alum. window. jamb or sliding glass doorjamb 1/4" max. struct. shim caulk attach as per manufacturers product approvals 'E: Method of attachment and Gunable sealants shall comply with rproofmg procedures are the ASTM C 920 Class 25 grade or at poured concrete sill. greater for proper joint expansion and contraction Bucks with DryLock Waterproofing they have been installed and Chaulked nrinxx/ Qu T7nnr MAchinrr n,-tnil At ('RC Wall Buck Attachment Method comer bars at beam (outside only) (2) comer bars at footing (min.) - Vert. dowel lapped with wall reinforcing, all laps 25" (min.) in grout filled cell 0 J9 all corner bars to be the same size, number, and spacing as horizontial bars in footing, beams, and walls Corner Reinforcing Detail 2 x 4 bottom cord bracing 10'-0" Safe Load Table Notes 1. All values based on minimum 4" nominal bearing. Exception: Safe loads for unfilled U lintels must be reduced by 20% if bearing length is less than 6 1/2". 2. N.R. = Not Rated 3. Safe loads are superimposed allowable loads. 4. One #7 rebar may be substituted for two #5 rebar in 8 inch U lintels onl . Y 5. All safe loads in units of pounds per linier foot 6. All safe loads are based on simply supported span. 7. Safe load ratings based on rational design analysis per ACI 318 and ACI 530. &1 batom qubn ombar r r¢NlinM Ciro witla, a! �F fiIIW Bme I aviry iaI� WIIII S 16-1B/1T c� 5/8' »s �a.¢��m �minali �a s°W'� ofhoed candy kj t, Lintel Type Designation Cast Crete Lintel Schedule Installation Notes 1. Installation of U lintels must comply with architectural and/or structural drawings. 2. U lintels can be field cut to the required length. 3. Cast in place concrete may be provided in composite U lintel in lieu of concrete masonry units. 4. The exterior surface of U lintels installed in exterior concrete masonry walls shall have a coating of stucco applied in accordance with ASTM C-926 or other approved coating. 5. Concrete masonry units used in composite U lintel shall be laid in a running bond. 6. Shore composite lintels as required. 7. U lintels are manufactured with a 5 1/2" long notch at both ends to accomodate vertical cell reinforcing and grout. Composite U Lintel Materials 1. Grout per ASTM C476 fg=3000 psi with maximum 3/8 inch aggregate and 8 to 11 inch slump. 2. Rebar per ASTM A615 Grade 60 3. Concrete masonry units (CMU) per ASTM C90 with minimum net area compressive strength = 1900 psi 4. Mortar per ASTM C270 Type M or S All Rebar to be#5 Grade 60 min. MARK LENGTH OF LINTEL ALLOWABLE GRAVITY LOAD APPLIED GRAVITY LOAD ALLOWABLE UPLIFT LOAD APPLIED UPLIFT LOAD BEAM SPECS. L-1 3'-8" 8974 550 4853 358 8F24-1B/lT L-2 T-4" 8974 125 5591 150 8F24-lB/lT L-3 T-6" 3486 911 2084 775 8F24-113/1T L4 4'-6" 8672 2081 4292 2161 8F24-1B/1T L-5 4'-8" 8060 1062 3277 483 8RF22-lB/lT L-6 13'-8" 1697 710 1434 598 8F24-1B/2T L-7 17-4" 1849 607 1268 697 8F30-lB/lT L 8 11'-0" 1366 200 798 80 8F16-1B/1T 119 12'-8" 1075 700 770 170 8F16-1B/2T Mim. Beam depths shown, beams may be increased without comment At Lintels over 24" deep provide (1) #3 vertical rebar at 24"o.c. along length of lintel Alum. window frame -� 3/8" continuous bead of caulk (back bedding)behind . shim to prevent liquid passage 1/4" struct. shim set flange in continuous bead of caulk across the entire face of buck perimeter caulk stucco finish `Bottom Cord Lateral Bracing Gunable sealants shall comply with ASTM C 920 Class 25 grade or v. ° greater for proper joint expansion and contraction precast FILE COPY cone. sill corrosive resistant Tapcon concrete srews installed as specified in window manufacturers product approval window sill Typical Precast Cone. Sill Detail PRODUCT APPROVAL Approval Product Model Number Manufacturer Glass Attachment Method Building Rated Product Rated Number Type Design Pressures Design Pressures S.H. Windows Head: 3" max. from comers & 1 at center. Jambs: ( ) U-Factor: 0.55 185 SH MI Windows 3116" 3" max. from comers & (2) equal spaced at each side of Use 3/16" Tapcon 1 1/4" +38.7 -50.5 FL# 17499.3 ANN. meeting, rail. with embedment +/- 55.0 S.H.G.C.:.22 into concrete S.H. Windows Head: 2" max. from comers & (1) at center. Jambs: FL# 17499.1 U-Factor: 0.55 185 SH MI Windows Impact 2" max. from corners &12) equal spaced at each side of meeting rail. Use 3/16" Tapcon with 1 1/4" embedment +38.7 -50.5 +/- 55 fl S.H.G.C.:.22 into concrete Fixed Window Head: 6" max. from comers & 18" max. O.C. all sides FL# 15349.1 U-Factor: 0.55 185 SH MI Windows 3/16" Use 3/16" Tapcon with 1 IA" +40.5 -54.0 +/- 60.0 S.H.G.C.:.22N' into concrete Fixed Window Head: 3" max. from comers & 13 1/2" max. o.c. all sides FL# 15349.3 U-Factor: 0.55 185 SH MI Windows Impact Use 3/16" Tapcon with 1 1/4" embedment +40.5 -54.0 +/- 55.0 S.H.O.C.:.22 into concrete Head: 6" max. from comers, (2) each side of meeting rail 3/16" 17"o.c. max. at Head and Sill. Jambs: 6" from comers and FL# 13332.2 Sliding Glass Dr. Series 420 MI Doors ANN. 17"o.c. max. Use 3/16" ITW tapeons with 1 1/4" +34.4 -37.8 +/-40.0 embedment into concrete FL# 15353.2 Mullion 5764 MI Windows NA, Two 1/4" Tapcons per clip with 1 1/4" embedment into concrete wi h 2 1 /2pedge distance. +38.7 -50 5 +/- 53.3 6" from corners & 14.5"o.c. at Jambs. Head and Sill 3" and FL#: 15037A Swing Doors Fiberglass Therma-Tin N.A. 7" from centerline. Use 1/4" Tapcon with 1 1/4" embedment +38.7 -42.1 +/- 50D Unto concrete FL#: 8248.7 Garage Door g Model 8000 Wa ne Dalton Y N.A. Jamb Bracket Angle (3) total 5/16" x 15/8" lag screws. (7) total +20.4 -22.7 +30.0 -33.5 Bracket T-O" height (1) 5/16" x 1 5/8" lag screws per bracket. Approval Product Model Number Manufacturer Attachment Method Building Rated Product Rated Number Design Pressures Design Pressures FL#: 5444.1 Roofing 4Tab Shingles CertainTeed (6)11/4" roofing nails per shingle FL#: 12856.2 Storm Panels 28 Ga. Steel Town & Country 1/4" All Points Solid Set Anchor x 7/8" embedment. 2" min. edge distance +40.5 -54.0 +/- 54.0 12"o.c. Top & Bottom 1 1/4" long No. 1 I Gauge Galv. Roofing Nail with full round head to penetrate FL#: 13192 Siding Lap Siding James Hardie furring I" 5 3/8"o.c. Vertical and 8"o.c. Horiz. with 3/8" min. edge distance and h -42.1 _92.0 max. 2"edge . distance OD /^��� DO 7t MM � W W z tu ~ a i tb W w a W A W N j'co#� � •t�l � U W U Ca E� vl O � Q,� O O M r� v 1 � t� to 4 Z U N Q un 00 M r-•I O w a) W u U •b z A s~ w � � U � C C/1 U drawn s.l. checked s.1. date b/26/18 scale as noted job number 18034 sheet A-4 t