HomeMy WebLinkAboutGENERATOR CONCRETE PAD PLAN\ \ GENERATOR I
w
2
PAD
THICKNESS
pP0 LENG�N
ISOMETRIC VIEW
PAD CODIMENSIONS:
ETE EPAD
GENERATOR
F
= I GENERATOR UNIT BY
o I' SEPARATE SUBMITTAL
(SEE SCHEDULE FOR
M MINIMUM WEIGHT
REQUIRED)
54" LENGTH
PLAN VIEW
CONCRETE PAD
ROAD MESH
MASTERFIBER 3" MIN
MAC100 �4" MIN
GROUND---\
54"
A.ivERICAST GENERATOR CONCRETE PA'v
GENERATOR. TABLE:
IVIV-VR/•1VL_ /-1rrL1�../`'\IIVIVJ VIVLT) I
SCANNEDBY RECEIVED
- st. LucieCounty
AMERICAST AUG 10 2018
9mwemerl, e-b mm
"MADE IN AAMMOA!*
FHDTAxa204252362 1.ICEN989599=050161 ST. Lucie County, PGrMitting �
53W P .Wo Ao Fon PWW. FL 3092
Tel. 772-971-19M I = 7724644509 I .-
i'null: falcaGlane.i-c<tNyeavna�eRa,lno1et201112avAo"<ea� _ - -
HVHZ OR NON-HVHZ
COUNTY
RISK
EXPOSURE EXP
RISK
EXPOSURE EXP
RISK
EXPOSURE EXP
I
C
D
II
C
I D
III, IV
C
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH
39.09 Psf
147.44 Psf
180 MPH
43.83 Psf
53.19 Psf
BROWARD
156 MPH
32.92 Psf
39.95 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
165 MPH
36.83 Psf
44.69 Psf
1175 MPH
41.43 Psfj
50.28 Psf
186 MPH
46.80 Psf
56.80 Psf
BRAND &MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT-
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005883
SO KW
25.00 "
48.00 "
29.00 "
387 Ibs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Generac 005872 & 005884
14 KW
25.00 "
48.00 "
29.00 "
439 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00 "
48.00 "
29.00 "
513 Ibs
47.44 Psf
Generac 006721
16 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 005873 & 00588S
•17 KW
25.00 "
48.00 "
29.00 "
455 Ibs
47.44 Psf
Generac 005874 & 005886
17 KW
25.00 "
48.00 "
29.00 "
421 Ibs
47.44 Psf
Generac 005875 & 005887
20 KW
25.00 "
48.00 "
29.00 "
451 Ibs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00 "
48.00 "
29.00 "
516 Ibs
47.44 Psf
Generac 006551 & 006552
22 KW
25.00 "
48.00 "
29.00 "
526 Ibs
47.44 Psf
Kohler 14RES & 20RES
14-20 KW
26.00 "
48.00 "
29.00 "
500 Ibs
47.44 Psf
GE 40323GE & 40324GE
13 KW
35.00 "
39.40 "
39.00 "
540 Ibs
39.09 Psf
EXP C 170 MPH & D 156 MPH
GE 04038215KW
15 KW
33.00 "
48.00 "
30.50 "
484 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
GE 04037817KW
17 KW
33.00 "
48.00 "
30.50 "
484 Ibs
43.83 Psf
GE 40330GE & 40331GE
20 KW
33.00 "
48.00 "
30.50 "
600 Ibs
43.83 Psf
Briggs & Stratton 040243-0
10 KW
31.00 "
32.00 "
34.00 "
430 Ibs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
50.00 "
31.60 "
507 Ibs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Briggs & Stratton G40303-1
15 KW
33.75 "
49.00 "
31.60 "
562 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75 "
49.00 "
31.60 "
568 Ibs
44.00 Psf
Briggs & Stratton 040305-1
20 KW
33.75 "
49.00 "
31.60 "
570 Ibs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00 "
48.00 "
29.00 "
406 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 007038 & 007039
20 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 007042 & 7043 1
22 KW
25.00 "
48.00 "
29.00 "
466 Ibs
47.44 Psf
GENERATOR MOUNTING CONFIGURATION:
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/ (4) #10 SS 316 SELF -DRILLING
SCREWS
TO GENERATOR
T_
Q� (SEE GENERATOR SPECS) F_ T ___T. T-F
THICK GALVANIZED
WASHER& RUBBER
GENERATOR VIBRATION PAD/
(SEE CONCRETE PAD
SCHEDULE FOR
_ I = I DIMENSIONS WEIGHT
REQUIRED)
0
N
4"
E
N �--32" WIDTH -� 54" LENGTH
v
o SIDE VIEW FRONT VIEW
GENERATOR
ANCHOR TO PAD SCHEDULE
SUBSTRATE
DESCRIPTION
CONCRETE:
(2)-3/8"0 TITEN HD
(6000 PSI
OR EQUIVALENT,
MIN.)
2-3/4" FULL EMBED
O CONCRETE, 3" MIN
EDGE DISTANCE, 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
NOTES:
1. ANCHOR QUANTITY PER LONG SIDE
2. EMBEDMENT AND EDGE DISTANCE
EXCLUDES FINISHES, IF
APPLICABLE.
3. ENSURE MINIMUM EDGE DISTANCE
AS NOTED IN ANCHOR SCHEDULE.
4. ENSURE MINIMUM SPACING TO
ANY ADJACENT ANCHORS.
5. FOLLOW -MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO
INSTALL ANCHORS.
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
%" SIMPSON TITEN HD,
SEE ANCHOR SCHEDULE
2"x3"x3/B' GALV. STEEL -
WASHER
RUBBER VIBRATION PAD -
Z CONCRETE PAD
6,000 PSI
LIGHTWEIGHT
CONCRETE PAD X CONCRETE MIX
6,000 PSI
LIGHTWEIGHT ` MASTERFIBER MAC 100
CONCRETE MIX & ROAD MESH
NOTES: FOAM CORE
1. Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2".
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
in
J 2"
I
I- - - - - - - - - -
WIND DESIGN REQUIREMENTS_
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
(2017))
AT -GRADE SIGN METHOD
ULTIMATE DESIGN WIND SPEED Vult = 186 mph
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd=
0.85 .
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H qh = 77.56
Ib/ft2
FORCE COEFFICIENT Cf = 1.44
WIND PRESSURE:
P = qh G Cf = 56.80 Ib/ft2 (ASD)
GENERAL NOTES
LANK L. BENNA DO, P.E.
:f• 0046549
rP01
03Id'jIr 069(FD, M P.E.APPEARSEUM
DON M. DIB TTISTO, P.E.
2328--- --
OTICE: IF T SHEET DOES
OT CONTAI N ORIGINAL
IGNATURE IVENGINEER SEAL
THERE IS A IGITAL
IGNATURE ON SHEET 1, THIS
4EET IS PART OF A DIGITALLY
IGNED FILE SHALL REMAIN IN
IG1TAl FORMAT,,-& PRINTEt�
OPIES OF THIS DOCUMENT
RE NOT CONSIDERED SIGNET
ND SEALED. IF THERE IS NO
IGITAL SIGNATURE ON SHEET 1
R THIS SHEET DOES NOT
ONTAIN AN ENGINEER'S
RIGINAL SIGNATURE & SEAL,
W C4
O ,a.
Z0
LL
Lu (n 2:
M O q ,
ui r�� U 'n
W
w 0
LLLf) "'X�
ZW
O O�
QI->ULLAX'a
0.r
zX
ED �
4
WW
ONO�SWwu
U W ,ten O .Z
LL Lu LJ
V7 a 2 W
W
1.
THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
W w
w 0
SIXTH EDITION (2017).
n
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH
THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A
JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE.
SITE -SPECIFIC LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
M
1
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR EQUAL TO THE "
O 0
DESIGN PRESSURE "ASD" CAPACITY VALUES LISTED HEREIN FOR ANY
ASSEMBLY AS SHOWN.
W ,J
3.
DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
STATED
LLJ
,, ^)
V/ Q�
C]
Y Z=
4.
HEREIN.
UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES HAVING EQUAL
M
a)
Q C) LLI
F-
ry
S.
CLEARANCE. A MINIMUM DISTANCE FROM UNIT TO PAD EDGE IS SPECIFIED.
CALCULATIONS MADE USING LIGHTWEIGHT CONCRETE 125 PCF
V a ,1
l
of W N w
LU
6.
THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE ALL
VEGETATION, STUMPS,
1--I LU n
r,
ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
-1 a
lA O
7.
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
Q N
Uj d �
M Z U
v
RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
n
M C) ,�„�
M LL
Q CD
O_ Z
O
8.
ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY
Y Of
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
a I
W
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
.nl )- coEXPRESS
RESPONSIBILITY OF THE CONTRACTOR.
LU N
9.
ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS
p
SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al.
INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES
O
INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL
J
LL
FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
us
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM
DEVIATIONS OF THIS PLAN.
10.
WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
G
z
o
o
RESPONSIBILITY OF THE INSTALLING CONTRACTOR. CONTRACTOR SHALL
ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING
G
MEMBRANE IS
a s
RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE
LL
p
PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
V
-Vi
U-,
Z Q
Z
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING
3
O O
O
o r o
CONTRACTOR.
13
o
11.
THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
z
ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
pp,� w $�12
INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL
BE COORDINATED BY THE PERMITTING CONTRACTOR.
W
12.
THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY SPECIFIC
C'a
Cu
z
PROJECT SITE. INFORMATION CONTAINED HEREIN IS BASED ON
H
Y
o
z
w
C
c ui
CONTRACTOR -SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EXPRESS
y
E
o _
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
OR INACCURATE DATA OR MEASUREMENTS.
DIMENSIONS ARE SHOWN TO
z
c
ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY VARY
SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN.
00-GRT ENGINEERING
EXPRESS®
WORK SHALL BE FIELD VERIFIED BY OTHERS PRIOR TO CONSTRUCTION.
ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
17-3961.1
REEVALUATE OUR WORK UPON DISCOVERY OF ANY INACCURATE
INFORMATION PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS
SCALE: NTS UNLESS
NOTED
AND FABRICATION AND INSTALLATION OF MATERIALS. ALTERATIONS OR
OF
ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR
CERTIFICATION.
13.
EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS
J�
r�'LIIII
OR AFFIRMATIONS ARE INTENDED.