Loading...
HomeMy WebLinkAboutENERGY EFFICIENCY CODE 11-9-18FORM; R405-2017 FLORIDA ENERGY EFFICIENCY CODE FOR BU ILD Fi r'da Department of Business and Professional Regulation - ResidIntl ON Project ame: Express Hayden st lucie RIGHT r30 8flex block Builder Name: ���A1NA1�� u' Street: l3 coy '9 Lo-Wl� t%1` Permit Office: City, St e, Zip: st lucie . FL , Permit Number: BY Owner: '� Express Homes Jurisdiction: St. LuVe Count - Design (location: FL. ST_LUCIE_CO INTL County: St. Lucie (Florida Climate Zone 2 ) 1. New c instruction or existing New (From Plans) 9. Wall Types(2721.3 sqft.) Insulation Area 2. Single {amity or multiple family Single-family a. Concrete Block - Int Insul, Exterior R=4.1 2374.70 ft2 b. Frame - Wood, Adjacent R=13.0 346.67 ft2 3. Numb r of units, if multiple family 1 c. N/A R= ft2 4. Numb r of Bedrooms 5 d. N/A R= ft2 1 10. Ceiling Types (2605.0 sgft.) Insulation Area 5. is this worst case? Yes a. Under Attic (Vented) R=30.0 2605.00 ft2 6. Condit ned floor area above grade (ft2) 2605. b. N/A R= ft2 c. N/A R= ft2 Condi oned floor area below grade (ft2) 0 11. Ducts R ft2 7. Windo sgft.) Description Area a.. Sup: Attic, Ret: Attic, AH: 2nd Floor a 1.50 INs(259.5 a. U- actor Dbl, U=0.40 219.50 ft2 SH�11 C: SHGC=0.31 b. U-F'zCtOT Dbl, U=0.61 40.00 ft2 12. Cooling systems kBtu/hr Efficiency SH11 C'. SHGC=0.34 a. Central Unit 47.2 SEER:15.00 c. U-F ctor: NIA ft2 SH C: 13. Heating systems kBtu/hr Efficiency d. U- actor. N/A ft2 a. Electric Heat Pump 45.5 HSPF:8.50 SH C: Area b eighted Average Overhang Depth: 1.547 ft. Area eighted Average SHGC: 0.315 14. Hot water systems I a. Electric Cap: 50 gallons 8. Floor ypes (2605.0 sgft.) Insulation Area EF: 0.980 a. Sla' On -Grade Edge Insulation R=0.0 1104.00 ft2 b. Conservation features b. Flo Over Other Space R=0.0 1064.00 ft2 None c. oth (see details) R= 437.00 ft2 15. Credits Pstat Glass/ Area: 0.100 Total Proposed Modified Loads: 86.86 PASS oor Total Baseline Loads: 87.58 I hereby certify that the plans and specifications covered by Review of the plans and R'00 S� � �0�, this talc lation are in compliance with the Florida Energy specifications covered by thiOR= s Code. �01,CONDjrjp4 calculation indicates compliance ¢ 1 with the Florida Energy Code. PREPARED BY: 01- Before construction is completed DATE: this building will be inspected for compliance with Section 553.908 I hereb '�Iorjda ertify that this building, as desiXMKRmplia a Florida Statutes. ,c with the I Energy Code. �1814�113 Ob VVE � OWNER/AGENT: DATE: BUILDING OFFICIAL: DATE: - Compliance requires certification by the air handier unit manufacturer that the air handler enclosure qualifies as certifil� d factory -sealed in accordance with R403.3.2.1. - Comp! Dance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelo leakage test report with envelope leakage no greater than 6.00 ACH50 (R402.4.1.2). - Compliance with a proposed duct leakage Qn requires a Duct Leakage Test Report confirming duct leakage to outdoors, tested iP accordance with ANSI/RESNET/ICC 380, is not greater than 0.070 Qn for whole house. !3 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5 ., FORP:i 05-2017 � +n�i I RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST_ t of Business and Professional Regu FTfF Florida Department ® p P Simulated Performance Alternative (Performance) Method is for compliance with the 2017 Florida Building Code, Energy Conservation via the Simulated Performance Method shall include: ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, a -ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst -case orientation, name and version of the compliance software tool, name of individual completing the compliance report (one page) and an input summary checklist that can be used for field verification (usually four pages/may be greater). ❑ Energy Performance level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403. 7 ❑ Mandatory Requirements (five pages) Required prior to CO for the Performance Method: ❑ Air Barrier and insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report (usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed Form R405 Duct Leakage Test Report (usually one page) 8 11:23:14 AM EnergyGauge® USA 6.0.02 (Rev. 1) - RaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 r�mR On ji r%r- nn-i-7 1K10t IT ci IMi1NeRv r.WPr_KI._IAT REPORT rvniv� i-tv.r-w -- - -- - - -- - PROJECT Title: Express Hayden st lucie RIG Bedrooms: 5 Address Type: Street Address Building ype: User Conditioned Area: 2605 Lot # Owner lI ame: Express Homes Total Stories: 2 Block/Subdivision: # of Units: 1 Worst Case: Yes PlatBook: Builder I ame: Rotate Angle: 90 Street: Permit ffice: Cross Ventilation: No County: St. Lucie Jurisdic �on: Whole House Fan: No City, State, Zip: st lucie , Family Type: Single-family FL. New/Ex'sting: New From Plans) Comme� t: CLIMATE Design Temp Int Design Temp Heating . Design Daily Temp J Design Location TMY Site 97.5 % Z5 % Winter Summer Degree Days Moisture Range ST LUCIE_CO INTL FL VEROLBEACH MUNI 39 90 70 75 299 58 Medium BLOCKS Number Name Area Volume t Blockl 2605 22403 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 1 1 st Floor 1104 9494.4 Yes 1 1 1 Yes Yes Yes 2 2nd Floor 1501 12908.6 No 5 4 1 Yes Yes Yes FLOORS III # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab -On -Grade Edge insulatio 1st Floor 154 ft 0 1104 ft2 ---- 0.8 0 0.2 2 Floor Over Other Space 2nd Floor ---- _--_ 1064 W 0 0.8 0 0.2 3 Floor over Garage 2nd Floor -- ---- 437 ft2 0.8 0 0.2 ROOF Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg) 1 Hip Composition shingles 1723 ft2 0 ftz Medium N 0.85 No 0.9 No 0 26.6 !I ATTIC V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Vented 300 1541 ft2 N N 11/9/2�18 11:23 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5 i ' FORM'R p5-2017 IMPUT SUMMARY CHECKLIST REPORT CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Vented) 1st Floor 2 Under Attic (Vented) 2nd Floor 30 30 Blown Blown 1104 ft2 1501 ft2 0.11 0.11 Wood Wood WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below Space R_yaluP Ff Ln R In ArAn R-Vahip 0 _ 1 pP N=>E Exterior Concrete Block - Int Insul 1st Floor 4.1 39 8 8 8 343.8 ft2 0 0 0.5 0 2 W=>N Exterior Concrete Block - Int Insul 1 st Floor 4.1 36 8 8 8 317.8 f12 0 0 0.5 0 _ 3 S=>W Exterior Concrete Block - Int Insul 1st Floor 4.1 18 0 8 8 156.0 ft2 0 0 0.5 0 _ 4 E=>S Exterior Concrete Block - Int Insul 1st Floor 4.1 19 0 8 8 164.7 ft2 0 0 0.5 0 _ 5 S=>W Garage Frame - Wood 1st Floor 13 22 0 8 8 190.7 ft2 0 0.23 0.5 0 6 E=>S Garage Frame - Wood 1st Floor 13 18 0 8 8 156.0 ft2 0 0.23 0.5 0 7 N=>E Exterior Concrete Block - Int Insul2nd Floor 4.1 39 8, 8 8 3418 ft2 0 0 0.5 0 8 W=>N Exterior Concrete Block - Int Insul2nd Floor 4.1 40 8 8 8 352.4 ft2 0 0 0.5 0 _ 9 S=>W Exterior Concrete Block - Int Insul2nd Floor 4.1 39 8 8 8 343.8 ft2 0, 0 0.5 0 _ 10 E=>S Exterior Concrete Block - Int Insul2nd Floor 4.1 40 8 8 8 352.4 ft2 0 0 0.5 0 DOORS # Ornt Door Type Space Storms U-Value 'Width Height Area Ft In Ft In 1 S=>W Insulated 1st Floor None .4 3 6 8 20 ft2 2 S=>W Insulated 1st Floor None .4 2 8 6 8 17.8 ft2 WINDOWS Orientation shown is the entered orientation (=>) changed to Worst Case. Wall Overhang 1/ # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 N=>E 1 Vinyl Low-E Double Yes 0.4 0.31 N 46.5 ft2 ft 0 in 10 ft 0 in None None 2 N=>E 1 Vinyl Low-E Double Yes 0.61 0.34 N 40.0 ft2 3 ft 0 in 1 ft 0 in None None 3 S=>W 3 Vinyl Low-E Double Yes 0.4 0.31 N 31.0 ft2 1 ft 0 in 10 It 0 in None None 4 S=>W 3 Vinyl Low-E Double Yes 0.4 0,31 N 12.0 ft2 6 It 2 in 2 ft 0 in None None 5 N=>E 7 Vinyl low-E Double Yes 0.4 0.31 N 62.0 ft2 1 ft 0 in 1 It 0 in None None 6 S=>W 9 Vinyl Low-E Double Yes 0.4 0.31 N 62.0 ft2 1 ft 0 in 1 ft 5 in None None 7 S=>W 9 Vinyl Low-E Double Yes 0.4 0.31 N 6.0 ft2 1 ft 0 in 1 ft 0 in None None GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation 1 437.008 ft2 437.008 ft2 64 ft 8.6 ft 13 11/9/2018 11:23 AM EnergyGaugeO USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5 ' FORM,15-2017 INPUT SUMMARY CHECKLIST REPORT INFILTRATION # S ,ope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholli house Proposed ACH(50) .000328 2240.3 122.99 231.3 .1543 6 HEATING SYSTEM # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump/ Split HSPF:8.5 45.5 kBtu/hr 1 sys#1 Ij COOLING SYSTEM 777 # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split SEER: '15 47.2 kBtu/hr 1416 cfm 0.73 1 sys#1 I HOT WATER SYSTEM 77-1 # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Garage 0.98 50 gal 80 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Cert # Company Name Collector System Model # Collector Model # Area Storage Volume FEF None None W I DUCTS V — Supply — # Location R-Value Area --- Return -- Air CFM 25 CFM25 Location Area Leakage Type Handler TOT OUT ON RLF HVAC # Heat Cool 1 Attic 8 150 ft' Attic 50 ft' Proposed On 2nd Floor -- cfm 182.4 cfm 0.07 0.60 1 1 TEMPERATURES Progra i CoolingJan Heatin Ventin able Thermostat: Y Feb Mar Jan Feb �X� Mar Jan Feb [k Mar Ceiling Fans: A r May Jul r Au [X Se Apr t Ma� Jun Jul AuE Sep f rl Junri A r [ ]]] Ma Jun Jul Aug Se [X Oct Nov Oct X� Nov Oct [X Nov Dec HDec Dec 8 11:23 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5 INPUT SUMMARY CHECKLIST REPORT ' FORM R405-2017 Thermos Schedule: HERS 2006 Reference Hours Schedule ype 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (11 D) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating (,VD) AM 66 66 66 66 66 68 68 68 66 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating ( EH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 1 MASS ass Type Area Thickness Furniture Fraction Space fault(8 Ibslsq.ft. 0 ft2 OR 0.3 1st Floor efault(8 Ibsls .ft. 0 ft2 Oft 0.3 2nd Floor 11/9/2q� 8 11:23 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5 2617I EPL DISPLAY CARD ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 99 The lower the Energy Performance Index, the more efficient the home. New home or, addition 1. New (From Plans) 12. Ducts, location & insulation level a) Supply ducts R 8.0 Single-family or multiple -family 2. Single-family b) Return ducts R 8.0 c) AHU location 2nd Floor No. of units (if multiple -family) 3. 1 Number of bedrooms 4. 5 Is this a worst case? (yes/no) 5. Yes Conditioned floor area (sq. ft.) 6. 2605 Windows, type and area a) U-factor:(weighted average) 7a. 0.432 b) Solar Heat Gain Coefficient (SHGC) 7b. 0.315 c) Area 7c. 259.5 Skylights a) U-factor:(weighted average) b) Solar Heat Gain Coefficient (SHGC) Floor type, insulation level: a) Slab -on -grade (R-value) b) Wood, raised (R-value) c) Concrete, raised (R-value) Wall type and insulation: A. Exterior: 1. Wood frame (Insulation R-value) 2. Masonry (Insulation R-value) B. Adjacent: 1. Wood frame (insulation R-value) 2. Masonry (Insulation R-value) 1. Ceiling type and insulation level a) Under attic b) Single assembly c) Knee walls/skylight walls d) Radiant barrier installed 8a. NA 8b. NA 9a. 0.0 9b. 0.0 9c. 10A1. 10A2. 4.1 1081. 13.0 1092. 11 a. 30.0 11 b. 11 c. 11 d. No 13. Cooling system: Capacity 47.2 a) Split system SEER 15.0 b) Single package SEER c) Ground/water source SEER/COP d) Room unit/PTAC EER e) Other 14. Heating system: Capacity 45.5 a) Split system heat pump HSPF 8.5 b) Single package heat pump HSPF c) Electric resistance COP d) Gas furnace, natural gas AFUE e) Gas furnace, LPG AFUE f) Other 15. Water heating system a) Electric resistance EF 0.98 b) Gas fired, natural gas EF c) Gas fired. LPG EF d) Solar system with tank EF e) Dedicated heat pump with tank EF f) Heat recovery unit HeatRec% g) Other 16. HVAC credits claimed (Performance Method) a) Ceiling fans b) Cross ventilation No c) Whole house fan No d) Multizone cooling credit e) Multizone heating credit f) Programmable thermostat Yes required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy aving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL isplay card will be completed based on installed code compliant features. uiider Signature: Date: of New Home: &h ���f�(�J)r44-9 04f City/FL Zip: st lucie. FL 11/9/ ,018 11:23:23 AM EnergyGaugeO USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 6th Edition (2017) atory Reauirements for Residential Performance, Prescriptive and ERI Methods Permit Number st lucie , FL, MANDOORY REQUIREMENTS See individual code sections for full details. SECTION R401 GENERAL R4 1.3 Energy Performance Level {EPL) display card (Mandatary). The building official shall require that an energy performance level (EPL) dis lay card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida taw (SAtion 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and noqq resold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components insiled in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans anqj specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. R4.2.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. I R402.4,1 Building thermal envelope building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The seating methods between dissimilar materials shall allow for differential expansion and contraction. i R402.4.1.1 Installation.The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. I R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 653.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. I Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. j 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑J02.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fir place. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. r-} R402.4.3 Fenestration air Ieakage.Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per U s4�are foot (1.5 Us/m2), and swinging doors no more than 0.5 efm per square foot (2.6 Us/m2), when tested according to NFRC 400 or MAI WDMAJCSA 10111.8.21A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 8 11:23 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5 MAN ATORY REQUIREMENTS - (Continued) mR402. 4 Rooms containing fuel -burning appliances. to Climate Zones 3 through 8, where open combustion air ducts provide combustion air to . open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Tat) e R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully c skated and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it pass through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑R402 .5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage betwf n conditioned and unconditioned spaces. Ali recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more han 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. SECTION R403 SYSTEMS R403.1 Controls. ❑ R4 Rt or In 3.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. 3.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. 13.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shalt be verified by testing in accordance with ANSI/RESNETIICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Seated air handier. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. 5 Building cavities (Mandatary). Building framing cavities shall not be used as ducts or plenums. Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41 °C) 55DF (I WC) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). Heated water circulation systems shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 118 11:23 AM EnergyGauge(D USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5 ❑K; hE do to R, ❑� —01 L- D TORY REQUIREMENTS - (Continued) 1.5.6 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have traps installed on both the inlets and outlets. External heat traps shall consist of either commercially available heat trap or a sward and -upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible a storage tank. 5.6 Water heater efficiencies (Mandatory). R403.5.6.1A Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to. permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burners) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of -the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar -water heaters shall meet the criteria of Section R403.5.6.2.1.. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TMA, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. 3.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3• if ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall.be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19. space permitting, or R-10 otherwise. ,. 7 Heating and cooling equipment (Mandatory). R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and Indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 Erbrr.rnr r=_weN Q;: Mt=rWANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE NMIMU (CFM) Range hoods Any 2.8 cfmfwatt Any In -line fan Any 2.8 ofmlwatt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfmtwatt Any For SI: 1 drn = 28.3 Umin. When tested In accordance with HVI Standard 916 8 11:23 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5 MANDI` TORY REQUIREMENTS - (Continued) ❑114 3.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less tha the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Sed ion 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the eq I pment shall not be less than the calculated latent load. Th published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's ex nded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb te, erature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded palarmance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. De ign values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load cal ulation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that Its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R4 3.7.1.2 Heating equipment capacity. ' R403.7.1.2.1. Neat pumps. Heat'pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sued or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. 403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ 03 and C404 of the IECC—Commercial Provisions in lieu of Section R403. ❑ R 03.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40`F (4.8°C). ❑ R40 .10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. ❑ R403.10.3 Covers. Outdoor heated swimming, pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. 11/9/20i 8 11:23 AM EnergyGaugeG USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5 R403.10.6 Heat pump pool heaters. Heat pump pool heaters stfali have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403 11 Portable spas (Mandatory)he energy consumption of electric -powered portable spas shall be controlled by the requir Pments of APSP-14. ELEC R40! I., - SECTION R404 'RICAL POWER AND LIGHTING SYSTEMS 1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be fficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps. Exception: Low -voltage lighting. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 11 11/9/2018 11:23 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5 i 2017 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Pr ect Name: Express Hayden st lucie RIGHT r30 8flex block Builder Name: Str et: I Permit Office: x Cit', State, Zip: st iucie , FL , Permit Number: U O er: Express Homes Jurisdiction: U De Iign Location: FL, ST LUCIE_CO_INTL COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA Gene.I A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall The exterior thermal envelope contains a continuous air barrier. not be used as a seating material. requit men Breaks or joints in the air barrier shall be sealed. The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit Ceilin /attic the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attics aces shall be sealed. I! The junction of the foundation and sill plate shall be sealed_ Cavities within comers and headers of frame walls Walls' The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3. Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. WindltI' ws, skylights The space between window/door Jambs and framing, and and IF ors skylights and framing shall be sealed. Rim j ists Rim joists shall include the air barrier. Rim joists shall be insulated. Floo The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (incl ing �garage insulation. maintain permanent contact with the underside of abov subfloor decking, or floor framing cavity insulation and 'antilevered shall be permitted to be in contact with the top side floor of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crar space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace Shal penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow 1w, cavities shall be filled by insulation that on Narr cavities Installation readily conforms to the available cavity spaces. Gan a separation Air sealing shall be provided between the garage and conditioned spac 3s. Rec ssed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated. f PIu bing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall Sho er/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on anterior wall tubs shall separate them from the showers and tubs. be insulated. Elejrical/phone box o The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HV ' register boots HVAC register boots that penetrate building thermal envelope shall be seated to the sub -floor or drywall. Col sled When required to be sealed, concealed fire sprinklers shall only be spri klers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids Ire sp�pkl cover plates ago walls or ceilings. , a. In II ddition, inspection of log walls shall be in accordance wdh the provisions of ICC-400. 1119/�01811,23 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1