HomeMy WebLinkAboutBUILDING PAD PREPARATION VERIFICATIONC
S
A. M. ENGINEERING AND TESTING, INC.
590N.W. MERCANTILE PLACE
PORT ST. LUCIE, FLORIDA 34986
LOCAL OFFICE: (772) 924-3575 FAX: (772) 924-3580
BUILDING PAD PREPARATION VERIFICATION
Allied New Technologies �� �� Report Date: August 18, 2008
3901 NW 115 Avenue �� ,01 Project No: PSL1940I
Miami, Florida 33178 Report No: 5
Secondary Building Pad Permit No:
Allied Fort Pierce Plant
9545 Rangeline Road, Port St. Lucie
Ft. Pierce, St. Lucie County, Florida
1. Engineering and Testing, Inc. periodically verified the preparation of the Secondary Building pad at
above referenced project including the clearing and grubbing, preparation of the existing subgrade soils
placement of fill material. Additionally, field density tests were performed on each layer of fill placed in
building pad area. Based on our observations and test results, it is our professional opinion that the fill
erial placed in the referenced pad was compacted to 95 percent of the Modified Proctor maximum dry
sity and the building pad was prepared in general accordance with the specifications for the project.
Si I grade soils beneath bottom of footings were tested and inspected. Undercutting and replacement of
subgrade soils with rock fill (No. 57 Stone) for footing subgrade preparation was performed. Our test results
an I field observations indicate that it was performed in general accordance with the project specifications. It
is ) ur professional opinion that subgrade soils in the bottom of the footings were prepared with and meet the
specifications for the project.
Fi�,ld inspections and/or density tests results have been submitted separately.
M. Engineering and Testing, Inc. has appreciated the opportunity to assist you with this phase of
Ir project. If you have any questions regarding this report or need any further information, please call
submitted,
A. [M. ENGINEERING AND TESTING, INC.
1,1,/( � I g/w
W. Moler, P.E. "
Geotechnical Engineer
Registration No. 60675
WM DataUllied New Technologies, Inc. - Allied Fort Pierce Plant - PSL194011nspectionsU - Secondary Buiding Pad Preparation Letter -
raust 18 2008.doc