HomeMy WebLinkAboutFIRE MARSHALL PLAN REVIEW 1-30-08�h ST LUCIE COUNTY FIRE DISTRICT MANNED Office of the Fire Marshal sly Plan Review SQ--0000M 5160 N.W. Milner Drive Telephone: 772.621.3322 Port Saint Lucie, FL 34983 FAX: 772.621.3604 THE FLORIDA FIRE PREVENTION CODE, 2004 EDITION IS CURRENTLY ENFORCED. The Code is based on NFPA 1 and NFPA 101, 2003 Florida Specific edition. lurisdiction: SLC FMO Permit #: B-08-349 Iroject Name: Allied Chemical Secondary Building Building Permit #: 0802-0119 kddress: 9549 Rangeline Road C11ontractor VM Construction Phone # 305-220-6557 Contractor's Address: 8370 West Flagler City: Miami (State: Florida Zip Code: 33144 Architect/Engineer: DNB Design Phone # 786-275-8480 Occupancy Type: Storage AS Permit: No Construction Type: VB FA Permit: No Square feet: 3525 FFP Permit: Number of stories: 1 Access Box: Occupant Load: A es ` Key Switch: NO 1. All revisions, including the electronic copy must ed pri permitting. 2. The Fire Marshal requires 24 hour noti n all specti 3. The respective Building Depart t s I hed 'nal inspections through the Fire Marshal's Office. 4. Failed inspections require f f pr' r to rescheduling of further inspections. 5. Penetrations through rate a of proper UL design. Design criteria shall be submitted with the construction plans. 6. Fire alarm panels shall be to 'ated indoors within a controlled environment. 7. Plans and construction are subject to corrections in the field to maintain code compliance. An electronic version of the construction plans on a CD is required. The file format shall be .pdf only. The CD shall contain a sheet index file. Files shall be separated by discipline. Files names shall match construction documents sheet numbers. Required Revisions 1. Provide portable fire protection. 2. MSDA sheets shall be provided to the fire district. 2008.08.27 08:16:06 - R: 04'00' (Design Report SBS 9AC 74498 (Order Allied Steel Project IIJ: 6400 North Andrews Ave Fort Lauderdale, FL, 33309 rRelease: SBS 9AC Plant: ELZ Service F lop: Rick Akram Est. Date: 11/17/2005 District IV onager: Other Project ID: Purchase BUILDING CODE Project Ue Category: Commercial Jobsite State: FL Building ,ode: 2004 Florida Jobsite County: Palm Beach Live Lc ;ad: 20.000 psf Reduction: Yes Wind L oad: 150.00 mph Wind Exposure: Exposure C 1/10ye r Wind: N/A Wind Category: N/A 1/30 Y ar Wind: N/A Hurricane Coastline: No Miles From Coastline: N/A Snow brounc Snow Load: 0.000 psf Snow Exp6sure* N/A Min R f Snow Load: 0.000 psf Sea Level: N/A Therm I Condition: N/A Rain Load: N/A Seismic Spectral Response(Sh) N/A % A[SnoWr Seismic: Normal Spectr I Response(Ss) ! N/A Seisms one: N/A Spectr I Response(S1) N/A Acceleration Zone(Za): N/A Spectr I Response(S2) N/A Velocity Zone(Zv): N/A Veloci Coefficient(Aa): N/A Zonal Velocity Ratio: N/A Accele fated Coefficient;(Av): N/A Near Source Factor: N/A Soil Type: i (D) Stiff Soil Design Seismic For Schools: N/A i Soil types (A, B, or C), (11, 2, or 3), (SA, SB, or SC), (S1, S2, or S3) result in smaller forces imposed on a building during seismic event.; In the absence of a soils report prepared by a licensed design professional the building code specifi s that the worst case, soil type (D), (4), (SD), (S4), be used by the building designer for determining seismic forces. Star Building Systems requires a letter and copy of a soils report from a registered design professional to document that the specified soil type exists at the site. Otherwise the conservative soil type (D), (4), (SD), (S4) must be ass med for design! Ordinarily, for buildings with metal roof and wall and no collateral materials with high mass, s�peci ling the conservative soil type will not affect the design or price of materials supplied by Star Building Systems. V Pate and time ptjnted: 01/30/2008 13:44:16 Conve + Page 1 of 17 r . IBUILDING A - MAIN 'Label: nt: Design Report 1SBS 9r4C '74498 Allied Steel Project ID: A Type: New Frame Type: No Elevation A: GEOMETRY, SIDEWALLS & ENDWALLS Stand Alone Single Slope Sidewall Width: 34'-11" Length: 7314" SWA SWC Eave eight: 21'-9 59/64" Eave Height: 18'-11" Roof Slope: 0.000000 / 12 Roof Slope: 1.000000 / 12 Dist. tc Ridge: 0'-0" Dist. to Ridge: 34'-11" Girts: 8.5" Z - Exterior Girts: 8.5" Z - Exterior EWB EWD Type: Non -Expandable Frame Type: Non -Expandable Frame Girts: 8.5" Z - Exterior Girts: 8.5" Z - Exterior Setbac System Standard Setbac System Standard Gable Flash: Yes lash. Yes Insulation Trim: No Cnsula,i n T,i No Purlins: 8.5" Z nized Secondary: No —rimary Reel Shop Coat: Red Frame Bolt Washers: No (Date and time dfinted: 01/30/2008 13:44:16 Conve + Design Report Allied Steel SBS 9.4C Project ID: 74498 IBUILDI �IG A - MAIN SP-ACINGS: Bay Spa ling (EWB-EWD): 27'-2", 22'-6", 23'-8" EWB CC L. Spacing (SWC-SWA): 1T-5 1/2",17'-5 1/2" EWD CC �. Spacing (SWA-SWC): 17'-5 1/2",17'-5 1/2" Purlin Spacing: System Standard Purlin Locations (SWA - Eave to Peak): Purlin L (cations (SWC - Eave to Peak): F-7 1/16", 3'-2 1/8", 5'-1 3/16", T-0 5/16", 8'-10 3/811, 10'-9 7/1611, 12'-6 1/211, 14'-5 5/8", 16-3 11/16", 18'-2 3/4",19'-11 13/16",21'-10 15/16", 23'-9", 25'-8 1/16", 27'-5 1/8", 29'-4 3/16", 30'-3 1/4", 32'-2 5/16", 33'-1 3/8" Framfe Lines: imn: Col. Web Depth: Raf. Web Depth: Col. Recession: 1 1, 2, 3, 4 Hard d ashers: Tapered Allowed Column: 72.00" Max Col. Web Depth: 72.00" Max Raf. Web Depth: 0.00" Ext Col. Recession: No Tapered Allowed 72.00" 72.00" 0.00" e d[inted: 01/30/2008 13:44:16 Conve + Design Report SBS 9AC 74498 i s 113uildin A - MAIN Allied Steel Project ID: �LOADSJ16ND ENCLOSURE, DEFLECTIONS & DRIFTS Roof Snow Load By Design Occupar ;cy Category: Thermal Condition: Seismic Design Category: Wind I Are all Are all 0.000 psf IV - Essential Heated osure: med Openings enclosed with materials designed to resist building wind loads: an Areas for Other enclosed with materials designed to resist building wind loads: Ceiling Load: Pfister/$,heetrock Ceiling Purlins ive: Purlins ;now: Purlins ind: Purlinsjotal Gravity: Purlins Uplift: Girts: total 0.000 psf Sprinkler: No Other: L/150 - Default fters L' L/N/A - Default er no L/180 - Defa tJ R Wind: L/120 - Defa Rafters Total Gravity: L/N/A - Defa 1 Rafters Total Uplift: L/90 - Default V Endwall Columns: Calculated - Enclosed Yes Yes 0.000 psf 0.500 psf L/150 - Default L/N/A - Default L/180 - Default L/120 - Default L/N/A - Default L/90 - Default Drifts Portal Fame Wind: H/60 - Default Portal Fame Seismic: H/50 - Default Crane: H/100 - Default Frame Live: H/60 - Default (by design H/90) Frame Snow: H/60 - Default (by design H/90) FrameWind: H/60 - Default Frame eismic: H/50 - Default Frame Total Gravity: H/60 - Default (by design H/90) Frame Qtal Wind: H/60 - Default Frame btal Seismic: H/50 - Default * Note - frame Drift (by design) values are determined by Building Code, Crane, and Open conditions. * Note - t is the responsibility of the Builder to interpret all aspects of the End Customer's specific itions and incorporate the appropriate specifications, design criteria, and design loads in o the Order Documents submitted to Star Building Systems. nta anrt times 'rintari• n1/m/9658 13.441R Conve + AVS-Brine-St. Lude.shs Design Report SBS 9.4C Allied Steel Project ID: _ 74498 I/ )BUILDING A - MAIN BRACT ` SWA Portal Frame (EWB to EWD) @ Bays: 3 Roof: Rod (EWB to EWD) @ Bays: 2 SWC: 1 Tier Rod (EWD to EWB) @ Bays: 1 EWB: None (SWC to SWA) @ Bays: No Bays EWD: None (SWA to SWC) @ Bays: No Bays Purlin: Angles Girt: Angles ROOF PANEL 2,606 s ft Type: DuraRib Struct Screws: 1-1/4" Self -Drill Gauge: 26 Stitch Screws: 7/8" Self -Drill Finish: Alum -Zinc 25 Year Coat Guarantee: N/A Thickness: N/A 20 Year Perf. Guarantee: N/A UL Rati 19: UL 30 Extended Panel: No UL Lett No Ridge Pan: No Standing Seam Clip: N/A Alignment Strip: N/A Not by anufacturer: N/A ;ALL ANEL 2,783 s ft Type: DuraRib Struct Screws: 1-1/4" Self -Drill Gauge: 26 Provide Washers: No Finish: Polar White (SIG-200) Stitch Screws: 7/8" Self -Drill Thickness: N/A 25 Year Coat Guarantee: No BASE C ONDITION Framin 1: Angle Flash Type: NB3 r Closurei None Flash Finish: Light Stone (SIG-200) FLASH FINISH Corner: Light Stone (SIG-200) Gable: Light Stone (SIG-200) Eave: Light Stone (SIG-200) All Other: Light Stone (SIG-200) Gutters Light Stone (SIG-200) Downspouts: Light Stone (SIG-200) uace ana time �nmea: uuavaeuu ­ia:44ab l;onve + AVS-urine-St. Lucie.sbs Page 5 of 17 I. Design Report I SBS 9.4C 1 74498 BUILDING A - MAIN Allied Steel Project ID: DESIG DATA FRAME(S): PORTAL -BAY 3 Inside 4arance: 19'-8 3/8" Peak Clearance: 18'-9 5/16" Peak Rafter Depth: 22.50" Column Column Knee: Quant ty: Diame er: .raunpE ortal) Elevation: A =Horiz ntal: Longi 6dinal: Column Y (Portal) Elevation: A Column a th Base: Knee 12.06" Rafter Depth: 22.50" 12.19" Clearance: 18'-9 7/16" Base Plate: 4 Lem 12.13" 0.75" Width: 8.00" 4 Thickness: 0.38" 8.46 Kips -7.27 Kips 3.98 Kips -3.82 Kips 0.00 Kips 0.00 Kips 12.06" 22.50" Knee: 12.19" -iearance: 18 -9 7/16 Anchor ods Base Plate: Quant—'ty: 4 Lem 12.13" Diame er: 0.75" Width: 8.00" Gaug 4 Thickness: 0.38" Maximu I Reactions ertic 8.46 Kips -7.27 Kips Horizo tal: 3.82 Kips -3.98 Kips Longi dinal: 0.00 Kips 0.00 Kips ****** *********************************************************************************** * These reactions control the design of the anchor rods. The load combinations which * these reactions may not be the controlling combinations required for the design of the * prod ed foundation. It is the responsibility of the foundation engineer to determine * the 3�ad combinations which are required for the design of the foundation. * Anch = rods are not supplied by Manufacturer. DESIGN DATA FRAME(S): 1 Inside C arance: 29'-10 1/2" Peak Clearance: 0'-0" - Peak Rafter Depth: 0.69" j Column I (SWC) Column i a th Knee ase: 9.56" —Rafter Depth: 20.00" Knee: lods 18.56" Clearance: 16'-811/16" Anchor Base Plate: Quantity: 4 Lem 10.00" Diamefer: 0.75" Width: 8.00" Gauge 4 Thickness: 0.38" � � I Design Report Allied Steel SBS 9AC Project ID: 74498 BUILDI G A - MAIN i C Colun , 1 (Sidewall) ertiC 5.53 Kips -14.13 Kips Horiz �tal: 7.96 Kips -5.62 Kips Longi udinal: 0.00 Kips 0.00 Kips Column i Aumn Det3th Knee Base: 1 9.56" Rafter Depth: 19.50" Knee: 23.56" Clearance: 19'-2 1/2" anchor nods Base Plate: Qua 4 LengtF— 10.00" •Diam ter: 0.75" Width: 8.00" Gauq : 4 Thickness: 0.38" e- rtic'a: 5.62 Kips -15.81 Kips Horiz i ntal: 4.45 Kips -9. 85 Kips Longitudinal: 0.00 Kips 0.00 Kips ***************************************************** ** ********************** * These reactions control the design of the ancho- T oad ombinations which * thesD reactions may not be the contro11' co nati red for the design of the * * prodaced foundation. It is the res s ility f e ndation engineer to determine * * the oad combinations which are ed th - sign of the foundation. * Anch r rods are not supplied b a t k Column 1 (SWC) --> Individdal Loads - Unfactored Lateral Lateral -` Lateral Lateral LWL1 LWL2 Wind Load 1 Wind Load 2 Wind Load 3 Wind Load 4 MR Vertical Horizontal -14.993 Kips -10.496 Kips -4.210 Kips 0.287 Kips -12.237 Kips -10.594 Kips Conve + AVS 6.870 Kips 8.107 Kips -5.360 Kips -4.122 Kips -1.796 Kips -1.803 Kips itudinal 0.000 Kips 0.000 Kips 0.000 Kips 0.000 Kips 0.000 Kips 0.000 Kips i Design Report Allied Steel SBS 9AC Project ID: y- u 74498 BUILDI G A - MAIN Individu I Loads - Unfactored Vertical Horizontal Longitudinal Column 1 SWC LWL3 -7.680 Kips -2.283 Kips 0.000 Kips LWL4 -6.989 Kips -2.286 Kips 0.000 Kips Roof Collateral Load 0.124 Kips -0 .025 Kips 0.000 Kips Roof Deal Load 1.446 Kips -0.239 Kips 0.000 Kips Roof Live Load 3.957 Kips -0.807 Kips 0.000 Kips Column 2 SWA Lateral P unary Wind Load 1 -5.950 Kips 4.184 Kips 0.000 Kips Lateral P unary Wind Load 2 -1.524 Kips 2.946 Kips 0.000 Kips Lateral P imary Wind Load 3-16.735 Kips -8 .751 Kips 0.000 Kips Lateral P imary Wind Load 4 -12 .309 Kips -9. 988 Kips 0.000 Kips LWL1-11.209 Kips 1.143 Kips 0.000 Kips LWL2-12.853 Kips 1.151 Kips 0.000 Kips LWL3 -6.745 Kips 2.382 Kips 0.000 Kips LWL4 -7.437 Kips 2.385 Kips 0.000 Kips Roof Collateral Load 0.124 Kips 0.025 Kips 0.000 Kips Roof Dea Load 1.542 Kips 0.239 Kips 0.000 Kips Rgof Liv Load 3.958 Kips 0.807 Kips 0.000 Kips coo I I t Design Report SBS 9AC 74498 Allied Steel Project ID: DESIG14 DATA FRAMES : 2 Inside learance: 29'-2 1/2" Peak Clearance: 0'-0" Peak Rafter Depth: 0.75" Columrti 1 Knee 9.69" Rafter Depth: 22.50" 21.63" Clearance: 16-6 7/16" ►nchoidLRods - Base Plate: Quantity: 4 Length 10.00" Diam ter: 0.75" Width: 8.00" - Gaug6: 4 Thickness: 0.50" Aaxim]m Reactions ertt al: 7.41 Kips -19.8 K -Horiz ntal: 11.01 Kips 7.8 Kips Longitudinal: 0.00 Kips OQL Kip i ;olum1 2 (SWA) Columr I Depth Knee _ `Base 9.63" after Depth: 22.00" Knee 28.50" Clearance: 18'-11 9/16" Anchor Rods Base Plate: Quantity: 4 Length: 10.00" Diam iter: 0.75" Width: 8.00" Gaug 4 Thickness: 0.50" Maxim m Reactions erti a : 7.51 Kips -22.12 Kips Horizontal: 6.25 Kips -13.58 Kips Long hudinal: 0.00 Kips 0.00 Kips ****** *********************************************************************************** * These reactions control the design of the anchor rods. The load combinations which * -these, reactions may not be the controlling combinations required for the design of the * * produced foundation. It is the responsibility of the foundation engineer to determine * * the oad combinations which are required for the design of the foundation. * Anchor rods are not supplied by Manufacturer. _ I Column 1 (SWC) --> R me lirinted: 01/30/2008 13:44:16 Conve + e Design Report SBS 9.4C 74498 Allied Steel Project ID: Individu I Loads - Unfactored Vertical Horizontal Longitudinal Column 1 SWC Lateral P imary Wind Load 1-21.089 Kips 9.197 Kips 0.000 Kips Lateral P-imary Wind Load 2-13.394 Kips 11.237 Kips 0.000 Kips Lateral P'mary Wind Load 3 -6. 678 Kips -7 .379 Kips 0.000 Kips Lateral P imary Wind Load 4 1.017 Kips -5.338 Kips 0.000 Kips LWL1-20.942 Kips -2.883 Kips 0.000 Kips LWL2-18.124 Kips -2.902 Kips 0.000 Kips LWL3-13.143 Kips -3.782 Kips 0.000 Kips LWL4-11.957 Kips -3.790 Kips 0.000 Kips Roof Col ateral Load 0.211 Kips -0.045 Kips 0.000 Kips Roof Dead Load 2.119 Kips -0.386 Kips 0.000 Kips Roof Li Load 5.075 Kips -1.078 Kips 0.000 Kips Column 2 SWA Lateral P imary Wind Load 1 -9.037 Kips 5.816 Kips 0.000 Kips Lateral P �!mary Wind Load 2 -1 .456 Kips 3.775 Kips 0.000 Kips Lateral P imary Wind Load 3-23.448 Kips-11.771 Kips 0.000 Kips Lateral P imary Wind Load 4 -15. 867 Kips-13.811 Kips 0.000 Kips LWL1-19.197 Kips 1.766 Kips 0.000 Kips LWL2-22.016 Kips 1.785 Kips 0.000 Kips LWL3-11.551 Kips 3.952 Kips 0.000 Kips LWL4-12.738 Kips 3.960 Kips 0.000 Kips Roof Collateral Load 0.212 Kips 0.045 Kips 0.000 Kips Roof De d Load 2.215 Kips 0 .386 Kips 0.000 Kips Roof Liv Load 5.086 Kips 078 Kips 0.000 Kips Date and time brinted: 01/30/2008 13:44:16 Conve + AVS-Brine-St. Lucie.sbs Paae 10 of Design Report SBS 9.4C 74498 Allied Steel Project ID: DESIG DATA FRAMES : 3 - Inside a'Iearance: 29'-3 1/2" Peak Clearance: 0'-0" 11 Peak Rafter Depth: 0.69" Columril1 Column�lDe th Knee Base: 9.56" R—a ter Depth: 22.50" Knee 19.56" Clearance: 16-6 1/4" Anchor Rods Base Plate: Quan ity: 4 Length: 10.00" Diam ter: 0.75" Width: 8.00" - Gaug 4 Thickness: 0.50" Maximum Reactions ertt a : 6.92 Kips C-7.26 Horiz'ntal: 10.04 Kips Kips Long iudinal: 0.00 Kips i Colum 2 (SWA) CX1 ColumnlDe th Knee Base: 9.56" meter Depth: 22.00" Knee 29.56" Clearance: 18'-11 1/2" Base Plate: Anchor Quantity: ods 4 Length 10.00" Diam lter. 0.75" Width: 8.00" Gaug I : 4 Thickness: 0.50" Maximu I Reactions Vertical: 7.01 Kips -20.48 Kips Horiz ntal: 5.96 Kips -12.74 Kips Longitudinal: 0.00 Kips 0.00 Kips ****** *********************************************************************************** * Thesel reactions control the design of the anchor rods. The load combinations which *.these reactions may not be the controlling combinations required for the design of the * produced foundation. It is the responsibility of the foundation engineer to determine * the toad combinations which are required for the design of the foundation. * Anchor rods are not supplied by Manufacturer. I Column 1 (SWC) --> and time Q'rinted: 01/30/2008 13:44:16 Conve + I'� r. is Design Report Allied Steel ` SBS 9.4C Project ID: _W 74498 Individu I Loads - Unfactored Vertical Horizontal Longitudinal _ Column .l SWC Lateral Pr mary Wind Load 1-19.577 Kips 8.366 Kips 0.000 Kips Lateral Primary Wind Load 2 -12 .431 Kips 10.258 Kips 0.000 Kips Lateral Pr mary Wind Load 3 -6.215 Kips -6.704 Kips 0.000 Kips Lateral Pr mary Wind Load 4 0.931 Kips -4 . 812 Kips 0.000 Kips LWL1-25.280 Kips -2.719 Kips -7.255 Kips LWL2-22.666 Kips -2.730 Kips -7.255 Kips LWL3-18.037 Kips -3.545 Kips -7.255 Kips LWL4-16.936 Kips -3.550 Kips -7.255 Kips Roof Coll teral Load 0.196 Kips -0 .041 Kips 0.000 Kips Roof Deac Load 2.011 Kips -0.358 Kips 0.000 Kips Roof Liv Load 4.714 Kips -0.984 Kips 0.000 Kips Column SWA Lateral Pi mary Wind Load 1 -8 .371 Kips 5.564 Kips 0.000 Kips Lateral P mary Wind Load 2 -1 .346 Kips 3.671 Kip 0.000 Kips Lateral P mary Wind Load 3 -21 .734 Kips -11 .064 Ki 0.000 Kips Lateral Pi mary Wind Load 4 -14 .709 Kips -12. 95 0.000 Kips LWL1-17.757 Kips 1. i 0.000 Kips LWL2-20.372 Kips ip 0.000 Kips LWL3-10.672 Kips 3. Kips 0.000 Kips LWL4-11.773 Kips 3. Kips 0.000 Kips Roof Coll era l Load 0.196 Kips 41 Kips 0.000 Kips Roof Dea Load 2.0 ips D .358 Kips 0.000 Kips Roof Live Load 71 ps 0.984 Kips 0.000 Kips Date and time I�rinted: 01/30/2008 13:44:16 Conve + AVS-Brine-St. Lucie.sbs Page 12 of 17 Design Report R ` ` SBS 9AC 74498 Allied Steel Project ID: DESIG II DATA FRAMES : 4 Inside Q�earance: 30'-4 1/8" Peak Clearance: 0'-0" II Peak Rafter Depth: 0.75" Columoll (SWC) Column IDeoth Knee Base : 12.19" Rueter Depth: 20.00" Knee: 12.19" Clearance: 16-8 1/8" Anchor Rods Base Plate: Quan ity: 4 Length 12.25" Diam ter: 0.75" Width: 8.00" - Gaug 4 Thickness* 0.38" Maximum Reactions erti 5.02 Kips - -ps Horiz ntal: 7.79 Kips - .3J6, Longs udinal: 0.00 Kips - ps Colum 2 (SWA) Colum De th Knee Base: 9.81" after Depth: 19.50" Knee 24.63" Clearance: 19'-2 7/16" Anchor ods Base Plate: Qua sty: 4 Lem 10.00" Diameter: 0.75" Width: 8.00" Gaug � • 4 Thickness: 0.50" Maxim M Reactions V—ertic Kips -16.41 Kips Horiz ntal: 5.03 Kips -10.66 Kips Longitudinal: 0.00 Kips 0.00 Kips * These reactions control the design of the anchor rods. The load combinations which *-these reactions may not be the controlling combinations required for the design of the * prodlced foundation. It is the responsibility of the foundation engineer to determine * the load combinations which are required for the design of the foundation. * Anch r rods are not supplied by Manufacturer. _ I Column 1 (SWC) --> Design Report Allied Steel Project ID: SBS 9.4C 74498 Individual Loads - Unfactored Vertical Horizontal Longitudinal Colum I1 SWC Lateral P imary Wind Load 1-15.494 Kips 6.758 Kips 0.000 Kips Lateral P Iimary Wind Load 2-11.544 Kips Lateral P 7.914 Kips 0.000 Kips Primary Wind Load 3 -3. 988 Kips -5.173 Kips 0.000 Kips Lateral P imary Wind Load 4 -0.039 Kips -4 .017 Kips 0.000 Kips LWL1-16.598 Kips -1.794 Kips -7.255 Kips LWL2-15.152 Kips -1.796 Kips -7.255 Kips LWL3-12.597 Kips -2.184 Kips -7.255 Kips LWL4-11.987 Kips -2.185 Kips -7.255 Kips Roof Collateral Load 0.109 Kips -0.020 Kips 0.000 Kips Roof De d Load 1.432 Kips -0.200 Kips 0.000 Kips Roof Liv Load 3.475 Kips -0. 641 Kips 0.000 Kips Column 2 SWA Ieateral P'imary Wind Load 1 -5.798 Kips 4.814 Kips 0.000 Kips Lateral P ;mary Wind Load 2 -1. 926 Kips 3 5 Kips 0.000 Kips Lateral P mary Wind Load 3 -17 .303 Kips Kips 0.000 Kips Lateral P imary Wind Load 4-13.432 Kips 0 Kips 0.000 Kips LWL1 -9.754 Ki.222 ips 0.000 Kips LWL2-11.200 .224 Kips 0.000 Kips LWL3 -5.847U&O .271 Kips 0.000 Kips LWL4 .456 2.272 Kips 0.000 Kips Roof Col ateral Load 08 0.020 Kips 0.000 Kips Roof Dead Load 495 Kips 0.200 Kips 0.000 Kips Roof Liv Load Kips 0.641 Kips 0.000 Kips Irlato -I Limo n inlorl- 51/,An/gnnR 13-dd-1Fi Cnnva + AVS-Rrine-St Luriesbs Paae 14 of 17 Design Report SBS 9.4C 74498 i BUILDI G A -MAIN Column 2 (Hot Rolled) Anchor Rods: Anchor Rods Diameter: Column Depth: Flange idth: Individual -oads - Unfactored Column 2 Dead Ld id Wind Lo d as Inward Pressure Wind Lod d as Outward Pressure Allied Steel Project ID: 4 Base Plate Width: 5.75" 0.75" Base Plate Length: 10.17" 10.17" Base Plate Thickness: 0.38" 5.75" Vertical Horizontal Longitudinal 0.433 Kips 0.000 Kips 0.000 Kips 0.000 Kips 0.000 Kips 8.639 Kips 0.000 Kips 0.000 Kips -6.890 Kips Dati 01 /30/2008 1 Design Report Allied Steel SBS 9.4C Project ID: ' 74498 DESIGN DATA ENDWALL s : EWD Colum ,'2 (Hot Rolled) - AnchorRods: 4 Base Plate Width: 5.75" Anchor Rods Diameter: 0.75" Base Plate Length: 10.17" Column Depth: 10.17" Base Plate Thickness: 0.38" Flange I Vidth: 5.75" Individual -oads - Unfactored Vertical Horizontal Longitudinal Colum 2 Dead Lo, 0.433 Kips 0.000 Kips 0.000 Kips Wind Lo d as Inward Pressure 0.000 Kips 0.000 Ki s 8.639 Kips Wind Lo d as Outward Pressure 0.000 Kips 0.000 K' s -6. 890 Kips - 6 Date and time rinted: 0