ST LUCIE COUNTY FIRE DISTRICT
Office of the Fire Marshal �f
Plan Review
5160 N.W. Milner Drive Telephone: 772.621.3322
Port Saint Lucie, FL 34983 FAX: 772.621.3604
THE FLORIDA FIRE PREVENTION CODE, 2004 EDITION IS CURRENTLY ENFORCED.
The Code is based on NFPA 1 and NFPA 101, 2003 Florida Specific edition.
III urisdiction: SLC FMO Permit #: B-08-350
IProject Name: Allied Chemical Main Building(Bleach Treatment) Building Per it #: 0802-0119
�4ddress: 9549 Rangeline Road
I�Contractor VM Construction P 5-220-6557
`Contractor's Address: 8370 West Flagler mi
State: Florida Zi e: 33144
l!Prchitect/Engineer: DNB Design one # 786-275-8480
I10ccupancy Type: Industrial AS Permit: No
(Construction Type: VB FA Permit: No
Square feet: 37,453 FFP Permit:
umber of stories: 2 Access Box: Required
umber
Load: Access Key Switch:
NOTE
All revisions, including the electronic copy must be received prior to permitting.
The Fire Marshal requires 24 hour notice on all inspections.
The respective Building Department shall schedule all final inspections through the Fire. Marshal's Office.
Failed inspections require payment of fee prior to rescheduling of further inspections.
- Penetrations through rated assemblies shall be of proper UL design. Design criteria shall be submitted
with the construction plans.
Fire alarm panels shall be located indoors within a controlled environment.
Plans and construction are subject to corrections in the field to maintain code compliance.
i electronic version of the construction plans on a CD is required. The file
-mat shall be .pdf only. The CD shall contain a sheet index file.
es shall be separated by discipline. Files names shall match construction
cuments sheet numbers.
f Required Revisions
1� Provide portable fire protection.
2! Provide MSDA sheets to fire district.
3� HVAC shall be installed and meet NFPA 90A requirements.
All installations are subject to field inspection to meet code compliance.
2008.08.27