HomeMy WebLinkAboutNOA ROOF SYSTEM FOR CONCRETE DECKWANNE®
BY
MIAMIDADE
JI DING CODE COMPLIANCE OFFICE (BCCO)
tODUCT CONTROL DIVISION
NOTICE OF ACCEPT
GAF Material Corporation
1361 Alps Road
Wayne, NJ 07470
MIAMI-DADE COUNTY, FLORIDA
METRO-DADE FLAGLER BUILDING
140 WEST FLAGLER STREET, SUITE 1603
MUNI I, FLORIDA 33130.1563
(305) 375-2901 FAX (305) 375-2908
This NOA is being issued under the applicable rules and regulations governing the use of construction materials.
The documentation submitted has been reviewed by the BCCO and accepted by the Building Code and Product
Review Committee to be used in Miami Dade County and other areas where allowed by the Authority Having
Jurisdiction (AHJ).
s NOA shall not be valid after the expiration date stated below. The BCCO (In Miami Dade County) and/or
AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for
lity assurance purposes. If this product or material fails to perform'in the accepted manner, the manufacturer
incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such
iuct or material within their jurisdiction. BCCO reserves the right to revoke this acceptance, if it is
,mind by BCCO that this product or material fails to meet the requirements of the applicable building code.
product is approved as described herein, and has been designed to comply with the High Velocity Hurricane
e of the Florida Building Code.
GAF Conventional Built -Up -Roof System for Concrete Decks.
dEWAL of this NOA shall be considered after a renewal application has been filed and there has been no
ge in the applicable building code negatively affecting the performance of this product.
t IINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
rials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any
act, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply
any section of this NOA shall be cause for termination and removal of NOA.
)VERTISEMENT: The NOA number preceded by the words Miami Dade County, Florida, and followed by
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall
done in its entirety.
IFECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews NOA #00-0403.02 and consists of pages 1 through 28.
The submitted documentation was reviewed by Frank Zuloaga, RRC.
NOA No: 03-0430.14
19 Expiration Date: 11/06/08
Approval Date:10/31/03
Page 1 of 28
ROOFING SYSTEM APPROVAL
CategM: Roofing
Sub-C_ ategM: BUR
Deck Tvne: Concrete
Maximum Design Pressure -457.5 psf
Fire Classification: See General Limitation #1
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
TABLE 1
Test Product
Product Dimensions Specification Descriution
GAF Asphalt Concrete 5, 55 gallons ASTM D 41 Asphalt concrete primer used to promote
Primer (MatdxTM 307 adhesion of asphalt in built-up roofing.
Primer)
GAP Mineral Shield® 60 lb. & 100 lb ASTM D 1863 Granules for surfacing of exposed asphalt,
Granules bags cold process cement or emulsion. GAF
Mineral Shield® Granules shall be used for
flashing applications only.
GAF WeatherCoat® 5 gallons ASTM 1227 Surface coating for smooth surfaced roofs.
Emulsion (MatrixTM
Fibered 305 Emulsion)
GAF Premium Fibered 1, 5 gallons ASTM D 2824 Fibered aluminum coating.
Aluminum Roof
Coating (MatrixTM
System Pro Aluminum
Roof Coating Fibered
301)
GAF Jetblak All 1, 5 gallons ASTM D 3019 Refined asphalt blended with a mineral
Weather Plastic ASTM D 3409 stabilizer and fibers. Permits adhesion to wet
Cement (MatrixTm and dry surfaces.
Standard Wet/Dry
Roof Cement 204)
GAF Aluminum 5 gallons Mineral colloidial bituminous emulsion with
Emulsion reflective aluminum flakes.
GAF Aluminum Roof 5 gallons ASTM D2824, Non-fbered. aluminum pigmented, asphalt
Paint (MatrixTM Type I roof coating.
System Pro Aluminum
Roof Coating Fibered
302)
GAF Built -Up 1001b. cartons, ASTM D312, Interply mopping and surfacing asphalt
Roofing Asphalt bulk Tpyes I, II, III
and IVi
GAFGLASO #75 39.37" (1 meter) ASTM D 4601 Asphalt impregnated and coated glass mat
Wide base sheet.
NOA No: 03-0430.14
Expiration Date:.11/06/08
Approval Date:10/31/03
Page 2 of 28
Test
Product
Product
Dimensions
Specification
Descriution
GAFGLAS #80
39.37" (1 meter)
ASTM D4601
Asphalt impregnated and coated, fiberglass
U1tima7 Base Sheet
Wide
base sheet.
GAFGLAS F1exP1yTM
39.37" (1 meter)
ASTM D 2178
Type VI asphalt impregnated glass felt with
6
Wide
asphalt coating.
GAFGLAS Ply 40
39.37" (1 meter)
ASTM D 2178
Type IV asphalt impregnated glass felt with
Wide
asphalt coating.
GAFGLAS® Mineral
39.37" (1 meter)
ASTM D 3909
Asphalt coated, glass fiber mat cap sheet
Surfaced Cap Sheet
Wide
surfaced with mineral granules.
GAFGLAS®
39.37" (1 meter)
ASTM D3672
Fiberglass base sheet coated on both sides
STRATAVENT®
Wide
ASTM D 4897
with asphalt. Surfaced on the bottom side
Eliminator Perforated
with mineral granules embedded in asphaltic
coating with factory perforations:
GAFGLAS® Flashing
various
Asphalt coated glass fiber mat flashing sheet
available in three- sizes.
GAFGLASO
39.37" (1 meter)
ASTM D3672
Fiberglass base sheet coated on both sides
STRATAVENT®
Wide
ASTM D 4897
with asphalt. Surfaced on the bottom side
Eliminator Perforated
with mineral granules embedded in asphaltic
Nailable
coating.
RUBEROID MOP
39.37" (1 meter)
ASTM D5147
Non -woven polyester mat coated with
Smooth
Wide
ASTM D6298
polymer modified asphalt. Does not have a
factory applied surfacing.
RUBEROID
1 sq. roll
ASTM D5147
Woven fiberglass mat coated with polymer
ULTRACLAD® SBS
101 lb.
modified asphalt and surfaced with aluminum,
copper or stainless steel foil.
RUBEROIDMOD
60 lb. kegs
SEBS modified asphalt
Asphalt, Asphalt L &
Asphalt P
RUBEROIDO
39.37" (1 meter)
ASTM D4601
Premium glass fiber reinforced SBS-modified
Modified Base Sheet
Wide.
Type II, Type
base sheet:
G2 BUR
Ruberoid® Mop
39.37" (1 meter)
ASTM D 6222
Non -woven polyester mat coated with
Granule
Wide
ASTM D 5147
polymer modified asphalt and surfaced with
mineral granules.
Ruberoid® Torch
39.37" (1 meter)
ASTM D 5147
Heavy duty, polyester reinforced, asphalt
Smooth
Wide
modified bitumen membrane.
Ruberoid® Torch Plus
39.37" (1 meter)
, ASTM D 6222
Heavy duty, polyester reinforced, asphalt
(Granule)
Wide
ASTM D 5147
modified bitumen membrane.
Ruberoid® Torch
39.37" (1 meter)
ASTM D 6222
Asphalt impregnated, coated felt, surfaced
Granule
Wide
ASTM D 5147
with mineral' granules.
Ruberoid® Torch FR
39.37" (1 meter)
ASTM D 6222
Heavy duty;.polyester reinforced, coated with
Wide
ASTM D 5147
fire retardant asphalt modified bitumen
membrane, granule surface.
NOA No: 03-0430.14
ffs.X{
Expiration Date: 11/06/08
Approval Date:10/31/03
Page 3 of 28
Test
Product
Product
Dimensions
Specification
Description
Ruberoid® Mop Plus
39.37" (1 meter)
ASTM D 6164
Non -woven polyester mat coated with
(Granule)
Wide
ASTM D 5147
polymer modified asphalt and surfaced with
mineral granules.
Ruberoid® Mop FR
39.37" (1 meter)
ASTM D 6164
Non -woven polyester mat coated with fire -
Wide
ASTM D 5147
retardant, polymer modified asphalt surfaced
with mineral granules.
Ruberoid® 20
39.37" (1 meter)
ASTM D 6163
SBS modified asphalt base sheet reinforce
Wide
ASTM D 5147
with a glass fiber mat.
Ruberoid® 30
39.37" (1 meter)
ASTM D 6163
Non woven fiberglass mat coated with
Wide
ASTM D 5147
polymer modified asphalt and surfaced with
mineral granules.
Ruberoid® 30 FR
39.3T' (1 meter)
ASTM D 6163
Non woven fiberglass mat coated with fire
Wide
ASTM D 5147
retardant, polymer modified asphalt and
surfaced with mineral granules.
Ruberoid® Mop 170
39.3T' (1 meter)
ASTM D 6164
Non -woven polyester mat coated with fire
FR
Wide
ASTM D 5147
retardant polymer modified asphalt surfaced
with mineral granules.
Vent Stacks (metal
PA 100(A)
One way valve vent used to relieve built-up
and plastic)
ASTM D 1929
pressure within theroof system. GAF Vent
ASTM D 635
Stacks are available in metal or plastic.
APPROVED INSULATIONS:
TABLE 2
Product Name
Product Description
GAFTEMP Isotherm RA, RN & Polyisocyanurate foam insulation
Composite
GAFTEMP® Composite A & N Polyisocyanurate foam insulation with
high density fiberboard or Permalite
perlite insulation.
(BMCA)GAFIEWO Fiberboard Fiberboard insulation.
EnergyGuard Perlite Perlite insulation board.
EnergyGuard Recover Board
EnergyGuard High Density
Fiberboard
PYROX
White Line
ACFoam I, Il & Composite
ISO 95+
Perlite recover board
High density wood fiberboard insulation.
Polyisocyanurate foam insulation
Polyisocyanurate foam insulation
Polyisocyanurate foam insulation
Polyisocyanurate foam insulation
Manufacturer
(With Current NOA)
GAF Materials Corp.
GAF Materials Corp.
GAF Materials Corp.
GAF Materials Corp.
GAF Materials Corp.
GAF Materials Corp.
Apache Products Co.
Apache Products. Co.
Atlas Energy Products
Firestone Building
Products, Inc.
C. NOA No: 03.0430.14
Expiration Date: 11/06/08
Approval Date:10/31/03
Page 4 of 28
APPROVED INSULATIONS:
TABLE 2
Product Name Product Description Manufacturer
(With Current NOA)
Wood Fiber Wood fiber insulation board generic
High Density Wood Fiberboard Wood fiber insulation board generic
Perlite Insulation Perlite insulation board generic
Pelite/Urethane Composite Perlite / urethane composite board generic
insulation
Type X Gypsum Fire resistant rated gypsum generic
Dens Deck Water resistant gypsum board G P Gypsum Corp.
ENRGY 2 & ENRGY 2 PLUS, Polyisocyanurate foam insulation Johns Manville
U1traGard Gold
FiberGlass Roof Insulation Glass fiber/Mineral fiber insulation Johns Manville
ISORoc Polyisocyanurate foam / rockwool Johns Manville
composite insulation
Stmctodek Wood fiber insulation board Masonite.
Paroc Base Board, Paroc Cap Rockwool insulation. Partek, Inc.
Board
Multi -Max, FA Polyisocyanurate roof insulation RMax, Inc.
APPROVED FASTENERS:
TABLE 3
Fastener Product Product Manufacturer
Number Name Description Dimensions (With Current NOA)
1. GAFTITE® (Drill-Tec®) Insulation fastener for GAF Materials Corp.
#14 Heavy Duty Roofing_ steel, wood & concrete
Fastener decks.
2. GAFTITE® (Drill-Tec®) Pre -assembled GAFTITE GAF. Materials Corp.
ASAP Fasteners and metal and
plastic plates.
3. GAFTITE® (Drill-Tec®) Base sheet fastening GAF Materials Corp.
Base Sheet Fastener and assembly.
Plate
4. Galvalume Plates (Drill- Round galvalume stress 3" and 3/i' GAF Materials Corp.
Tee® Metal) plates.
S. Polypropylene Plates Round polypropylene 3" and 31/2" GAF Materials Corp.
(Drill-Tec® Plastic) stress plates.
6. Dekfast Fasteners #14 & Insulation fastener for Construction Fasteners
#15 wood, steel and concrete Inc.
decks
NOA No: 03.0430.14
is Expiration Date: 11/06/08
Approval Date:10/31/03
Page 5 of 28
APPROVED FASTENERS:
Fastener Product
Number Name
7. Dekfast Hex Plate
8. Dekfast Lock Plate
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
#14 Roofgrip Fasteners
Hextra Plus
Metal Plate
TABLE 3
Product
Manufacturer
Description
Dimensions
(With Current NOA)
Galvalume hex stress
2 7/8" x
Construction Fasteners
plate.
3 1/4"
Inc.
Polypropylene locking
3" x 31/4" '
Construction Fasteners
plate.
Inc.
Insulation fastener for
ITW Buildex Corp.
wood and steel.
Pre -assembled Insulation
ITW Buildex Corp.
fastener and 3" metal
plate
Galvalume stress plate.
3" round
JTW Buildex Corp.
3" square
Gearlok Plastic Plate
Polypropylene round plate
3.2"
ITW Buildex Corp.
Olympic Fastener #14
Insulation fastener
Olympic Manufacturing
Group, Inc.
Fluted Nail (Con-Tite)
Insulation fastener
Olympic Manufacturing
Group, -Inc.
Olympic Fastener ASAP
Pre -assembled Insulation
Olympic Manufacturing
fastener and plate
Group, Inc.
Olympic Polypropylene
Polypropylene plastic
3.25" round
Olympic Manufacturing
plate
Group, Inc.
Olympic G-2
3" round galvalume AZ,55
3.5" round
Olympic Manufacturing
steel plate
Group, Inc.
Olympic Standard
3" round galvalume AZ50
3" round
Olympic Manufacturing
steel plate
Group, Inc.
Rawl Drive
Insulation fastener for
Powers Fasteners, Inc.
concrete decks
Rawl Plate
3" round galvalume AZ55
3" round
Powers Fasteners, Inc.
steel plate
HD Insul-Fixx Fastener
Insulation fastener for
SFS/Stadler
concrete decks
Insul Fixx S Plate
3." round galvalume AZ50
3" round
SFS/Stadler
steel plate
Insul-Fixx P Plate
3" round polyethylene
3" round
SFS/Stadler
stress plate
Tru-Fast Fasteners
Insulation fastener for
Tru-Fast
concrete decks
NOA No: 03-0430.14
Expiration Date: 11/06/08
Approval Date:10/31/03
Page 6 of 28
APPROVED FASTENERS:
TABLE 3
Fastener
Product
Product
Manufacturer
Number
Name
Description Dimensions
(With Current NOA)
25.
Tru-Fast MP-3
Galvalume AZ50 steel 3.23" round
Tru Fast
plate
26.
Tru Fast Plastic Plate
Polyethylene plastic plate. 3.04" round
Tru Fast
EVIDENCE SUBMITTED:
Test AQencv
Test Identifier
Description
Date
Factory Mutual Research Corp.
FMRC 1996
Current Insulation
01.01.96
Attachment Requirements
Factory Mutual Research Corp.
J.I.2B8A4.AM
Wind Uplift
07.02.97
J.I.3B9Q1.AM
FMRC 44704
01.08.98
J.I.ODOA8.AM
07.09.99
Factory Mutual Research Corp.
J.L OD1A8.AM
Wind Uplift
07.29.94
J.I.OY9Q5.AM
FMRC 4470 - PA 114
04.01.98
a NOA No: 03-0430.14
Y
Expiration Date: 11/06/08
Approval Date:10/31/03
Page 7 of 28
Deck Type 3I: Concrete Decks, Insulated
Deck Description: 2500 psi structural concrete or concrete plank
System Type D(1): Anchor sheet adhered with approved asphalt; all layers of insulation adhered with
approved asphalt.
All General and System Limitations shall apply.
One or more layers of any of the following insulations.
Insulation Layer Insulation Fasteners Fastener
(Table 3) Density/fe
Pyrox, White Line, ISORoc, UltraGuard Gold, ENRGY 2, GAFTEMP® Isotherm R, GAFTEMP
Isotherm RA, GAFTEMP Isotherm RN, ENRGY 2 Plus, GAFTEMP Composite, GAFTEMP
Composite A, GAFTEMP Composite N, Iso 95 +
Minimum 1" thick N/A N/A
High Density Wood Fiber, EnergyGuard High Density Fiberboard Perlite, EnergyGuard
PERLITE, EnergyGuard Recover Board
Minimum Vz" thick
N/A
N/A
Paroc
Minimum -/4" thick
N/A-
N/A
Wood Fiber, EnergyGuard Fiberboard
Minimum 1" thick
N/A
N/A
Fiberglas
Minimum 15/16" thick
N/A
N/A
Note: Concrete deck shall be primed with ASTM D 41 asphalt primer and allowed to dry prior to
application of base sheet. All insulation shall be adhered to the anchor sheet in full mopping of
approved hot asphalt within the EVT range and at a rate of 20-40 lbs/100 fe. Please refer to
Roofing Application Standard RAS 117 for insulation attachment. Insulation listed as base layer
only shall be used only as base layers with a second layer of approved top layer insulation installed
as the final membrane substrate. Composite insulation panels may be used as a top layer placed
with the polyisocyanurate side facing down. GAF requires eithera ply of GAFGLAS
STRATAVENTO EliminatorTM Perforated laid dry or a layer of Eq. ergyGuard PERLITE or wood
fiber overlay board on all isocyanurate applications.
Anchor Sheet: (Optional) Install one ply of GAFGLASO #75, GAFGLAS #80 Ultima a Base
Sheet, GAFGLAS® PLY 4®, GAFGLAS F1exply'm 6 GAFGLAS®
STRATAVENT@ Eliminator Perforated, RUBEROID Modified Base Sheet or
RUBEROID® 20 directly to primed deck adhere with any approved mopping
asphalt applied within the EVT range and at a rate of 2040 lbs./sq.
Base Sheet: (Optional) Install one ply of GAFGLAS® #75, GAFGLAS #80 UltimaTM,
GAFGLASO PLY 4®, GAFGLAS F1exPlyTM GAFGLAS® STRATAVENT®
Eliminator Perforated, RUBEROID Modified Base Sheet or RUBEROID® 20
directly to the insulated substrate. Adhere with any approved mopping asphalt
applied within the EVT range and at a rate of 20-40 lbs./sq.
NOA No: 03-0430.14
Expiration Date: 11/06/08
Approval Date:10/31/03
Page 22 of 28
Ply Sheet: Two or more plies of GAFGLAS® Ply 40 or GAFGLAS F1exPly 6 ply sheets
adhered in a full mopping of approved asphalt applied within the EVT range and at
a rate of 20-40 lbs./sq.
Cap Sheet: (Optional) One ply of GAFGLAS® Mineral Surfaced Cap Sheet adhered in a full
mopping of approved asphalt applied within the EVT range and at a rate of 2040
lbs./sq.
Surfacing: (Required if no cap sheet is used) Install one of the following: '
1. Gravel or slag applied at 400 lb./sq. and 300 lb./sq. respectively in a flood coat
of approved asphalt at 60 lb./sq.
2. GAF Premium Fibered Aluminum Roof Coating, at 1.5 gal./sq. or GAF
WeatherCoae Emulsion at 3 gal./sq.
Maximum Design
Pressure: -90 psf (See General Limitation #9.)
NOA No- 03-0430.14
{ Expiration Date: 11/06/08
Approval Date:10/31/03
Page 23 of 28
CONCRETE DECK SYSTEM LIMITATIONS:
1. If mechanical attachment to the structural deck through the lightweight insulating concrete is
proposed, a field withdrawal resistance testing shall be performed to determine fastener patterns
and density. All testing and fastening design shall be in compliance with Testing Application
Standard TAS 105 and Roofing Application Standard RAS 117, calculations shall be signed and
sealed by a Florida Registered Engineer, Architect, or Registered Roof Consultant.
•%rip
NOA No: 03-0430.14
Expiration Date: 11/06/08
Approval Date:10/31/03
Page 27 of 28
GENERAL LDaTATIONS:
1.
+01
3.
4.
5
7.
8.
9.
10.
Fire classification is not part of this acceptance, refer to a current Approved Roofing Materials
Directory for fire ratings of this product.
Insulation may be installed in multiple layers. The first layer shall be attached in compliance with
Product Control Approval guidelines. All other layers shall be adhered in a full mopping of
approved asphalt applied within the EVT range and at a rate of 20401bs./sq., or mechanically
attached using the fastening pattern of the top layer
All standard panel sizes are acceptable for mechanical attachment. When applied in approved.
asphalt, panel size shall be 4' x 4' maximum
An overlay and/or recovery board insulation panel is required on all applications over closed cell
foam insulations when the base sheet is fully mopped. If no recovery board is used the base sheet
shall be applied using spot mopping with approved asphalt, 12" diameter circles, 24" o.c.; or strip
mopped 8" ribbons in three rows, one at each sidelap and one down the center of the sheet allowing
a continuous area of ventilation. Encircling of the strips is not'acceptable. A 6" break shall be
placed every 12' in each ribbon to allow cross ventilation. Asphalt, application of either system shall
be at a minimum rate of 121bs./sq. Note: Spot attached systems shall be limited to a maximum
design pressure of 45 psf.
Fastener spacing for insulation attachment is based on a Minimum Characteristic Force (F) value of
2751bf., as tested in compliance with Testing Application Standard TAS 105. If the fastener value,
as field-tested, are below 2751bf. insulation attachment shall not be acceptable.
Fastener spacing for mechanical attachment of anchor/base sheet or membrane attachment is based
on a minimum fastener resistance value in conjunction with the maximum design value listed within
a specific system Should the fastener resistance be less than that equired, as determined by the
Building Official, a revised fastener spacing, prepared, signed and sealed by a Florida Registered
Engineer, Architect, or Registered Roof Consultant may be submitted. Said revised fastener spacing
shall utilize the withdrawal resistance value taken from Testing Application Standards TAS 105 and
calculations in compliance with Roofing Application Standard RAS 117.
Perimeter and comer areas shall comply with the enhanced uplift pressure requirements of these
areas. Fastener densities shall be increased for both insulatioi -and base sheet as calculated in
compliance with Roofing Application Standard RAS 117. (Whpn this limitation is specifically
referred within this NOA, General Limitation #9 will not be applicable.)
All attachment and sizing of perimeter na.ilers, metal profile, and/oX flashing termination designs
shall conform with Roofmg Application Standard RAS 111 and applicable wind load requirements.
The maximum designed pressure limitation.listed shall be applicable to all roof pressure zones (i.e.
field, perimeters, and comers). Neither rational analysis, nor extrapolation shall be permitted for
enhanced fastening at enhanced pressure zones (i.e. perimeters, extended comers and comers).
(When this limitation is specifically referred within this NOA, General Limitation #7 will not
be applicable.)
All products listed herein shall have a quality assurance audit in accordance with the Florida
Building Code and Rule 9B-72 of the Florida Administrative Code.
END OF THIS ACCEPTANCE
NOA No: 03-0430.14
Expiration Date: 11/06/08
Approval Date:10/31/03
Page 28 of 28