Answers to Permit Revisions
Architectural Comments
ST �UCIEC WUN
CpUNry Fl
Permit Number 0807-0170
Dear Sir:
Attached are the answers to the Architectural Comments as attached:
Comment #1, Page 2:
Provide three signed and sealed
copies of `St Lucie bounty
Design Certification for wind Ic
ad compliance' per I' BC
Section 1603.
Answer:
See Attached.
Comment #2, Page 2:
Provide three signed and sealed
copies of St. Lucie County
`Product Review Affidavit' completely
filled out for' all
cladding components.
Answer:
See Attached.
Comment #3, Page 2:
Provide three copies of truss manufacturers
placemint
drawings, with signed statement
by engineer of record that
they have been reviewed and a
proved for construction.
Answer:
Drawings by GC. See reviewed
drawings attached.
Comment #4, Page 2:
Provide detail for solid area of
offit, including all
attachments.
nt Business Center • 2101 Vista Parkway • Suite 108 • West Palm Beach, FL 334111 • (561) 684-1988 / Fa$ (561) 228-6132
RR-CO02181
1n1
r i
n
I
I
I
y I
Answer: See revised sheets A-3 & A-4.
Comment #5, Page 2: Provide lintel schedule.
Answer: See revised sheets S-2.
Comment #6, Page 2: Provide UL number for framed
hr fire wall.
Answer: See revised sheets A-4, detail 4/
-4. Most of these tenant
separation walls will not be installed
at this time but under
separate permit when spaces are
to be finished. Only, 2hr
wall sections will occur in the overhang
areas. See sheet
A-1.
Comment V, Page 2: Provide tenant separation wall d
tails, including UL
number and rating.
Answer: See revised sheets A-1 & A-4. A
-1 shows locations of only
tenant separation walls that are t
be installed under this
permit. Sheet A-4 shows details
for both the framed walls
and the masonry walls.
i
Comment #8, Page 2: Provide attic access for each
unit.
Answer: See revised sheets A-1 showing
ocations and sizes of
access panels and construction materials.
Comment #9, Page 2: If you are providing air conditioning
at this time, provide
sealed energy calcs and supply afid
return air duct plan for
each unit.
Answer: No air conditioning will be installed
under this permit.
Each unit will have separate construction
documents for the
interior work to be done. At that
time an energy code and
load calcs will be submitted.
i
i
I
i
;omment #10, Page 2: Drawing 3A shows A 1" water service and meter, plumbing
plan P-1 requires a 2" water service.
knswer: Sheet A3 is a Civil Engineer plan and the 1" meter is for
the Convenience Store to be buil on the North end of this
site. Same sheet A3 calls for a 2' water meter for each of
the three Flex buildings. The ph bing plans shows a 2"
meter to the first Flex building ( ermit being asks for at
this time ) in accordance with the Civil design.
�omments # 11 & # 12 : No answers requested.
f you have any questions with regards to the Architectural andl MEP plans for this
wilding please call our office.
[hanks,