HomeMy WebLinkAboutEVALUATION REPORTEVALUATION REPORT OF METAL SALES MANUFACTURING CORPORATION `2.6 GA. 5V-CRIMP PANEL' FLORIDA BUILDING CODE 6TH EDI-TION (2017) FLORIDA PRODUCT APPROVAL FL 14645.2-R3 ROOFING METAL ROOFING Prepared For: Metal Sales Manufacturing Corporation 545' South 311 Street, Suite 200 Louisville, KY 40202 Telephone: (502) 855-4300 Fax: (502) 855-4200 Prepared By: Bala Sockalingam, Ph.D., P.E. Florida Professional Engineer #62240 12.16 N Lansing Ave., Suite C Tulsa, OK 74106 Telephone: (918) 492-5992 FAX: (918) 493-3568 This report consists of Evaluation Report (3 Pages including cover) Installation Details (1 Page) `I'o c E e a' 111s etiee04 SQ C K,q C/®�sa ® No 62240 n � X OF 414 • �v o p� V $934it% 9. 20'1�7 SCANNED BY Report No. C2182-2 Date: 9.9.17 FL 14645.2-R3 C2182-2 Manufacturer: � Product Name: Panel Description: I Materials: 9.9.17 Page 2 of 3 Metal Sales Manufacturing Corporation 5V-Crimp 24" wide coverage with (5) 1/2" high ribs Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). Deck Description: Min. 19/32" plywood or min. 3/4" thick wood plank (min SG of 0.42) for new and existing constructions. Designed by others and installed as per FBC 2017. Deck Attachment: 8d x 2.5" long ring shank nails or #8 x 2" long wood screws @ 6" o.c. (Minimum) in the field and edges. Designed as per FBC 2017. Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1 Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2. Requires applied lap sealant for roof slopes less than 3:12. Design Uplift Pressure: 84.5 psf @ fastener spacing of 24" o.c. (Factor of Safety = 2) 131.3 psf @ fastener spacing of 18" o.c. 149.6 psf @ fastener spacing of 12" o.c. Fastener Pattern: Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener shall be of sufficient length to penetrate through the deck a minimum of 3/8". At panel ends 6 fasteners per panel width. (4 located adjacent to ribs and 2 between ribs) At intermediate 4 fasteners per panel width. (4 located adjacent to ribs) Test Standards: Roof assembly tested in accordance with TAS 125-03 `Standard Requirements for Metal Roofing Systems'. Code Compliance: The product described herein has demonstrated compliance with FBC 2017 Section 1507.4 Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress design. The maximum fastener spacing listed herein shall not be exceeded. This evaluation report is not applicable in High Velocity Hurricane Zone. Fire classification is not within scope of this Evaluation Report. Refer to FBC 2017 Section 1505 and current ` FL 14645.2-R3 C2182-2 9.9.17 Page 3 of 3 approved roofing materials directory or ASTM E108/UL790 report from an accredited laboratory for fire ratings of this product. Supporting Documents: TAS 125 Test Reports Farabaugh Engineering and Testing Inc Project No. T235-07, Reporting Date 7/12/07 Project No. T172-08, Reporting Date 4/29/08 5V-CRIMP 5V-CRIMP SEE DETAIL 1 —\ PANEL FASTENER SPACING PER ALLOWABLE PRESSURE TABLE ON THIS SHEET. TRUSS AT MAX. 24" O.C. SPACED ® 6" O.C. IN THE FIELD & AT PLYWOOD EDGES FASTENER PATTERN AT INTERMEDIATE LOCATIONS SEE DETAIL 1 � 24 (JU 1 - LV GUIDELINES OR #8 x 2" LONG WOOD SCREWS MIN. 2X_ WOOD RAFTER/JOIST/ TRUSS AT MAX. 24" O.C. SPACED ® 6" O.C. IN THE FIELD & AT PLYWOOD EDGES FASTENER PATTERN AT PANEL ENDS TYPICAL PANEL INSTALLATION X-SECTION #9-16 OR #10-14 WOODSCREWS WITH SELF SEALING WASHER AT MAXIMUM SPACING OF 24" O.C. UNDERLAYMENT --I DETAIL 1 5V-CRIMP MIN 26 GA. PLYWOOD 19/32" THICK (MIN.) ALLOWABLE UPLIFT PRESSURE FASTENER SPACING (IN) PRESSURE (PSF) 24 84.5 18 131.3 12 149,6 GENERAL NOTES: 1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE (FBC). 2. ROOF PANELS SHALL BE MIN. 26 GA. (t = 0.017"). EFFECTIVE COVERING WIDTH OF PANEL = 24". 3. THE ROOF PANELS SHALL BE INSTALLED OVER SHEATHING & STRUCTURE AS SPECIFIED ON THIS DRAWING. 4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LOADS ARE GREATER THAN THE ALLOWABLE WIND LOADS SPECIFIED ON THIS DRAWING. 5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING & THE FLORIDA BUILDING CODE. IF A DIFFERENCE OCCURS BETWEEN THE MINIMUM REQUIREMENTS OF THIS DRAWING & THE CODE, THE CODE SHALL CONTROL. 6, RAFTERS/JOISTS/TRUSSES MUST BE DESIGNED TO WITHSTAND WIND LOADS AS REQUIRED FOR EACH APPLICATION AND ARE THE RESPONSIBILITY OF OTHERS. a It 0 00 - z ��a rn <r LE wy I Ln aw00 MJ I j N QJ co (n J �¢ 't LL� Lo w N w a T z a c _ t2 a a U z 3oq o �T OF 1 Certificate of Authorization No. 29824 CREEK 17520 Edinburgh Drive Tampa, FL 33647 TECHNICAL SERVICES, LLC (813) 480-3421 EVALUATION REPORT FLORIDA BUILDING CODE, 6T" EDITION (2017) Manufacturer: MID -STATES ASPHALT AND. CANT STRIP, INC. Issued October 11, 2017 1637 51 sc Street Tuscaloosa, AL 35401 (800) 489-2391 www.msaroof.com Manufacturing Location: Tuscaloosa, AL Quality Assurance: UL LLC (QUA9625) SCOPE ory: Roofing degory: Underlayments Sections: 1504.3.1, 1507.1.1 !rties: Physical properties DESCRIPTION AND LIMITS OF USE QUIKStick Ice & Water QUIK-Stick Ice & Water Granular is an ASTM D 1970 self-adhesive underlayment Granular constructed from SBS modified asphalt, a fiberglass mat reinforcement and surfaced with granules. The product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.8-ft and has a nominal thickness of 50 mils. QUIK-Stick Ice & Water Granular is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roofing coverings. Exposure on the roof deck shall be limited to a maximum 30 days. QUIK-Stick Ice & Water QUIK-Stick Ice & Water Sand is an ASTM D 1970 self-adhesive underlayment Sand constructed from SBS modified asphalt with a fiberglass mat reinforcement and surfaced with sand. The product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.8-ft and has a nominal thickness of 50 mils. QUIK-Stick Ice & Water Sand is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roofing coverings. Exposure on the roof deck shall be limited to a maximum 30 days. QUIK-Stick HT QUIK-Stick HT is an ASTM D 1970 self-adhesive underlayment constructed from SBS (High Temperature) modified asphalt with a fiberglass mat reinforcement and poly -fabric surface. The product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.8-ft or 3-ft 3-in x 61- ft and has a nominal thickness of 60 mils. QUIK-Stick HT is to be used as prescribed in FBC Section 1507.1.1. QUIK-Stick HT is permitted to be used with adhered clay or concrete tile roofing using either ICP Adhesives Polyset AH-160 (ICP Adhesives and Sealants, Inc.). Exposure on the roof deck shall be limited to a maximum 90 days. The maximum roof slope shall be 6:12 when used with clay or concrete tile installations without battens. Tile shall be stored on battens for roof slopes greater than 6:12. Tiles shall not be stacked greater 10 tiles per stack. . MSA17001 FL17401-R4 File COPY_ Page 1 of This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK MID -STATES ASPHALT AND CANT STRIP, INC Self -Adhering Underlayments TECHNICAL SERVICES, LLC QUIK-Stick HT Pro QUIK-Stick HT Pro is an ASTM D 1970 self-adhesive underlayment constructed from (High Temperature) SBS modified asphalt with a fiberglass mat reinforcement and poly -fabric surface. The product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.8-ft and has a nominal thickness of 60 mils. QUIK-Stick HT Pro is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roofing coverings. Exposure on the roof deck shall be limited to a maximum 30 days. QUIK-Stick FS QUIK-Stick FS is an ASTM D 1970 self-adhesive underlayment constructed from SIBS (Film Surface) modified asphalt with a fiberglass mat reinforcement and textured film surface. The product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.8-ft and has a nominal thickness of 45 mils. QUIK-Stick FS is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roofing coverings. Exposure on the roof deck shall be limited to a maximum 30 days. PRODUCT APPLICATION Min. Roof Slope: 2:12 or in accordance in with the FBC Application: All underiayments shall be installed in accordance with the FBC. Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck shall be checked for protrusion and corrected prior to underlayment application. Prior to beginning installation, the underlayment shall be unrolled and allowed to relax for a minimum of 3-5 minutes. The underlayment shall be installed with the release backer removed and pressed firmly into place to ensure complete contact with the deck. The underlayment shall be installed with the roll length parallel to the eave, starting at the eave, and with minimum 3" side laps and minimum 6" end laps staggered min. 6-ft.from preceding course. It is permissible to back nail the underlayment 12-inches on -center as needed (nails shall be installed perpendicular to deck with the nail heads flush to the top surface of the underlayment). Min. Application 40°F; Contact the manufacturer when installing at temperatures below the minimum Temperature: application temperature. WIND RESISTANCE The Maximum Design Pressures shown below were calculated using a 2:1 margin of safety per FBC Section 1504.9. Underlayment System No.1 — QUIK-Stick HT only Roof Deck: Min. 15/32-inch CDX plywood attached to wood supports spaced a maximum 24" o.c. Underlayment: QUIK-Stick HT shall be fully adhered to the optionally primed plywood deck. Maximum Design -52.5 psf Pressure: MSA17001 FL17401-R4 Page 2 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. G REEjj MID -STATES ASPHALT AND CANT STRIP, INC j1 Self -Adhering Underlayments TECHNICAL SERVICES, LLC GENERAL LIMITATIONS 1) This evaluation report is not use in the HVHZ. 2) Fire Classification is not within the scope of this evaluation. 3) 'Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer's published application instructions. Where discrepancies exist between these sources, the more restrictive and FBC compliant installation detail shall prevail. 4) The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction. 5) The space under the deck area shall be properly ventilated in accordance with the FBC requirements. 6) All side lap seams shall be installed to shed water from the deck. 7) The underlayment may be used as described in other current FBC product approval documents. 8) Design wind load pressures shall be determined for components and cladding in accordance with FBC 1609. 9) The roof deck shall be designed by others in accordance with FBC requirements to resist the design wind load pressures for components and cladding. 10) Maximum Design Pressures for a given underlayment shall meet or exceed the design wind loads determined for the roof assembly. 11) All products listed in this report shall be manufactured under a quality assurance program in compliance with Rule 61G20-3. REFERENCES Entity Report No. Standard Year PRI Construction Materials Technologies (TST5878) BWR-514-02-01 ASTM D 1970 2015a PRI Construction Materials Technologies (TST5878) BWR-522-02-01 ASTM D 1970 2015a PRI Construction Materials Technologies (TST5878) BWR-533-02-01 TAS 103 1995 PRI Construction Materials Technologies (TST5878) BWR-534-02-01 ASTM D 1970 2015a ASTM D 4798 2011(2016) PRI Construction Materials Technologies (TST5878) BWR-543-02-01 ASTM D 1970 2015a PRI Construction Materials Technologies (TST5878) WRMI-011-02-01 ASTM D 1970 2015a PRI Construction Materials Technologies (TST6049) MSA-007-02-01 UL 1897 2012 PRI Construction Materials Technologies (TST6049) MSA-026-02-01 ASTM D 1970 2015a MSA17001 FL17401-R4 Page 3 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-1 The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. MID -STATES ASPHALT AND CANT STRIP, INC CREEKr Self-AdheringUnderla ments TECHNICAL SERVICES, LLC COMPLIANCE STATEMENT The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building Code, 6t' Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer. %����,'RYI IRII ��P. 9•� 2017.10.11 No 74021 10-2a; 11:41:31 * K=�-04'00' STATE OF : 141 '.�.n'••�` Q,: *� Zachary R. Priest, P.E. Si • R D•••�jN,:S Florida Registration No. 74021 % Organization No. ANE9641 CERTIFICATION OF INDEPENDENCE CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing products under this evaluation. CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under this evaluation. Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products under this evaluation. Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. END OF REPORT MSA17001 FL17401-R4 Page 4 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. TRINITY 1 ER® APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE Table Deck Application Type Description Page IA Wood New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 5-6 1B Wood New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 7 - 1C Wood New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 8-9 1D Wood New, Reroof (Tear -Off) or Recover D Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 10-12 1E-1 Wood New, Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 13-15 1E-2 Wood New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 16-17 IF Wood New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 17 2A Steel or Structural Concrete New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 18-20 2B Steel or Structural Concrete New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 21-25 2C Steel or Structural Concrete New, Reroof (Tear -Off) or Recover D Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 26-28 3A Concrete New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 29-36 3B Concrete New or Reroof (Tear -Off) A-3 Bonded Temp Roof/Vapor Barrier, Bonded Insulation, Bonded Roof Cover 36 3C Concrete New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 37 4A LWIC New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 38-39 4B LWIC New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 40 4C LWIC New, Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 41-44 5A CWF New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 45 5B CWF New or Reroof (Tear -Oft) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 46 5C CWF New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 46 5D CWF New, Reroof (Tear -Off) E Non•lnsulated, Mech. Attached Base Sheet, Bonded Roof Cover 47 6A Gypsum Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 48-49 6B Gypsum Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 50 6C Gypsum Reroof (Tear -Off) C Mech. Attached Insulation, Bonded Roof Cover 51 6D Gypsum Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 51 7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 52-57 7B Various Recover F Non -Insulated, Bonded Roof Cover 57 The following notes apply to the systems outlined herein: The roof system evaluation herein pertains to above -deck roof components. Roof decks shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the' roof d�c(c shall be documented through proper codified and/or FBC Approval documentation. 'I V Uhle=herwise noted, fasteners and stress plates for insulation attachment shall be as follows. Fasteners shall be of sufficient length for the following engagements: ➢(DWood Deck: OMG #14 Roofgrip with Flat Bottom Plate (Accutrac), OMG HD with OMG 3 in. Galvalume Steel Plate, Dekfast #14 with Hex Plate or 3" Round Insulation Plate, Trufast HD with Trufast 3" Metal Insulation Plates or FlintFast #14 Fastener with FlintFast 3" Insulation Plates. Minimum 0.75-inch plywood penetration or minimum 1-inch wood plank embedment. ➢ Meel Deck: OMG #12 or #14 Roofgrip with Recessed or Flat Bottom Plate (Accutrac), OMG #12 Standard or HD with OMG 3 in. Galvalume Steel Plate, Dekfast #12 or #14 with Hex Plate or 3" Round ® Insulation Plate, Trufast DP or HD with Trufast 3" Metal Insulation Plates or FlintFast #12 or #14 Fastener with FlintFast 3" Insulation Plates. Minimum 0.75-inch steel penetration and PC engage the top flute of the steel deck. ➢structural Concrete: OMG #14 Roofgrip with Recessed or Flat Bottom Plate (Accutrac), OMG HD or CD-10 with OMG 3 in. Galvalume Steel Plate, Dekfast #14 or DekSpike with Hex Plate or 3" Round Insulation Plate, Trufast HD or CF with Trufasf 3" Metal Insulation Plates or FlintFast #14 Fastener with FlintFast 3" Insulation Plates. Minimum 1-inch embedment. Fasteners installed with a pilot hole in accordance with the fastener manufacturer's published installation instructions. Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report 3520.03.04-R20 for FL2533-1119 Certificate of Authorization #9503 6' EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/14/2017 Prepared by: Robert Nieminen, PE-59166 Certainteed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847 Appendix 1, Page 1 of 57 TRINITY I ERD 3. Unless otherwise noted, insulation may be anyone layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite, GlasRoc Roof Board or gypsum -based roof board that meets the CIA requirements of F.A.C. Rule 61620-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover. 4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for, or installed beneath rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base sheet screws and plates are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance ofthe roof deck shall be documented through proper codified and/or FBC Approval documentation. 5. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016). 6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions. ➢ Hot asphalt (HA): Full coverage at 25-30 Ibs/square ➢ Ashland Pliodeck (A-PD): Continuous 0.75 inch wide ribbons, 12-inch o.c. Ribbons of subsequent layers shall be perpendicular to those in the layer below. ➢ Dow INSTA-STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1 inch wide ribbons, 12-inch o.c. ➢ Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c. / ➢ Millennium PG-1 Pump Grade Adhesive (M-PG1): Continuous 0.5 to 0.75-inch wide ribbons, 12-inch o.c. \r ➢ OMG OlyBond 500 or OlyBond Green (OB500): Continuous 0.75-inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot) ➢ ICP Adhesives CR-20: Continuous 2.5 to 3-inch wide ribbons, 12-inch o.c. ➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, boards shall be staggered from layer -to -layer. ➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing. Unless otherwise noted, all insulations are flat -stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then the thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table: ➢ Ashland Pliodeck (A-PD) @ 12-inch o.c, MDP -105.0 psf (Min. 1.0-inch) ➢ Ashland Pliodeck (A-PD) @ 6-inch o.c. MDP -277.5 psf (Min. 1.0-inch) ➢ Dow INSTA-STIK Quik Set Insulation Adhesive (D-IS): MDP -120.0 psf (Min. 1.0-inch) ➢ Millennium One Step Foamable Adhesive (M-OSFA): MDP 457.5 psf (Min. 1.0-inch) ➢ Millennium PG-1 Pump Grade Adhesive (M-PG1): MDP -157.5 psf (Min. 1.0-inch) ➢ OMG OlyBond 500 (OB500): MDP -45.0 psf (Min. 0.5-inch Multi -Max FA3) ➢ OMG OlyBond 500 (OB500): MDP -187.5 psf (Min. 0.5-inch ISO 95+ GL) ➢ OMG OlyBond 500 (OB500): MDP -315.0 psf (Min. 0.5-inch ENRGY 3) ➢ OMG OlyBond 500 (OB500): MDP -487.5 psf (Min. 0.5-inch ACFoam II) ➢ ICP Adhesives CR-20: MDP -117.5 psf (Min. 1.0-inch) 8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft. 9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM' Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 10. For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted. 11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105. Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report 3520.03.04-1120 for FL2533-1119 Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/14/2017 Prepared by: Robert N'ieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847 Appendix 1, Page 2 of 57 \I TRINITY] ERD 12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124. 13. For Concrete Deck or Recover Applications using System Type D, the insulation is optional. 14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches. For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1 15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications. CERTAINTEED FLINTLASTIC® MODIFIED BITUMEN COMPONENTS & APPLICATION METHODS Reference Layer Material Application BP -AA Base Glasbase; All Weather/Empire Base; Flexiglas Base; Flintlastic Base 20 Hot asphalt at 20-40 Ibs/square i Ply One or more Flintglas Ply 4; Flintglas Premium Ply 6 (Base and Ply sheets, Asphalt -Applied) BP-AA2 Base Yosemite Venting Base Hot asphalt in 24-inch diameter spots in 30- (Base, Spot -Asphalt -Applied) inch grid pattern BP-AA3 Base Yosemite Venting Base Hot asphalt in 9-inch diameter spots in grid (Base, Spot -Asphalt -Applied) pattern noted herein. BP-AA4 Base Yosemite Venting Base Hot asphalt in 9-inch wide ribbons spaced (Base, Strip -Asphalt -Applied) as noted herein: BP-CA2 Base/Ply Glasbase; All Weather/Empire Base; Flexiglas Base; Flintlastic Base 20 Henry #903 Adhesive at 1.5 gal/square Base/Ply Glasbase; All Weather/Empire Base; Flexiglas Base; FIiintlastic Base 20 Millennium Hurricane Force Membrane BP-CA3 Adhesive, beads spaced 6-inch D.C. Base Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base Ply One or more Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base SBS-AA (SBS, Asphalt -Applied) Hot asphalt at 20-40 Ibs/square Cap Flintlastic Cap 30; Flintlastic Cap 30 CoolStar; Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar; Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar; Flintlastic GMS; Flintlastic GMS CoolStar Base Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base Note: Base ply cures overnight prior to application of the ply or cap ply. FlintBond Brush or Karnak No. 81 Cold SBS-CAI Process Modified Bitumen Adhesive Brush Ply Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base (sss, Cold -Applied) Grade at 1 gal/square Cap Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar; Flintlastic Premium FR-P, Flintlastic Premium FR-P CoolStar; Flintlastic GMS; Flintlastic GMS CoolStar Base Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base Ply Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base SBS-CA2 (SBS, Cold -Applied) Henry #903 Adhesive at 1.5 gal/square. Cap Flintlastic Cap 30; Flintlastic Cap 30 CoolStar, Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar; Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar; Flintlastic GMS; Flintlastic GMS CoolStar Exterior Research and Design, LLC. d/b/a Trinity ( ERD Evaluation Report 3520.03.04-R20 for FL2533-R39 Certificate of Authorization #9503 6' EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/14/2017 Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847 Appendix 1, Page 3 of 57 FT-kii��,Ty IER CERTAINTEED FLINTLASTIC®MODIFIED BITUMEN COMPONENTS & APPLICATION METHODS (CONTINUED) Reference Layer Material Application Base Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base SBS-CA3 Ply Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base Millennium Hurricane Force Membrane Cap Flintlastic Cap 30; Flintlastic Cap 30 CoolStar; Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual (sss,cold-Applied) Adhesive, beads spaced 6-inch o.c. Cap; Flintlastic FR-P; Fliritlastic FR-P CoolStar, Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar; Flintlastic GMS; Flintlastic GMS CoolStar Base Flintlastic Ultra Poly SMS Base; Flintlastic Base 20 T Ply One or more Flintlastic Ultra Poly SMS Base; Flintlastic Base 20 T SBS-TA Torch -Applied Cap Flintlastic FR Cap 30 T; Flintlastic FR Cap 30 T CoolStar; Flintlastic GTS; Flintlastic GTS CoolStar; Flintlastic GTS-FR; (SBS, Torch -Applied) Flintlastic GTS-FR CoolStar; FlintClad Base One or more Flintlastic APP Base T; Flintlastic STA; Flintlastic STA Plus APP-TA (APP,Torch-Applied) Torch -Applied Cap Flintlastic STA; Flintlastic STA Plus; Flintlastic GTA; Flintlastic GTA CoolStar; Flintlastic GTA-FR; Flintlastic GTA-FR CoolStar SBS-SA-H Base/Ply Black Diamond Base Sheet; Flintlastic Ultra Glass SA Self Adhering (SBS, Self -Adhering, Hybrid Systems) Base Flintlastic SA PlyBase; Flintlastic SA Mid Ply SBS-SA Self -Adhering Ply Flintlastic SA PlyBase; Flintlastic SA Mid Ply (SBS, Self -Adhering) Cap Flintlastic SA Cap; Flintlastic SA Cap CoolStar; Flintlastic SA Cap FR; Flintlastic SA Cap FR CoolStar 16. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design, U.C. d/b/a Trinity I ERD Evaluation Report 3520.03.04-R20 for FL2533-R19 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/14/2017 Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847 Appendix 1, Page 4 of 57 TRINITY 1 ERD TABLE lE-is WOOD DECKS —NEW CONSTRUCTION OR REROOF (TEAR -OFF) SYSTEM TYPE E; NON -INSULATED, MECHANICALLY. ATTACHED BASE SHEET, BONDED ROOF COVER System Deck Base Sheet Roof Cover (Note 14) MOP No. (Note 1) Base Fasteners Attach Ply Cap (Psfl Min. 11/32-inch plywood at Glasbase; Flexiglas; Flintlastic 32 ga., 1-5/8-inch dia. tin caps 8-inch o.c. at 4-inch lap and 8-inch o.c. in three SBS-AA, SBS-TA W-61 max 24-inch'spans Base 20; Poly SMS Base; Ultra with 11 ga. annular ring shank (3), equally spaced, staggered center rows SBS-SA-H or APP-TA -52.5 Poly SMS Base nails Min. 19/32-inch plywood at Glasbase; Flexiglas; Flintlastic 32 ga., 1-5/8-inch dia, tin caps 8-inch o.c. at 4-inch lap and 8-inch o.c. in three SBS AA, SBS-TA W 62 max 24-inch'spans Base 20; Poly SMS Base; Ultra with 11 ga. annular ring shank (3), equally spaced, staggered center rows SBS-SA-H or APP-TA 60.0 Poly SMS Base nails - Min.19/32-inch plywood at Glasbase; Flexiglas; Flintlastic 32 ga., 1-5/8-inch dia. tin caps 6-inch o.c. at 4-inch lap and 6-inch o.c. in four SBS-AA, SBS-TA W-63 max 24-inch'spans Base Poly SMS Base; Ultra with 11 ga. annular ring shank (4), equally spaced, staggered center rows SBS-SA-H or APP-TA -82.5 Poly SMS Base nails Min. 19/32-inch plywood at Glasbase; Flexiglas; Flintlastic 32 ga., 1-5/8-inch dia. tin caps 4-inch o.c. at 3-inch lap and 4-inch o.c. in four SBS-AA, SBS-TA W-64 max 24-inch spans Base Poly SMS Base; Ultra with 11 ga. annular ring shank (4), equally spaced, staggered center rows SBS-SA-H or APP-TA 105.0 Poly SMS Base nails CONVENTIONAL SYSTEMS: _ - Glasbase; Flexiglas; Flintlastic 32 ga., 1-5/8-inch dia. tin caps BP -AA, SBS-AA, W-65 Min. 19/32-inch exterior grade Base 20; •AII Weather / Empire 11 ga. annular ring shank 9-inch o.c. at 4-inch lap and 12-inch o.c. in two SBS-TA or APP- SBS-AA, SBS-TA 45.0 * at max. 24-inch spans plywood P Base; Poly SMS Base; Ultra Polywith y nails (2), equally spaced, staggered center rows () q Y P gg TA or APP-TA SMS Base; Yosemite Min. 15/32-inch exterior grade Glasbase; Flexiglas; Flintlastic 9-inch o.c. at 2-inch lap and 18-inch o.c, in two (Optional) BP - SBS-AA, SBS-TA W 66 plywood at max. 24-inch spans Base 2 All Weather / Empire Simplex MAXX Cap (2), equally spaced, staggered center rows AA, SBS-SBS or APP-TA 45.0* Base; Poo ly SMS Base; Yosemite TA or APP-TA W 67 Min. 15/32-inch exterior grade Flintlastic APP Base T Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 18-inch o.c. in two (Optional) APP- APP-TA -45.0* plywood at max. 24-inch spans (2), equally spaced, staggered center rows TA Glasbase; Flexiglas; Flintlastic (Optional) BP - W 68 Min. 15/32-inch plywood at Base 20; All Weather / Empire Min. 1-inch long, 12 ga. Simplex 6-inch o.c. at 3-inch lap and 6-inch o.c. in four AA, , SBS- SBS-AA, SBS-TA 52.5 max 24-inch'spans Base; Poly SMS Base; Ultra Poly Metal Cap Nails (4), equally spaced, staggered center rows r APP-TA TA or APP- or APP-TA SMS Base; Yosemite Min. 19/32-inch plywood at Glasbase; Flexiglas; Flintlastic 32 ga., 1-5/8-inch dia. tin caps 8-inch o.c. at 4-inch lap and 8-inch o.c. in three BP -AA, SBS-AA, SBS-AA, SBS-TA W 69 max 24-inch'spans Base 20; Poly SMS Base; Ultra with 11 ga. annular ring shank (3), equally spaced, staggered center rows SBS-TA or APP- or APP-TA -52.5 Poly SMS Base; Yosemite nails TA Min. 15/32-inch exterior grade Glasbase; Flexiglas; Flintlastic 9-inch o.c. at 2-inch lap and 12-inch o.c. in two (Optional) BP- SBS-AA, SBS-TA W-70 plywood at max. 24-inch spans Base 20; All Weather / Empire Simplex MAXX Cap (2), equally spaced, staggered center rows AA, SBS-AA, SBS- or APP-fA -52.5 Base; Poly SMS Base; Yosemite TA or APP-TA W 71 Min. 15/32-inch exterior grade Flintlastic APP Base T Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 12-inch o.c. in two (Optional) APP- APP-TA -52.5 plywood at max. 24-inch spans (2), equally spaced, staggered center rows TA - Min. 19/32-inch plywood at Glasbase; Flexiglas; Flintlastic 32 ga., 1-5/8-inch dia, tin caps - 8-inch o.c. at 4-inch lap and 8-inch o.c. in three BP -AA, SBS-AA, SBS-AA, SBS-TA W-72 max 24-inch spans Base 20; Poly SMS Base; Ultra with 11 ga. annular ring shank (3), equally spaced, staggered center rows SBS-TA or APP- or APP-TA -60.0 Poly SIVIS Base; Yosemite nails TA Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report 3520.03.04-R20 for FL2533-R19 Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/14/2017 Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847 Appendix 1, Page 14 of 57