August 16, 2018
Mr. Carl Peterson, Building Official
St. Lucie County
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Subject: Re -Roof Letter — Applebee Residence
Porch Roof Area Per Attached Sketch
7102 Penny Lane
Fort Pierce FL 34951
Engineer's Project Number: 18FO33
Dear Mr. Peterson:
AMA--e-
ST. LUCIE COUN 10U1L P;C DI'MJ01N
REVIENUD FOR Co LIANCE
REVIEWED B _
DATE
PLANS APiD PE �' MUST BE IaPT ON JOB
0 NO IMPECTIOX WILL BE MADE.
We have reviewed the comments from Plans Examiner William Durden dated August 15, 2018.
This letter addresses those comments.
The above referenced project has a existing roof covering systems the roof that will be removed
down to the wood deck. This project contains both flat roof and sloped roof areas. The new roof
systems will be installed per the following specifications.
Project Design Parameters
• Florida Building Code - Sixth Edition
• Building Occupancy Categor: J
• Internal Pres u�`� �I -N
� now—, MIAW
^` NbLIG
• V�9�I;c�@'tegory: C
• Size of Building (WxL): 28'x54'
• Height of Building: 15'-0"
• Slope of Roof Area: Flat and Sloped
• Edge ZcUMC&ED FASTENERS OR ATTACHMENTS
• Corner: 3' Qt THE RESPONSIBILITY OF THE
CONTRACTOR OF RECORD
The existing roof coverings and underlayment shall be removed, and the existing wood deck shall
be verified to be in sound condition. Any necessary sheathing repairs shall be performed per code
with minimum size of sheathing repairs to span three (3) rafters (approximately 48"). The existing
deck and any repairs shall be re -nailed per current code requirements.
Material Specifications for the Flat Roof
Florida Product Approval: FL 2533-R19: System Type W-64
File COPY
1 �
Mr. Peterson
August 16, 2018
EPN: 18FO33 Page 2
Underlayment System: 75# base sheet mechanically attached
The underlayment system shall be installed over minimum 15/32" thick, APA rated plywood. The
base layer shall be one of the following: Glasbase; Flexiglas; Flintlastic Base 20; All Weather/
Empire Base; Poly SMS Base; Ultra Poly SMS Base; Yosemite with Flintfast 3-inch Insulation Plates
with FlintFast #14; Trufast 3-inch Metal Insulation Plates with Trufast HD fastened per the
schedule below:
Zone
Effective Area
(minimum)
Nominal (ASD) Wind
Load Pressure
Maximum Pressure per
Method of
Manufacturer
+PSF
-PSF
2
36 SF
26.6
78.0
-196.75 PSF
3
9 SF
29.8
120.6
-196.75 PSF
All areas shall be fastened at 4" on center at 3" lap and 4" on center at four (4) equally spaced,
staggered center rows.
First Ply Roof Covering System: SBS-SA-H
The first ply shall be Black Diamond Base Sheet with 4" side laps and 6" end laps with end laps
diagonally staggered not less than 3' apart.
Roof Covering System: APP-TA
The bonded roof cover shall be Flintlastic GTA CoolStar applied in hot asphalt at 25 Ibs/square.
Follow manufacturers product application requirements for additional installation requirements.
Material Specifications for the Sloped Roof
Underlayment System: QUIK-Stick self-adhesive, Florida Product Approval: FL 17401-114
The underlayment system shall be installed over minimum 15/32" thick, APA rated plywood. The
base layer shall be one of the following: QUIK-Stick Ice & Water Granular, QUIK-Stick Ice & Water
Sand, QUIK-Stick HT (High Temperature), QUIK-Stick HT Product (High Temperature), or QUIK-
Stick FS (Film Surface) fastened per below:
The underlayment shall be installed with the release backer removed and pressed firmly into
place to ensure complete contact with the deck. The underlayment shall be installed with the roll
1575 Indian River Blvd. Suite C-210 T: 772.360.4998
Vero Beach, FL 32960 StructuralFL@gmail.com
I
Mr. Peterson
August 16, 2018
EPN: 18FO33 Page 3
length parallel to the eave, starting at the eave, and with minimum 3" side laps and minimum 6"
end laps staged minimum 6-ft. from preceding course.
It is permissible to back nail the underlayment 12 inches on -center as needed (nails shall be
installed perpendicular to deck with the nail heads flush to the top surface of the underlayment).
Roof Covering System: 5V Crimp 24 Gauge, Florida Product Approval: FL 14645.3-R3
Zone
Effective Area
(minimum)
Nominal (ASD) Wind
Load Pressure
Maximum Pressure per
Method of
Manufacturer
+PSF
-PSF
2
36 SF
26.6
78.0
-149.6 PSF
3
9 SF
29.8
120.6
-149.6 PSF
I understand the product approval lists 26 gauge roof panels. I approve the use of 24 gauge roof
panels for this product, all other specifications remain the same. The approved fasteners shall be
#9-16 or #10-14 hex head wood screws with sealed washer and fastener length to penetrate the
deck a minimum of 3/8". The fasteners spacing shall be 12" on center maximum along the length
of the panel. There shall be 6 fasteners per panel width at the panel ends and 4 fasteners per
panel width at intermediate.
Follow manufacturers product application requirements for additional installation requirements.
I have reviewed the above information and certify that to my best knowledge and belief; the
referenced method of attachment provides adequate resistance to the wind loads and forces
specified by current code provisions. Should you have any questions regarding the above subject,
please call.
Very Y , truly oursCE'8�����/�
Y ��`\���N�c E N Fyl��► �'�
A
* No. 81238
Terence Schlitt, P.E. a_
FL P.E. # 81238 August 16, 2018 �p�. STATE OF
ORI
cc: Mr. Paul Lucas, Lucas Roofing, Inc. //r ZONAI.E�G��
IIInI�ti
1575 Indian River Blvd. Suite C-210 T: 772.360.4998
Vero Beach, FL 32960 StructuralFL@gmail.com
I)P.slnn PrnfP.sslnnnl'.s Plvrtrnnir. nr dinitnl.cPnl nrclonnturP is PffPrtivP nnly n.s to thnt vvrsinn of this dnrumvnt n.s nrininnlly nuhli.shPd by [)Pcinn PrnfrssinnnL I)P.cinn PrnfP.scinnnl is not rvsnnncihlP fnr nnv.suhsPmiPnt mndiflrntinn. rnrruntinn. nr unnuthnri7Pd u.sP nf.surh dnrumrnt. Tn vvrifv the validity nr nnnlirnhility of the .sanl nr.sinnnturp. rnntnrt I)rsinn PrnfPsclnnnl.