HomeMy WebLinkAboutEVALUATION REPORT POLYGLASS ROOF UNDERLAYMENTr
SCANNED MEMO I etc.
BY Certificate of Authorization #32455
c3t• Lude Co anjj?53 Christian Street, Unit #13
O � � �� �� Oxford, CT 06478
(203) 262-9245
GINEER I EVALUATE j`�12%�vTI sT CONSULT CERTIFY
EVALU�1�
REPORT ST. LUCIE COUNTY ILDING IVI
n Lim
REV!— NED
Polygla' s USA, Inc. REVIEWED Evaluation Report P12060.02.09-R24
1111 lest Newport Center DritkATE t FL5259-R28
Deerfie J Beach, FL 33442 PLANS ANDVPERMIT
KEPT ON JOB
SITE OR NO INSPECILL BE MADE Date of Issuance: 02/24/2009
(954) 2 3-1230 Revision 24: 01/24/2018
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
constru tion materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E.
for use �of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products
described herein have been evaluated for compliance with the 6t Edition (•2017 Florida Buildin Code sections noted
herein. FILE
COPY
DESCRIP11ION: Polyg ass Roo Un erlayments
LABELIN I: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTIN ED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
QualityAssurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluatj; n Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
producis), the Quality Assurance or the production facility location(s). NEMOIetc'. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOletc. Evaluated" may be displayed in
adverti ng literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: N: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distribul ors and shall be available for inspection at the job site at the request of the Building Official.
This Eva,luation Report consists of pages 1 through 14.
Prepared by:
Robert M. Nieminen, P.E.
Florida �gistration No. 59166, Florida DC4ANE1983
CONCEALED FASTENERS OR ATTACHMENTS
ARE THE RESPONSIBILITY OF THE
CONTRACTOR OR RECORD
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 01/24/2018. This does not serve as an electronically
signed document.
CERTIFICA IION OF INDEPENDENCE:
1. NE 0 etc. does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distr puting products it evaluates.
2. NEIVOletc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robel, Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
5. This isa building code evaluation. Neither NEMOIetc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
projCt on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specfically for that purpose.
THESE PLANS AND ALL PROPOSED WORK
ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY FIELD INSPECTORS THAT
MAY BE NECESSARY IN ORDER TO
COMPLY WITH ALL APPLICABLE CODES.
ROOFING,
1.
2.
3.
ONEMOletc.
EVALUATION:
uct Category: Roofing
Category: Underlayment
pliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the
wing sections of the 6 E Rion 201�7,Florida Bui in Co a through testing in accordance with the following Standards.
pliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein.
tion
Property
Standard
Year
�.3.1
Wind Uplift
FM 4474
2011
�.3.1
Wind Uplift
UL 1897
2012
7.2.3 / 1507.1.1
Physical Properties
ASTM D226
2009
7.2.4 / 1507.1.1, 1507.2.9.2
Physical Properties
ASTM D1970
2015
7.3.3
Physical Properties
FRSA/TRI April 2012
2012
7.11.2
Physical Properties
ASTM D6164
2011
7.11.2
Physical Properties
ASTM D6222
2011
110
Accelerated Weathering
ASTM D4798
2011
ntity
Examination
Reference
Date
M Approvals (TST 1867)
Wind Uplift
3004091
01/12/2000
RI (TST 5878)
Physical Properties
PRIO1111
04/08/2002
RI (TST 5878)
Physical Properties
PUSA-005-02-01
01/31/2002
RI (TST 5878)
Physical Properties
PUSA-013-02-01
12/23/2002
RI (TST 5878)
Physical Properties
PUSA-013-02-02
12/23/2002
RI (TST 5878)
Physical Properties
PUSA-013-02-03
12/23/2002
RI (TST 5878)
Physical Properties
PUSA-018-02-01
07/14/2003
RI (TST 5878)
Physical Properties
PUSA-028-02-01
07/13/2005
RI (TST 5878)
Physical Properties
PUSA-033-02-01
01/12/2006
RI (TST 5878)
Physical Properties
PUSA-035-02-01
09/29/2006
RI (TST 5878)
Physical Properties
PUSA-055-02-02
12/10/2007
RI (TST5878)
Physical Properties
PUSA-061-02-02
01/28/2008
RI (TST 5878)
Physical Properties
PUSA-076-02-01
02/22/2008
RI (TST 5878)
Physical Properties
PUSA-083-02-01
04/14/2008
RI (TST 5878)
Physical Properties
PUSA-088-02-01
07/29/2009
1TI (TST 2508)
Physical Properties
JX201-17A
04/01/2008
1TI (TST 2508)
Physical Properties
RX14E8A
01/29/2009
RD (TST 6049)
Physical Properties
11752.09.99-1
02/08/2000
RD (TST 6049)
Wind Uplift
11757.08.01-1
08/13/2001
RD (TST 6049)
Wind Uplift
11776.06.02
01/16/2003
RD (TST 6049)
Physical Properties
02200.07.03
07/14/2003
RD (TST 6049)
Wind Uplift
P1740.01.07
01/04/2007
RD (TST 6049)
Physical Properties
P5110.04.07-1
04/11/2007
RD (TST 6049)
Wind Uplift
P9260.03.08
03/21/2008
RD (TST 6049)
Physical Properties
P13450.08.09
08/13/2009
RD (TST 6049)
Wind Uplift
P30540.11.09-111
11/30/2009
RD (TST 6049)
Physical Properties
P11030.11.09-1
11/30/2009
RD (TST 6049)
Wind Uplift
P11030.11.09-2
11/30/2009
RD (TST 6049)
Physical Properties
P11030.11.09-3
11/30/2009
RD (TST 6049)
Physical Properties
P33360.06.10
06/25/2010
RD (TST 6049)
Physical Properties
P33370.03.11
03/02/2011
RD (TST 6049)
Physical Properties
P33370.04.11
04/26/2011
RD (TST 6049)
Physical Properties
P37300.10.11
10/19/2011
ETC, LLC. Evaluation Report P12060.02.09-R24
to of Authorization #32455 6EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 2 of 14
4.
f
ONEMOjetc.
iti�t Examination Reference Date
iD (TST 6049) Physical Properties P40390.08.12-1 08/06/2012
ID (TST 6049) Physical Properties P40390.08.12-2 08/07/2012
tD (TST 6049) Physical Properties C41420.09.12-3 09/11/2012
tD (TST 6049) Wind Uplift P39680.03.13 03/04/2013
tD (TST 6049) Physical Properties P45370.04.13 04/26/2013
tD (TST 6049) Wind Uplift P1738.02.07-R2 04/29/2013
tD (TST 6049) Wind Uplift 11757.04.01-1-R1 04/30/2013
ID (TST 6049) Wind Uplift P41630.08.13 08/06/2013
W (TST 6049) Wind Uplift P11751.05.03-R1 11/26/2013
tD (TST 6049) Wind Uplift P11781.11.03-R1 11/26/2013
W (TST 6049) Physical Properties P45270.05.14 05/12/2014
M (TST 6049) Physical Properties 6020.07.14-1 09/08/2014
M (TST 6049) Physical Properties 6020.09.14-2 09/08/2014
tD (TST 6049) Physical Properties 6020.09.14-3 09/08/2014
M (TST 6049) Physical Properties 6020.09.14-4 09/08/2014
M (TST 6049) Physical Properties 6020.09.14-5 09/08/2014
M (TST 6049) Physical Properties 6020.09.14-6 09/08/2014
tD (TST 6049) Physical Properties P46520.10.14 10/03/2014
M (TST 6049) Physical Properties P43290.10.14 10/17/2014
tD (TST 6049) Physical Properties PLYG-SC7550.03.15 03/24/2015
tD (TST 6049) Physical Properties P40390.04.15 04/03/2015
M (TST 6049) Physical Properties P44360.10.14-R1 05/18/2015
M (TST 6049) Physical Properties PLYG-SC8080.05.15-1 05/20/2015
tD (TST 6049) Wind Uplift PLYG-SC8905.05.16-1 05/17/2016
tD (TST 6049) Physical Properties PLYG-SC8080.07.16 07/16/2016
M (TST 6049) Wind Uplift PLYG-SC12025.10.16 10/12/2016
M (TST 6049) Physical Properties PLYG-SC13040.12.16 12/27/2016
M (TST 6049) Physical Properties PLYG-SC11900.03.17 03/10/2017
tD (TST 6049) Physical Properties PLYG-SC12115.08.17 08/08/2017
C-ES (EVL 2396) IBC Compliance ESR-1697 11/01/2014
iami-Dade (CER 1592) HVHZ Compliance NOA 14-0717.08 01/22/2015
ilyglass USA Manufacturing Affidavit Products Current 02/18/2009
ilyglass USA P/L Affidavit Mule -Hide Cross Ltg 03/01/2008
ilyglass USA Materials Affidavit Polystick SA Compound 08/18/2011
., LLC. (QUA9625) Quality Control Service Confirmation Exp. 10/05/2018
RODUCT DESCRIPTION:
I{Y. IVlechamcally Fastened Underlayments
1.1 Elastobase is a fiberglass reinforced,'SBS modified bitumen base sheet.
1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet.
`1.3 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheet.
1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet.
"12 Self -Adhering Underlayments: -
2.1 Polystick MTS or Polystick MTS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass
fiber reinforced, surfaced with polyolefinic film surface; meets FRSA/TRI April 2012.
2.2 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an
aggregate surface; meets ASTM D1970.
1' 2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a
polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
ETC, U.C.
to of Authorization #32455
CH EDITION (2017) FBC NON-HVHZ EVALUATION
Polyglass Roof Underlayments; (954) 233-1230
Evaluation Report P12060.02.09-R24
FL5259-R28
Revision 24: 01/24/2018
Page 3 of 14
1
MEMO I etc.
1 2.4 Polystick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester
I, reinforced, with a granular surface; meets FRSA/TRI April 2012.
-> 4�2.5 Po stic TU Max is a nomina 60-mi this ru erize as - a t waterproo In mem rave wit a 190 m2 o ester
a U su aCe; meets .'SiTKA11 RI FATE,i 1 F2012,
S.
6 Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester
reinforced, APP modified bitumen cap sheets; meet FRSA/TRI April 2012.
7 Polystick Dual ProTm is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTM D1970.
8 Polystick Tile ProTm is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
9 Polystick MU-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polypropylene film surface; meets AC188 and physical requirements, of ASTM D1970 (See Section
5.8).
413: Mechanically Fastened and/or Bonded Underlayments:
Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS
modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an
alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the "Two Ply
System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems.
Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164.
Elastoflex S6 G and Elastoflex S6 G FR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380,
Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems.
Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FR is for use as an
alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath
mechanically fastened tile roof systems.
Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222.
Polyflex G is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012
(04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FR is for use as an alternate to Heat
Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile
roof systems.
This is a building code evaluation. Neither NEM01etc. nor Robert Nieminen, P.E. are, in any way, the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
This Evaluation Report is not for use in the HVHZ.
Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire
ratings of this product.
Polyglass Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced
within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for
approval based on this evaluation combined with supporting data for the prepared roof covering.
-c, LLC. Evaluation Report P12060.02.09-1124
of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 4 of 14
ONEMOjetc.
Allowable Roof Covers:
f
TABLE 1: ROOF COVER OPTIONS
hderlayment
Asphalt Shingles
Nail -On Tile
Foam -On Tile
Metal
Wood Shakes
& Shingles
Slate
E
stobase
Yes
Yes
(Base Sheet in 2-ply system)
Yes
(Base Sheet in 2-ply system)
Yes
Yes
Yes
E
stobase P
Yes
Yes
(Base Sheet in 2-ply system)
Yes
(Base Sheet In 2-ply system)
Yes
Yes
Yes
PI
lyglass G2 Base
No
Yes
(Base Sheet in 2-ply system)
Yes
(Base Sheet In 2-p1y system)
No
No
No
P
lyglass APP Base
No
Yes
(Base Sheet In 2-ply system)
Yes
(Base Sheet In 2-ply system)
NO
No
No
Pplystick
MTS or MTS PLUS
Yes
Yes
No
Yes
Yes
Yes
P°
lystick IR-Xe
Yes
No
No
No
Yes
Yes
Polystick
TU P
No
Yes
Yes (See 5.5.1)
No
No
No
P�lystick
TU Plus
Yes
Yes
Yes (See 5.5.1)
Yes
Yes
Yes
P
stie Max
No
es
Yes (See 5.5.1)
Yes
No
No
Pplystick
Dual Pro
Yes
No
No
Yes
Yes
Yes
Pplystick
Tile Pro
Yes
Yes
Yes (See 5.5.1)
Yes
Yes
Yes
P
lystick MU-X
Yes
No
No
Yes
Yes
Yes
E,
stoflex S6 G
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
E
astoflex S6 G FR
Yes
Yes
No
No
Yes
Yes
E
astoflex G TU
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
P
Ayflex G
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
P
lyflex G FR
Yes
Yes
No
No
Yes
Yes
P
lyflex SAP or SAP FR
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
o
le -Hide SA-APP Cap Sheet
SA-APP Cap Sheet (FR)
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
5� 15.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations.
,, TABLE:IA:ALLOWABLE;TILE
ADHESIVE � UNDERLAYMENT COMBINATIONsl
Adhesive
Florida Product
Approval
Underlayments
DAP
The
Foam Touch `n Seal StormBond Roof
Adhesive
FL14506
Polystick TU Plus, Polystick TU Max
Dhow TileBond""
FL22525
Polystick TU P, Polystick TU Plus, Polyflex SAP or Tile Pro
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
I I P Adhesives Polyset® AH-160
FL6332
Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
IAdhesives Polyset® RTA-1
FL6276
Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
Tc, I.I.C. Evaluation Report P12060.02.09-R24
e of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION F1.5259-1128
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 5 of 14
16.2
ONEMOletc.
Allowable Substrates:
Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet
(FR) self -adhered to:
➢ New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing
plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed
Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels
(designed and installed to meet wind loads for project).
Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or
OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
➢ ASTM D41 primed structural concrete.
Polyflex G or Polyflex G FR torch -applied to:
➢ ASTM D41 primed structural concrete.
Bond -to -Insulation:
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered
to:
➢ ASTM C1289, Type II, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck
DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
➢ Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
Polyflex G or Polyflex G FR torch -applied to:
➢ ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum
requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile
systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of
the insulation/underlayment system in accordance with FBC Section 1504.3.1.
Bond to Mechanically Attached Base Laver:
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or
Tile Pro self -adhered to:
➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base.
Polyflex G or Polyflex G FR torch -applied to:
➢ Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum
codified requirements. For installations under foam -on tile systems, base layer shall be attached per minimum
requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in
accordance with FBC Section 1504.3.1.
'C, LLC. Evaluation Report P12060.02.09-R24
ofAuthorizotion #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 6 of 14
ONEMOjetc.
4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed
that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design
pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density
designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked
with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January
2016) for Zone 2/3 enhancements.
Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days
after installation.
Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation.
Po ystic . MTrS, MTS PLUS, TU P, TU P us, TU Max, Dua Pro, Ti a Pro or E asta ex G TU s a not e e ex ose or
Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure
limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30
days.
Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the
prepared roof covering is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum
exposure is 180 days.
Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226
roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as
set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance.
Tile Slippage Limitations (FRSA/TRI April 2012 (04-12)):
When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
{
TABLE 2. TILE SLIPPAGE LIMITATIONS F,OR DIRECT -,DECK TIL6INSTACLATIONS
. ., ,. :.
itderlayment
Tile Profile
Staging Method
Maximum Slope
E�a1
stoflex G TU
Flat
10-tile stack
7:12
Lugged
8-tile stack (6 over 2)
6:12
El
astoflex S6 G or S6 G FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
Pplystick
II
MTS or MTS PLUS
III
Flat
6-tile stack (4 over 2)
5:12
Lugged
6-tile stack (4 over 2)
4:12
Pplystick Tile Pro
Flat or Lugged
6-tile stack (4 over 2)
7:12
P lystick TU Max
Flat
6-tile stack (4 over 2) or 10-tile stack
7:12
Lugged
6-tile stack (4 over 2)
7:12
Lu a
10-ti a stae
612
P
lystick TU P
1
Flat
6-tile stack (4 over 2)
6:12
Lugged
6-tile stack (4 over 2)
4:12
P
I lystick TU Plus
[1
Flat or Lugged
6-tile stack (4 over 2)
7:12
Flat or Lugged
10-tile stack
6:12
Polyflex
G or G FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
Polyflex
SA P or SA P FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
C, LLc. Evaluation Report P12060.02.09-R24
of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-1128
Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018
Page 11 of 14
6.
ONEMOletc.
6A Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements
subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove
any dust and debris prior to application, and prime the substrate (if applicable).
3 3 Elastobase, Elastobase P or Mule -Hide Nail Base:
6.1 Non -Tile Applications:
Shall be installed in compliance with the codified requirements for ASTM D226, Type II underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA
P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Elastoflex S6 G or
Elastoflex S6 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are
those associated with the top -layer underlayment, as set forth in Table 1.
6.3.2 Tile Applications:
Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the "Two
Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with
FRSA/TRI April 2012 (04-12) Installation Manual.
Po stic TS, MTS PLUS, IR-Xe, TLI P, TW Plus TU Ma Dual Pro, Tile'Pro or MU-X_ or Polyflex SAP' Polyflex SAP FR,
—� ;I,l - Ide SA-APP Cap Sheet or Mule -Hide SA -AP ap Sheet (FR);
Shall be installed in compliance with the codified requirements for ASTM D1970 (except Polystick TU P) underlayment
in FBC Table 1507.1.1 for the type of prepared roof covering to be installed.
Direct -to -Deck with Mechanically Fastened Roof Covers:
All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP
Cap Sheet or SA-APP Cap Sheet (FR) should be ac -nai ed in se va ee a seam in actor ante wit Po ass Mu e-
Hi a ac nal m ui a roes. Nal s s a e corrosion resistant, 11 au a nn -s an t e wit a minimum 1-ine
iameter meta is or Sim ex- pe meta ca nai , at a minimum rate o 12 I .c. Polystick TU Plus should be back -
nailed using the above noted fasteners and spacing, in area marked "nail area, area para clavar" on the face of
membrane. The head lap membrane is to cover the area being back -nailed.
All seal -lap seams (selvage laps) must be
firmly rolled with a minimum 28 lb. hand Iff,
aroller to ensure full contact and adhesion. 1 '
For Dual Pro and Tile Pro, align the edge of
the top sheet to the end of the glue pattern
(the sheet will overlap the fabric).
View of Ovelap Seam of Dual Pro and Tile Pro
All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified
Wet/Dry Cement or Polyglass PG500 Modified Cement applied in between the application of the lap.
Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys,
or exposed roof to wall details
-C, I.I.C. Evaluation Report P12060.02.09-1324
ojAuthorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-1128
Polyglass Roof Underlayments, (954) 233-1230 Revision 24: 01/24/2018
Page 12 of 14
(NNEMOjetc.
Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or
Polyglass PG500 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the
Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be
installed in a water shedding manner.
All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a
minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied
for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the
roof that are not accessible to a large roller or broom.
Tile Applications (not allowed for Polystick Dual Pro, IR Xe or Polystick MU X):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions
noted above as a guideline.
For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base
Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1.
For adhesive -set the applications, refer to Section 5.6.4 herein.
Two (2) Ply Underlayment Systems:
Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex
SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with
the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired.
Polystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use
under foam -on tile systems. Limits of use are those associated with the top -layer material. This is not a requirement,
but is allowable if a 2-ply underlayment system is desired.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR:, .
5.1 Elastoflex G TU, Elastoflex S6 G or Elastoflex 56 G FR shall be installed in compliance with current Polyglass published
installation requirements. For use in tile applications:
✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single
Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems or the Hot Asphalt
applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or
adhered the roof systems.
✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply
System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems or the Hot Asphalt
applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or
adhered tile roof systems.
✓ Elastoflex S6 G FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single
Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile
roof systems.
6'5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be fully asphalt -applied to the
substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set
minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt
with asphalt extending approximately 3/8-inch beyond the lap edge.
6�6 Polyflex ;G or Polyflex G FR:
Polyflex G or Polyflex G FR shall be installed in compliance with current Polyglass published installation requirements.
For use in tile applications:
✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened or adhered the roof systems (Base Sheet Limited per 5.6.3).
✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.6.3).
-c, LLC. Evaluation Report P12060.02.09-R24
of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28
Polyglass Roof Underlayments, (954) 233-1230 Revision 24: 01/24/2018
Page 13 of 14
7.
8.
9.
(NNEMOjetc.
2 Polyflex G or Polyflex G FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be
minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end
laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap
edge.
' Tile Staging:
'.1 Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. Refer to
Table 2 herein, and Polyglass published requirements for the staging.
'.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used
on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or sail-
boards, to prevent tile sliding and/or damage to the underlayment during the loading process.
'.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of
roofing tiles is forty-eight (48) hours.
ILDING PERMIT REQUIREMENTS:
required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product.
kNUFACTURING PLANTS:
ntact the noted QA agency for information on product locations covered for F.A.C. 61G20-3 QA requirements. The following
nts have qualified products under their respective physical properties specifications.
i'lant
Specificatiorii,
Product Us
,ernley, NV, Hazleton, PA & Winter Haven, FL
ASTM D1970
Polystick MU-X
,azleton, PA
M-D 13-0004
Elastoflex G TU
'�I azleton, PA & Winter Haven, FL
ASTM D1970
Polystick IR-Xe
ASTM D1970 & FRSA/TRI April 2012
Polystick TU Plus
ASTM D1970 & FRSA/TRI April 2012
Polystick TU Max
Tuscaloosa,
AL
ASTM D4601, Type II
Polyglass G2 Base
inter Haven, FL
ASTM D226 (physicals)
Elastobase, Elastobase P
ASTM D6509
Polyglass APP Base
FRSA/TRI April 2012
Polystick MTS, Polystick MTS PLUS
FRSA/TRI April 2012
Polystick TU P
FRSA/TRI April 2012
Polyflex SAP, Polyflex SA P FR
ASTM D1970
Polystick Dual Pro
ASTM D1970 & FRSA/TRI April 2012
Polystick Tile Pro
ASTM D6164
Elastoflex S6, Elastoflex S6 G FR
ASTM D6222 I
Polyflex G, Polyflex G FR
ASSURANCE ENTITY:
LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com
'C, I.I.C.
of Authorization #32455
- END OF EVALUATION REPORT -
e EDITION (2017) FBC NON-HVHZ EVALUATION
Polyglass Roof Underlayments; (954) 233-1230
Evaluation Report P12060.02.09-R24
FL5259-R28
Revision 24: 01/24/2018
Page 14 of 14