HomeMy WebLinkAboutEVAULATION REPORT ENTEGRA CONCRETE ROOF TILESEXTERIOR RESEARCH & DESIGN, LLC.
YU Certificate of Authorization #9503
TRINITY � ERD 353 CHRISTIAN STREET, UNIT #13
CANNED
OXFORD, CT 06478
(203) 262-9245
EVALUATION REPORT BY
!� Entegra Roof Tile, LLC St. Due OUTI �ij aluation Report E39310.11.11-1-R4
r.NTC-GRA 1289 NE 9" Avenue FL7804-R10
R 0 0 F T I L E Okeechobee, FL 34972 Date of Issuance: 11/02/2011
(602) 515-6933 Revision 4: 10/17/2017
his Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
instruction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
roducts described herein have been evaluated for compliance with the 6t E ition WA F on a 87 In Co e
41;UHZ sections noted herein.
Ente ra Concrete of JT1 iles HVHZ 'uric ictions
Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
:ONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
kcceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
)roduct changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete
-eview of this Evaluation Report relative to updated Code requirements with each Code Cycle.
kDVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
idvertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
NSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
is distributors and shall be available for inspection at the job site at the request of the Building Official.
is Evaluation Report consists of pages 1 through 8.
!pared by:
ert J.M. Nieminen, P.E. -0'�; '=' '":`�.^ Thefacsimile seal appearingwas authorized by Robert Nieminen,
l'S P.E. on l0/17/2017. This does not serve as an electronically signed
is Registration No. 59166, Florida DCA ANE1983 i`. • 5'dpy �11. document Signed, sealed hardcopies have been transmitted to the
r �
�.Uyuiritc�i>>
�'•._ Product Approval Administrator and tothenamed client
IFICATION OF INDEPENDENCE:
TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
This is a building code evaluation. Neither TrinitylERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
QOTRRINITYIERD
NG SYSTEM EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Roofing Tiles
Compliance Statement: Entegra Concrete Roof Tiles, as produced by Entegra Roof Tile, LLC, have demonstrated
compliance with the following sections of the Florida Building Code through testing in accordance with the following
Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth
herein.
2. STANDARDS:
Section
Pro a
Standard
Year
1523.6.5.2
Physical Properties
TAS 112
1995
1523.6.5.2
Wind Driven Rain
TAS 100
1995
1523.6.5.2.2
Static Uplift Resistance
TAS 101
1995
1523.6.5.2:3
Static Uplift Resistance
TAS 102
1995
1523.6.5.2.3
Static Uplift Resistance
TAS 102(A)
1995
3. REFERENCES:
gnifty
Examination
Reference
Date
ERD (TST6049)
TAS 101
P39740.02.12
02/21/2012
ATL (TST3782)
Physical Properties
RT0624.05-14
07/03/2014
ATL(TST3782)
Physical Properties
RT0624.04-14
07/07/2014
ATL(TST3782)
Physical Properties
RT1210.02-15
12/17/2015
ATL(TST3782)
Physical Properties
RT1210.03-15
12/17/2015
ATL (TST 3782)
Physical Properties
RT1103.01-15
11/07/2015
ATL (TST 3782)
Physical Properties
RT1103.02-15
11/07/2015
ATL (TST 3782)
Physical Properties
RT1103.03-15
11/07/2015
ATL (TST 3782)
Physical Properties
RT1103.04-15
11/07/2015
ATL (TST 3782)
Physical Properties
RT1103.05-15
11/07/2015
Miami -Dade (CER1592)
HVHZ Compliance
14-0416.12
11/27/2014
Miami -Dade (CER1592)
HVHZ Compliance
15-0721.04
11/05/2015
Miami -Dade (CER1592)
HVHZ Compliance
16-0112.06
02/25/2016
Miami -Dade (CER1592)
HVHZ Compliance
16-0112.07
02/25/2016
Miami -Dade (CER1592)
HVHZ Compliance
16-0112.08
02/25/2016
Tile Roof Institute
TAS 300, TAS 101, 102, 102(A)
Membership Confirmation
Current
PRI (QUA9110)
Quality Assurance
Service Confirmation
Exp. 11/02/2018
terior Research and Design, LLC.
Evaluation Report E39310.31.11-1-R4
tijicate of Authorization #9503
6T"EDITION (2017) FBC HVHZ EVALUATION
FL7804-R10
Entegra Roof Tiles
Revision 4:10/17/2017
Page 2 of 8
4. PRODUCT DESCRIPTION:
—� 4.1 TAS 112, Type'3a (flat -profile) BERMUDA
16'
T4'
I
10•\ /
Y
f 16'
2'
Bermuda Flat
I�t
13" 1 7-1/4"
Horizon Flat
QOTRINITYIERD
P - Iron Flat
nd HORIZON FLAT
Research and Design, U.C. Evaluation Report E39310.11.11-1-R4
of Authorization #9503 6T" EDITION (2017) FBC HVHZ EVALUATION FL7804-R10
Entegra Roof Tiles Revision 4:10/17/2017
Page 3 of 8
QTPJNI-TYIERD
5. LimrwiONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is for use in FBC HVHZ jurisdictions or others adopting FBC HVHZ requirements.
5.3 Fire classification is not part of this evaluation; refer to FBC 1516 or listing by an approved testing agency for
fire rating of this product.
5.4 Reference is made to FBC 1512.4.2.4 regarding field testing of completed tile roof installations.
5.5 Applicant shall retain the services of an FBC listed, accredited laboratory to perform quarterly tests in
accordance with TAS 112, Appendix'A'.
5.6 Minimum underlayment shall comply with the RAS 118, RAS 119 or RAS 120, as applicable. Underlayment
products shall hold current Florida Statewide Product Approval or Local Approval for use in tile roof
assemblies in FBC HVHZ jurisdictions.
5.7 Minimum roof deck requirements shall be in accordance with applicable FBC HVHZ requirements.
5.8 All products in the roof assembly shall have quality assurance audit in accordance with the F.A.C. Rule
61G20-3.
6. INSTALLATION:
6.1 Entegra Concrete Roof Tiles may be mechanically fastened, mortar -set or adhesive -set. Installation shall
comply with manufacturer's current published instructions, but not less than the requirements of RAS 118,
RAS 119 or RAS 120, as applicable.
6.2 Attachment Calculations: Entegra Concrete Roof Tile shall be evaluated as a 'Moment -Based System' in
accordance with Roofing Application Standard RAS 127-11 using the data outlined herein.
a
j. :. TABLE 1. AERODYNAMIC MULTIPLIERS FT3�
Tile
Batten Application
Direct -Deck Application
Bermuda Flat
0.189
0.205
antation Flat
0.267
0.289
1 Horizon Flat
0.305
0.330
Bella High "S"
0.349
0.378
Estate "S"
0.267
0.289
Hacienda
0.267
0.289
Galena Spanish "S"
N/A
0.235
Regal
0.287
I 0.311
F' TABLE 2: RESTORING MOMENT DUE TO GRAVITY - M(FT-LB'
F)
Roof Slope
(0)
Tile
2:12<0<3:12
3:12<0<4:12
4:12<0<5:12
5:12<0<6:12
6.12<0<7:12
0>7:12
Battens
Direct
Battens
Direct
Battens
Direct
Battens
Direct
Battens
Direct
Battens
Direct
IlBermuda Flat
5.22
6.43
5.17
6.37
5.09
6.27
4.98
6.15
4.86
6.00
4.72
5.83
I antation F at
7.22
7.91
6.85
7.79
6.75
7.67
6.61
7.52
6.44
.33
6.26
7.04
Horizon
7.60
8.32
7.52
8.24
7.41
8.12
7.26
7.95
7.09
7.76
6.89
7.55
JBella High "S"
6.19
6.89
6.11
6.80
5.99
6.67
5.85
6.51
5.68
6.33
5.50
6.13
[,;Estate "S"
6.14
6.84
5.91
6.74
5.82
6.64
5.70
6.50
5.56
6.33
5.40
6.14
I', „Hacienda
5.92
6.80
5.92
6.80
5.82
6.69
5.70
6.55
5.56
6.39
5.41
6.22
Galena Spanish "S"
N/A
6.20
N/A
6.13
N/A
6.03
N/A
5.89
N/A
5.74
N/A
5.57
Regal
7.77
8.34
7.77
8.34
7.65
8.20
7.49 1
8.03 1
7.30
7.83
7.10
7.61
erior Research and Design, U.C.
rtiflcate of Authorization #9503
EDITION (2017) FBC HVHZ EVALUATION
Entegra Roof Tiles
Evaluation Report E39330.11.11-1-R4
FL7804-R10
Revision 4:10/17/2017
Page 5 of 8
ter'"
Q"TRINITYIERD
TACHMENTRSISTANCEXPRESSEDMMF�FT-LBFTABLE �
MECHANICALLY ATTACHED SYSTEMS
Tile
Fastener
Direct -Deck
(min.15/32"
plywood)
Direct -Deck
(min.19/32"
plywood)
Battens
Type
It
Size
Shank
Clip
Nail
One (1)
10d
Smooth or Screw
N/A
7.3
9.8
4.9
Nail
Two (2)
10d
Smooth or Screw
N/A
14.0
18.8
7.4
Nail
One (1)
10d
Smooth or Screw
Eave
19.0
19.0
22.1
Nail
One (1)
10d
Smooth or Screw
Field
24.3
24.3
24.2
Bermuda Flat,
Nail
Two (2)
10d
Smooth or Screw
Eave
31.9
31.9
32.2
P an anon F at or
Nail
Two (2)
10d
Smooth or Screw
Field
35.5
35.5
34.8
Horizon
Nail
Two (2)
10d
Ring
N/A
30.9
38.1
17.2
Nail'
Two (2)'
10d'
Ring1
N/A
50.3'
65.51
48.31
Screw
One (1)
#8
N/A
N/A
30.8
30.8
18.2
-�
crew
w0
#8
N A
N A
51.
51.7
24.4
' Installation with a 4-inch tile headlap and fasteners located min. 2Y2-inch from head of tile.
Nail
One (1)1
10d
Smooth or Screw
N/A
8.82
11.82
4.12
Nail
Two (2)
10d
Smooth or Screw
N/A
16.4
21.9
7.1
Nail
One (1)2
10d
Smooth or Screw
Eave
19.02
19.02
22.12
Nail
One
10d
Smooth or Screw
Field
24.3'
24.31
24.22
Nail
Two (2)
10d
Smooth or Screw
Eave
31.9
31.9
32.2
Estate "S" or Hacienda
Nail
Two (2)
10d
Smooth or Screw
Field
35.5
35.5
34.8
Nail
Two (2)
10d
Ring
N/A
27.8
37.4
28.8
Nail'
Two (2)'
10d'
Ring'
N/A
43.0'
67.5'
50.91
Screw
One (1) 2*
#8
N/A
N/A
25.8 Z
25.8'
22.9'
Screw
Two (2)
#8
N/A
N/A
47.1
47.1
49.1
1Installation with a 4-inch tile headlap and fasteners located min. 2F-inch from head of tile.
1 For one (1) fastener installations, utilize hole that is approximately 4%-inch from the interlocking edge.
Nail
One (1)
10d
Smooth or Screw
N/A
5.1
6.8
2.8
Nail
Two (2)
30d
Smooth or Screw
N/A
6.9
9.2
7.3
Nail
One (1)
10d
Smooth or Screw
Field
23.1
23.1
19.0
Nail
One (1)
10d
Smooth or Screw
Eave
29.3
29.3
24.0
"r
Nail
Two (2)
10d
Smooth or Screw
Field
27.6
27.6
38.6
Bella High
Spanish "S" or Regal Galena
o
Nail
Two (2)
10d
Smooth or Screw
Eave
38.1
38.1
41.8
Nail
Two (2)
10d
Ring
N/A
28.6
41.2
19.4
Nail'
Two (2)1
10d'
Ring'
N/A
33.1'
48.11
50.9'
Screw
One (1)
#8
N/A
N/A
20.7
20.7
18.1
Screw
Two (2)
#8
N/A
N/A
43.2
43.2
29.8
'Installation with a 4-inch tile headlap and fasteners located min. 2X-inch from head of tile.
esign, I.I.C.
#t9503 O EDITION (2017) FBC HVHZ EVALUATION
Entegra Roof Tiles
Evaluation Report E39310.11.11-1-R4
FL7804-R10
Revision 4:10/17/2017
Page 6 of 8
Q0T1mN1TYjERD
TABLE 4T ATTACHMENT RESISTANCE EXPRESSED AS.A MOMENT`—MF (FT-LBF)
..." MORTAR'ANDADHESIVE-SET,SYSTEMS
Note from Entegra Roof Tile,,LLC:, The performance ddta hstedjn Table,4 are based `on the respective,adhesive manufacturers' test
reports and Miami Dade NOAs. Entegra Roof Tile, L!C ,ehes upon the adhesive manufacturers to provide these values for ourinclusion
in this. FBC HVHZ.:Evaluation"Report: Please consult the: individual adhesive manufacturer for information on -product approvals,
limitations, revisions•or other information for determining, wind load and overturning moment performance..
Tile
Tile Adhesive
Mf (ft-lbf)
Product
Product Approval
Placement
"TILE BOND" by Dow Chemical
NOA 16-0222.01
Interdependent (2-paddy)
41
Bermuda
"Touch N' Seal Storm Bond" by DAP Foam
NOA 16-0421.03
Interdependent (2-paddy)
73
Flat,
Plantation
"Polyset" RTA-1" by ICP Adhesives & Sealants
NOA 16-0315.03
Interdependent (2-paddy)
52
Flat or
Horizon
"Polyset® AH-160" by ICP Adhesives &
Sealants
NOA 17-0322.03
Interdependent(2-paddy)
43
Independent (medium paddy, "30 g)
51
Independent (large paddy, —45 g)
92
"TILE BOND` by Dow Chemical
NOA 16-0222.01
Interdependent (2-paddy)
44
"Touch N' Seal Storm Bond" by DAP Foam
NOA 16-0421.03
Interdependent (2-paddy)
42
Estate "S"
"Polyset® RTA-1" by ICP Adhesives & Sealants
NOA 16-0315.03
Interdependent (2-paddy)
44
or
Hacienda
"Polyset® AH-160" by ICP Adhesives &
Sealants
NOA 17-0322.03
Interdependent (2-paddy)
50
Independent (medium paddy, —30 g)
37
Independent (large paddy, —54 g)
61
Mortar
Various
Per RAS 120
21
"TILE BOND TM" by Dow Chemical
NOA 16-0222.01
Interdependent (2-paddy)
48
"Touch N' Seal Storm Bond" by DAP Foam
NOA 16-0421.03
Interdependent (2-paddy)
52
Bella High
"S",
"Polyset® RTA-1" by ICP Adhesives & Sealants
NOA 16-0315.03
Interdependent (2-paddy)
36
Galena
Spanish "S"
or Regal
"Polyset® AH-160" by ICP Adhesives &
Sealants
NOA 17-0322.03
Interdependent (2-paddy)
30
Independent (medium paddy, —30 g)
49
Independent (large paddy, —63 g)
94
Mortar
Various
Per RAS 120
25
7. LABELING:
7.1 Each unit shall bear the imprint and/or identifiable marking of the manufacturer's name or logo, as detailed
below. Tile lots shall be labeled in accordance with the requirements of the Accredited Quality Assurance
Agency noted herein.
and/or
v��7 NT ERR
1\��
Labeling: Bermuda Flat, Plantation Flat, Estate "S", Bella High "S", Galena Spanish "S"
Research and Design, LLG Evaluation Report E39310.31.31-1-R4
ojAuthorizaVon 49503 6T" EDITION (2017) FBC HVHZ EVALUATION FL7804-R10
Entegra Roof Tlles Revision 4: 10/17/2017
Page 7 of 8
TRINITY I ERD
Hanson
Labeling: Horizon Flat, Hacienda, Regal
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Plant ..
Profiles
Okeechobee, FL
Bermuda Flat, Plantation Flat, Estate "S", Bella High "S", Galena Spanish "S"
Ft. Myers, FL
Horizon Flat, Hacienda
Deerfield Beach, FL
Horizon Flat, Hacienda, Regal
10. QUALITY ASSURANCE ENTITY:
PRI Construction Materials Technologies, LLC. — QUA9110; (813) 621-5777
- END OF EVALUATION REPORT —
Research and Design, I.I.C. Evaluation Report E39310.11.11-1-R4
ojAuthorkation #9503 6'" EDITION (2017) FBC HVH2 EVALUATION FL7804-R10
Entegra Roof Tiles Revision 4:10/17/2017
Page 8 of 8