FL14645-R3
Revision
A 2017
Sly�® Approved
1,
Quality Assurance Representative
Address/Phone/Email
Category
Subcategory
Compliance Method
Florida Engineer or Architect Name who developed
the Evaluation Report
Florida License
Quality Assurance Entity
Quality Assurance Contract Expiration Date
Validated By
Certificate of Independence
ST. LUCIE COUNTY
BUILDING DIVISION
REVIEWED
FOR COMPLIAN
REVIEWED BY
DATE -111-Life,
PLANS AND PERMITI
MUST BE KEPT ON JOB OR
NO INSPECTION WILL BE MADE
Metal Sales Manufacturing Corporation
545 South 3rd Street, Suite 200
Louisville, KY 40202
(502) 855-4300
dstermer@metaisales.us.com
David Stermer dstermer@ metalsales. us. cam THESE PLANS ARID ALL PROPOSED WOM
ARE SUBJECT TO ANY COOPIrIC'i IONS"
RCOUiRED SY MLW IPIPc",CTOri$ TnIAT
UY aE NECESI AW IN ORDER TO
il' '°
MaX; Myy"li�h�i�it��la'
Roofing ARE THE RESPONSI810 OF THE
Metal Roofing CONTRACTOR OF RECORD
Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
0( Evaluation Report - Hardcopy Received
Bala Sockalingam
PE-62240
Keystone Certifications, Inc.
12/27/2026
Yoosef Lavi, P.E.
W: Validation Checklist - Hardcopy Received
FL14645 R3 COI CertificateIndependence.pdf
Referenced Standard and Year (of Standard) Standard
Year
FM 4470
2012
TAS 125
2003
UL 1897
2012
UL 580
2006
Equivalence of Product Standards
Certified By
ons-fromthe Code
�'� 1 ° � fg {.• �0 ®rr
'f
Building Code Online
Page 2 of 4
Product Approval Method Method 1 Option D
Date Submitted
09/09/2017
Date Validated
09/1412017
Date Pending FBC Approval
09/15/2017
Date Approved
12/12/2017
Summary of Products
FL #
Model, Number or Name
Description
14645.1
2.5" Corrugated
Min. 26 ga., 21.33" wide coverage through fastened roof
panel over min. 19/32" thick plywood deck.
Limits of Use
Installation Instructions
Approved for use In HVHZ: No
FL14645 R3 IIEvaluationReportC2182_ l.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-86.0
Evaluation Reports
Other: Uplift load of 82.3 psf at fastener spacing of 36" o.c.
FL14645 R3 AE EvaluationReportC2182 1.pdf
and 86.0 psf at fastener spacing of 12" o.c.
Created by Independent Third Party: Yes
14645.2
SV-Crimp
Min. 26 ga., 24 wide through fastened roof panel over min.
19/32" thick plywood deck with fasteners through panel flat.
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645 R3 II EvaluationReportC2182 2.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-149.6
Evaluation Reports
Other: Uplift load of 84.5.psf at fastener spacing of 24' o.c.,
FL14645 R3 AE EvaluationReportC2182 2. pdf
131.3 psf at fastener spacing of 18" o.c, and 149.6 psf at'
Created by Independent Third Party: Yes
fastener spacing of 12" o.c.
14645.3
5V-Crimp
Min. 26 ga., 24" wide through fastened roof panel over min.
19/32" thick plywood deck with fasteners through panel rib.
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645 R3 II EvaluationReportC2182 3.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-196.75
Evaluation Reports
Other: Uplift load of 41.6 psf at fastener spacing of 36" o.c.,
FL14645 R3 AE EvaluationReportC2182_3.pdf
74.8 psf at fastener spacing of 16" o.c. and 196.75 psf at
Created by Independent Third Party: Yes
fastener spacing of 8" o.c.
4645.4
a .?
SV-Crimp u , ==.
.f ..- __
Pfi26 ga., 24 wide through fastened roaf panei aver min:
i5f32' th'7ck Plywood dec or 7JiS" thick OSB'rith fas ene
through.;pane�itr
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL1464f _R3_II EvaluationRgportC2182 4.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-172.5
Evaluation Reports
Other: Uplift load of 30.0 psf at fastener spacing of 36" o.c.
FL14645 R3 AE EvaluationReportC2182 4.pdf
and 172.5 psf at fastener spacing of 6" o.c.
Created by Independent Third Party: Yes
14645.5
Classic Rib
rrr�
Nom. 0.032" thick, 36" wide, aluminum through fastened roof
panel over min. 15/32" thick plywood deck or 7/16" thick
OSB.
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645 R3 II EvaluationReportC2182 S.odf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-120
Evaluation Reports'
Other: Uplift load of 30 psf at fastener spacing of 36" o.c.
FL14645 R3 AE EvaluationReportC2182_S.pdf
and 120 psf at fastener spacing of 6" o.c.
Created by Independent Third Party: Yes
14645.6
Aluminum Vertical Seam
Nom. 0.032" thick, 16" wide, aluminum standing seam roof
panel over min. 15/32" thick plywood deck or 7/16" thick
OSB.
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645_R3_II_EvaluationReportC2182 6.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-97.05
Evaluation Reports
Other: Uplift load of 41.6 psf at clip spacing of 36" ox., 71.0
FL14645 R3 AE EvaluationReportC2182 6.pdf
psf at clip spacing of 12" o.c. and 97.1 psf at clip spacing of
Created by Independent Third Party: Yes
12" o.c. with sidelap adhesive.
14645.7 i Aluminum Vertical Seam
r
/www.floi idabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDDgsw8ZVNfe8A7e... 9/6/2018
Building Code Online Page 3 of 4
Nom. 0.032" thick, 16" wide, aluminum standing seam roof
panel over min. 19/32" thick plywood deck
Limits of Use Installation Instructions
,Approved for use in HVHZ: No FL14645 R3 II EvaluationReportC2182 7.pdf
Approved for use outside HVHZ: Yes • Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A Created by Independent Third Party: Yes
Design Pressure: +N/A/-162.0 Evaluation Reports
Other: Uplift load of 41.6 psf at clip spacing of 36" o.c., FL14645 R3 AE EvaluationReportC2182 7.odf
100.2 psf at clip spacing of 12" o.c. and 162.0 psf at clip Created by Independent Third Party: Yes
spacing of 12" o.c. with support strap.
14645.8
Classic Rib
Min. 29 ga., 36" wide through fastened roof panel over min.
15/32" thick plywood deck.
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645 R3 IT EvaluationReportC2182 8.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-91
Evaluation Reports
Other: Uplift load of 41.5 psf at fastener spacing of 48" o.c.
FL14645 R3 AE EvaluationReportC2182 8.pdf
and 91 psf at fastener spacing of 6" o.c.
Created by Independent Third Party: Yes
14645.9
Classic Rib
Min. 26 ga., 36" wide through fastened roof panel over min.
19/32" thick plywood deck.
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645 R3 II EvaluationReportC2182_g.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-133.9
Evaluation Reports
Other: Uplift load of 74.8 psf at fastener spacing of 36" o.c.,
FL14645 R3 AE EvaluationReportC2182 9.pdf
92.3 psf at fastener spacing of 24" o.c. and 133.9 psf at
Created by Independent Third Party: Yes
fastener spacing of 18" o.c.
14645.10
Classic Rib
Min. 29 ga., 36" wide through fastened roof panel over min.
7/16" thick OS deck
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645 R3 II EvaluationReportC2182 10,pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-135.0
Evaluation Reports
Other: Uplift load of 45 psf at fastener spacing of 24" o.c.
FL14645 R3 AE EvaluationReportC2182 10.pdf
and 135 psf at fastener spacing of 6" o.c.
Created by Independent Third Party: Yes
14645.11
Classic Rib
Min. 29 ga., 36" wide through fastened roof panel over min.
15/32" thick plywood deck.
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645 R3 II EvaluationReoortC2182 k1.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-138.5
Evaluation Reports
Other: Uplift load of 68.4 psf at fastener spacing of 24" o.c.
FL14645 R3 AE EvaluationReportC2182 11.pdf
and 138.5 psf at fastener spacing of 12" o.c.
Created by Independent Third Party: Yes
14645.12 Image II Min. 26 ga., 16" wide concealed fastened roof panel over min.
15/32" thick plywood deck or 7/16" thick OSB.
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL14645 R3 II EvaluationReportC2182 12.pdf
Approved for use outside HVHZ: Yes Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A Created by Independent Third Party: Yes
Design Pressure: +N/A/-86.55 Evaluation Reports
Other: Uplift load of 20.8 psf at fastener spacing of 24" o.c., FL14645 R3 AE EvaluationReportC2182 12.pdf
63.5 psf at fastener spacing of 6" o.c. and 86.55 psf at Created bydndependent Third Party: Yes
fastener spacing of 6" o.c. with sidelap adhesive.
14645.13
PBR-Panel or R-Panel
Min. 26 ga., 36" wide through fastened roof panel over min.
15/32" thick plywood deck.
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645 R3 II EvaluationReoortC2182 13.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: +N/A/-131.0
Evaluation Reports
Other: Uplift load of 30.0 psf at fastener spacing of 48" o.c.
FL14645 R3 AE Evaluation ReportC2182 13.pdf
and 131.0 psf at fastener spacing of 6" o.c.
Created by Independent Third Party: Yes
14645.14
Pro -Panel II
Min. 29 ga., 36" wide through fastened roof panel over min.
15/32" thick plywood deck.
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL14645_R3_II_EvaluationReportC2182_14.pdf
Approved for use outside HVHZ: Yes
Verified By: Bala Sockalingam PE 62240
Impact Resistant: N/A
Created by Independent Third Party: Yes
'/www.floridabuil ding. org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgsw8Z VNfe8A7e... 9/6/2018
Fl °rida Building Code Online Page 4 of 4
Design Pressure: +N/A/-71.5 I Evaluation Reports
Other: Uplift load of 41.6 psf at fastener spacing of 24" D.C. FL14645 R3 AE EvaluationReportC2182 14.odf
i
and 71.5 psf at fastener spacing of 12" o.c. Created by Independent Third Party: Yes
Back Next
i
I contact Us :: 2601 Blair Stone Road. Tallahassee FL 32399 Phone: 850-487-1824
I
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida.:: Privacy Statement:: Accessibility Statement :: Refund Statement
Under Florida lave, email addresses are public records. If you do not want your e-mail address released in response to a public -records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. 'Pursuant to Section 455.275
(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address If they have one. The
emails provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personal address,
please provide the Department with an email address which can be made available to the public. To determine if you are a licensee under Chapter 455, F.S., please
click here.
Product Approva l Accepts:
'1fL' El FqA sCIK:I 0
Credit Card
Safe
I
I
I
i
i
I
I
I
I
I
h '-//www.floridabuilding.org/pr/pr app_dtl.aspx?param=wGEVXQwtDgsw8ZVNfe8A7e... 9/5/2018
EVALUATION REPORT OF
METAL SALES MANUFACTURING CORPORATION
`26 GA. 5V-CRIMP PANEL'
FLORIDA BUILDING CODE 6TH EDITION (2017)
FLORIDA PRODUCT APPROVAL
FL 14645.4-R3
ROOFING
METAL ROOFING
Prepared For:
Metal Sales Manufacturing Corporation
545 South 3rd Street, Suite 200
Louisville, KY 40202
Telephone: (502) 855-4300
Fax: (502) 855-4290
Prepared By:
Bala Sockalingam, Ph.D., P.E.
Florida Professional Engineer #62240
1216 N Lansing Ave., Suite. C
Tulsa, OK 74106
Telephone: (918) 492-5992
FAX: (918) 493-3568
This report consists of
Evaluation Report (3 Pages including cover)
ezjaeeirsa
Installation Details (1 Page) ,�%e®®�50CKA jNa��®�
Load Span Table (I Page) ,ob �,�;.• .G E°N S •-1
No 62240
�• ; w
Report No. C2182-4 �'. STATE Of -
Date: 9.9.17 °,��` e� O R 1 P° ���m,
o�
e
FL 14645.4-R3
Manufacturer:
Product Name:
Panel Description
Materials: ;
C2182-4
9.9.17
Page 2 of 3
Metal Sales Manufacturing Corporation
5V-Crimp
24" wide coverage with (5) 1/2" high ribs
Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or
Galvalume coated steel (ASTM A792) or painted steel (AST1bI A755)..
Deck Description: Min. 7/16" thick ®SB or min. 15/32" thick plywood or min. 3/" thick
wood plank (min SG of 0.42) for new and existing constructions.
Designed by others and installed as per FBC 2017.
Deck Attachment: 8d x 2.5" long ring shank nails or 98 x 2" long wood screws a 6" o.c.
(Minimum) in the plywood field and edges. Designed as per FBC 2017.
Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1.
Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2.
Requires applied lap sealant for roof slopes less than 3:12.
Design Uplift Pressure: 30.0 psf @ fastener spacing of 36" o.c.
(Factor of Safety = 2) 172.5 psf @ fastener spacing of 6" o.c.
]Fastener Pattern:
Type: 49-16 or 910-14 hex head wood screws with sealed washer. Fastener
shall be of 'sufficient length to penetrate through the deck a minimum
of 3/8" and installed as per Metal Sales current installation procedure.
At panel ends @ 6" o.c. across panel width
At intermediate @ 12" o.c. across panel width
Test Standards: Roof assembly tested in accordance with UL580-06 `Uplift Resistance
of Roof Assemblies' & UL1897-04 `Uplift Tests for Roof Covering
Systems'.
Test Equivalency: The test procedures in UL 1897-04 comply with test procedures
prescribed in UL 1897-12.
Code Compliance: The product described herein has demonstrated compliance with FBC
2017 Section 1507.4.
Product Limitations: Design wind loads shall be determined for each project in accordance
with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress
design. The maximum fastener spacing listed herein shall not be
exceeded. The design pressure for reduced fastener spacing may be
FL 14645.4-R3
C2182-4
9.9.17
Page 3 of 3
computed using rational analysis prepared by a Florida Professional
Engineer or based on Metal Sales load span table. This evaluation
report is not applicable in High Velocity Hurricane Zone. Fire
classification is not within scope of this Evaluation Report. Refer to
FBC 2017 Section 1505 and current approved roofing materials
directory or ASTM E108AJL790 report from an accredited laboratory
for fire ratings of this product.
Supporting Documents: UL580 & 1897 Test Reports
PRI Construction Materials Technologies
MSMC-017-02-01, Reporting Date 9/20/13
PANEL OVERLAP
5V-CRIMP
SEE DETAIL 2 / /-SEE DETAIL 1
FASTENER AT PANEL FLAT
REQUIRED FOR PANEL
ENDS ONLY.
/
u
PANEL FASTENER PER UPLIFT
MINIMUM ATTACHMENT: LOAD TABLE
x
8d x 2.5" LONG RING SHANK NAIL
UNDERLAYMENT SHALL BE INSTALLED
OR #8 x 2" LONG WOOD SCREWS
AS PER MANUFACTURER'S INSTALLATION
SPACED 0 5" O.C. IN THE FIELD
GUIDELINES
& AT EDGES
#9-16 OR #10-14 WOODSCREWS
WITH SELF SEALING WASHER AT
MAXIMUM SPACING OF 36" O.C.
UNDERLAYMENT
DETAIL 1
#9-16 OR #10-14 WOODSCREWS
WITH SELF SEALING WASHER AT
MAXIMUM SPACING OF 36" O.C.
`- MIN. 2X- WOOD RAFTER/JOIST/
TRUSS AT MAX. 24" O.C.
o
TYPICAL PANEL INSTALLATION X—SECTION
0
Z Na
K �Np
Np0
}�}M
D NYC
pLa
MJ�
j N
!n
5V-CRIMP
MIN 26 GA._
53 0
Np
Ln
+L
GENERAL NOTES:
w
d
a 7
1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE
\—OSB
= 1
FLORIDA BUILDING CODE (FBC).
THICK 2. ROOF PANELS SHALL BE MIN. 26 GA. (t = 0.019"). EFFECTIVE COVERING
i$
a
7/16' (MIN.) OR
PLYWOOD 15/32" THICK (MIN.) WIDTH OF PANEL = 24'.
U
a
3. THE ROOF PANELS SHALL BE INSTALLED OVER SHEATHING & STRUCTURE AS
SPECIFIED ON THIS DRAWING.
4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS
PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LOADS
ARE GREATER THAN THE DESIGN UPLIFT PRESSURES SPECIFIED ON THIS DRAWING.
!t
5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING & THE FLORIDA
BUILDING CODE. IF A DIFFERENCE OCCURS BETWEEN THE MINIMUM
REQUIREMENTS OF THIS DRAWING & THE CODE. THE CODE SHALL CONTROL
5V-CRIMP 6. RAFTERS/JOISTS/TRUSSES MUST BE DESIGNED TO WITHSTAND WIND LOADS AS
MIN 26 GA. REQUIRED FOR EACH APPLICATION AND ARE THE RESPONSIBILITY OF OTHERS.
,4
UNDERLAYMENT —1
OSB 7THICK (MIN.) OR
DETAIL 2
PLYWOOD OD 15/32 THICK (MIN.)
1 OF 1
METAL SALES MANUFACTURING CORPORATION -
5V-Crhnp Uplift Loads
(Mn. 26 ga.)
Description
Fastener Spacing
Allowable Uplift
along panel length
Load
(in)
(Psfl
Coverage width: 24"
_ 6
172.5 -
9
- � 120.0
12
90.0
_
15
Panel Fasteners
72.0
#9-16 or #10-14 hex head
�_- --1 g -T -
-� 60.0
wood screws with sealed
21._.
51.4
washer
45.0
-__— _._ 24
27
40.0
30
36.0
33
32.7
36 _ .—
30.0
otes:
The bold numbers indicate design loads calculated from test data with safety factor of 2.
Panels must be installed as per Evaluation Report FL 14645.4 and Metal Sales current installation procedure.
. Three or more spans condition.
216 N Lansing Ave., Suite C
ulsa, Ok 74106
18 4922 5992
j%%jil'aara
G E Al
No 62240 .Pei
4 # u
a > •°7 j �O
Q'• STATE OF ,o•44,
$fl _
Bala Sockalingam, Ph.D., P.E.