HomeMy WebLinkAboutEVALUATION REPORT ROOFING0 ft EVALUATION REPORT OF METAL SALES MANUFACTURING CORPORATION '26 GA. 5V-CRIMP PANEL' FLORIDA BUILDING CODE 6TH EDITION (2017) FLORA PRODUCT APPROVAL FL 14645.4-R3 ROOFING METAL ROOFING Prepared For: Metal Sales Manufacturing Corporation 545 South 3rd Street, Suite 200 Louisville, KY 40202 Telephone: (502) 855-4300 Fax: (502) 855-4290 Prepared By: Bala Sockalingam, Ph.D., P.E. Florida Professional Engineer #62240 1216 N Lansing Ave., Suite C Tulsa, OK 74106 Telephone: (918) 492-5992 FAX: (918) 493-3568 SCANNED By Sf. Lucie CORN This report consists of Evaluation Report (3 Pages including cover) ItI1eieeaee Installation Details (1 Page) �0%%-'SoCKAL�9 � ss Load Span Table (1 Page) �`o•�QP.��G 4 E N gF•�?'y,� ooB ro� b No 62240 a Report No. C2182-4 ®, STATE OF . . p . 0. Date: 9.9.17 <st�`s • o R ALE e `t C>(-7 ff FL 14645.4-R3 C2182-4 9.9.17 Page 2 of 3 Manufacturer: Metal Sales Manufacturing Corporation Product Name: 5V-Crimp Panel Description: 24" wide coverage with (5) 1 /2" high ribs Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). Deck Description: Min. 7/16" thick OSB or min. 15/32" thick plywood or min. 3/4" thick wood plank (min SG of 0.42) for new and existing constructions. Designed by others and installed as per FBC 2017. Deck Attachment: 8d.x 2.5" long ring shank nails or #8 x 2" long wood screws @ 6" o.c. (Minimum) in the plywood field, and edges. Designed as per FBC 2017. Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1. Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2. Requires applied lap sealant for roof slopes less than 3:12. :Design Uplift Pressure: 30.0 psf @ fastener spacing of 36" o.c. (Factor of Safety = 2) 172.5 psf @ fastener spacing of 6" o.c. Fastener Pattern: Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener shall :be of sufficient length to penetrate through the deck a minimum of 318" and installed as per Metal Sales current installation procedure. At panel ends @'6" o.c. across panel width At intermediate @ 12" o.c. across panel width Test Standards: Roof assembly tested in accordance. with UL580-06 `Uplift Resistance of Roof Assemblies' & UL1897-04 `Uplift Tests for Roof Covering Systems'. Test Equivalency: The test procedures in UL 1897-04 comply with test procedures prescribed in LL 1897-12. Code Compliance: The product described .herein has demonstrated compliance with FBC 2017 Section 1507.4. Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress design. The maximum fastener spacing listed herein shall not be exceeded. The design pressure for reduced fastener spacing may be directory or ASTM E108%UL790 report from an accredited laboratory foftatings of this product. Supporting Documents: UL580 & 1897 Test Reports PRI Construction Materials Technologies MSMC=017-02-01, Reporting Date 9/20/13 FL 14645.4-R3 C2182-4 9.9.17 Page 3 of 3 computed using rational analysis prepared by a Florida, Professional j Engineer or based on Metal Sales load span table. This evaluation 1 report is not applicable in High Velocity Hurricane Zone. Fire ! classification is not within scope of this Evaluation Report. Refer to FBC 2017 Section 1505 and current approved roofing materials PANEL OVERLAP 5V-CRIMP SEE DETAIL 2 SEE DETAIL 1 #9-16 OR #10-14 WOODSCREWS WITH SELF SEALING WASHER AT MAXIMUM SPACING OF 36" O.C. FASTENER AT PANEL FIAT REQUIRED FOR PANEL ENDS ONLY. MINIMUM ATTACHMENT: 8d x 2.5" LONG RING SHANK NAIL UNDERLAYMENT SHALL BE INSTALLED OR #8 x 2" LONG WOOD SCREWS AS PER MANUFACTURER'SINSTALLATION SPACED ® 6" O.C. IN THE FIELD GUIDELINES & AT EDGES MIN. 2X- WOOD RAFTER/JOIST/ TRUSS AT MAX. 24" O,C, TYPICAL PANEL INSTALLATION X—SECTION 5V-CRIMP MIN 26 GA. PANEL FASTENER PER UPLIFT LOAD TABLE d 0 0 u N CD co =No zs ii 2 M J 00 y x o V) (nJ a to a VOSB I=FNERAL NOTES: 1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE (FBC). 2. ROOF PANELS SHALL BE MIN. 26 GA. (t = 0.019"). EFFECTIVE COVERING IF 'L = ° " b om ^< UNDERLAYMENT 7/16" THICK (MIN.) OR � q THICK (MIN.) DETAIL I PLYWOOD 15/32 WIDTH OF PANEL = 24". 3. THE ROOF PANELS SHALL BE IN OVER SHEATHING &STRUCTURE AS Q I z SPECIFIED. ON THIS DRAWING. 4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS n PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LOADS - N m m 9-16 OR �10-14 WOODSCREWS 'AT ITH SELF. SEALING WASHER'AT ARE GREATER THAN THE. DESIGN UPLIFT PRESSURES SPECIFIED ON THIS DRAWING. 5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING & THE FLORIDA OCCURS BETWEEN THE MINIMUM & z R MAXIMUM' SPACING OF 36" BUILDING CODE. IF A DIFFERENCE REQUIREMENTS OF IE CODE SHALL �TOHWI S 6. RAFTERS/JOISTS/TRUSSES MOST BE DESIGNED TO,WITHSTAND WIND LOADSAS MIN 2RIMGA REQUIRED FOR EACH APPLICATION AND ARE THE OF OTHERS. UNDERLAYMENT \--OSB 7/16" THICK (MIN.) OR sneET i DETAIL 2 PLYWOOD 15/32THICK (MIN.) OF METAL SALES MANUFACTURING CORPORATION 5V-Crimp. Uplift -Loads (Min. 26 ga.) Description Fastener Spacing along panel length () Allowable Uplift Load (psfl Coverage width: 24" Panel Fasteners 99-16 or #10-14 hex head wood screws with sealed washer 6 172.5 g _ 120,0 15 72.0 18 60.0 21 51.4 24 45.0 27 40.0 -- 30 36.00___.. 32.7 33 36 30.0 Notes: L The bold numbers indicate design loads calculated from test data with safety factor of 2. 2. Panels must be installed as per Evaluation Report FL 14645.4 and Metal Sales current installation procedure. 3. Three or more spans condition. 1216 N Lansing Ave., Suite C Tulsa, Ok 74106. 918 492 5992 'gtiaaseleteee��ee� SO.CKgL� °'ae .N s, �4LQ2��•�'�GENSF••O'9 fss • No 62240 ell � • n •. � 4 �� :• STATE OF 44/ 'dAN 0 fi! Bala Sockalingam, Ph.D., P.E. FL 62240