EV ,�LUATION REPORT
Owens ns Corning Evaluation Report 037940.02.12-R8
On Owens Corning Parkway F1.10674-1113
Tolt o, OH 43659 Date of Issuance: 02/06/2012
(74 i ) 404-7829 Revision 8: 10/09/2017
SCOPE:
Thi$ Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
cor) truction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
pro, ucts described herein have been evaluated for compliance with the eh Edition (2017) Florida Building Code
se Pions noted herein.
LAeI�LING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
her in and FBC 1507.2.7.1 / R905.2.6.1.
COI INUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
ref; .Ire Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acc ptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
pro' uct changes or the referenced Quality Assurance documentation changes. TrinityJERD requires a complete
rev w of this Evaluation Report relative to updated Code requirements with each Code Cycle.
AD ERTISEMENT: The Evaluation Report number preceded by the words "Trinity) ERD Evaluated" may be -displayed in
ad iertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSF�cnON: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its t,�istributors and shall be available for inspection at the job site at the request of the Building Official.
Evaluation Report consists of pages 1 through 8.
ared by:
t J.M. Nieminen, P.E.
Registration No_ 59165, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert
Nieminen, RE on 10/09/2017. This does not serve as an
electronically signed document
CER FICATION OF INDEPENDENCE: i
1. TrinityIERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing,products for
i which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
Lil
�I
4.1
\I I KINITY I ERD
SYSTEMS EVALUATION:
SCOPE:
Product Category: Roofing
Sub -Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles, as produced by Owens Corning, have demonstrated
compliance with the following sections of the 6th Edition (2017) Florida Building Code and Florida Building Code,
Residential Volume through testing in accordance with the following Standards. Compliance is subject to the
Installation Requirements and Limitations / Conditions of Use set forth herein.
STANDARDS:
Section
Property
Standard
Year
1507.2.5, R905.2.4
Physical Properties
ASTM D3462
2010
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D3161
2016
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D7158
2011
REFERENCES:
Entity
Examination
Reference
Date
UL LLC (CER9626)
Physicals & Wind Resistance'
File R2453, Vol. 3
02/15/2007
UL LLC (CER9626)
Physicals & Wind Resistance
20120516-112453
05/16/2012
UL LLC (TST9628)
Physical Properties
06CA20263
04/18/2006
UL LLC (TST9628)
Wind Resistance
11CA34308
02/18/2012
UL LLC (TST9628)
Physicals & Wind Resistance
4786093137
02/01/2014
UL LLC (TST9628)
Wind Resistance
4786126532
02/10/2014
UL LLC (TST9628)
Physical Properties
Classification letter
02/13/2014
UL LLC (TST9628)
Physical Properties
Classification letter
10/02/2015'
Miami -Dade (CER1592)
FBC HVHZ Compliance
Various NOAs
Various
UL LLC (QUA9625)
Quality Control
Service Confirmation
Exp. 05/16/2020
PRODUCT DESCRIPTION:
4.1.1 Classic and Supreme are fiberglass reinforced, 3-tab asphalt roof shingles.
4.1.2 Berkshire are fiberglass reinforced, 4-tab asphalt roof shingles.
4.1.3 Devonshire m are fiberglass reinforced, 5-tab asphalt roof shingles.
® Duration', TruDefinitioe Duration® Duration' Premium Cool, TruDefinition' Duration® Designer Color
Collection, TruDefinition®Oakridge • and WeatherGuard® HP are fiberglass reinforced, laminated
asphalt roof shingles.
4.2 Hip & Ridge Shingles:
4.2.1 Berkshire Hip & Ridge Shingles, High Ridge, WeatherGuard® HP Hip & Ridge Shingles, ProEdge Hip & Ridge
Shingles and DuraRidge" Hip & Ridge Shingles are fiberglass reinforced, hip and ridge asphalt roof shingles.
4.3 Accessory Starter Strips:
4.3.1 Starter Strip Shingle, Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles.
LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory
for fire ratings of this product.
Research and Design, U.C. Evaluation Report 037940.02.12-118
e ofAuthoraotion #9503 6EDITION (2017) FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Coming Asphalt Roof Shingles Revision 9:10/09/2017
Page 2 of 8
t i
TRINITY j ERD
5.4 Wind. Classification:
5.4.1 All Owens Corning asphalt shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable
for use in all wind zones up to Vasd = 150 mph (V,,,t = 194 mph). Refer to Section 6 for installation
requirements to meet this wind rating.
5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are
Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F, indicating the
shingles are acceptable for use in all wind zones up to Vasd =150 mph (V„ It =194 mph). Refer to Section 6 for
installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies to exposure category B or C, as defined in FBC 1609.4.3, and a mean
roof height of 60 feet or less. Calculations by a qualified design professional are required for conditions
outside these limitations. Contact the shingle manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule 61G20-3.
INSTALLATION:
6.1 Underlayment-
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product
Approval, or be Locally Approved per Rule 61620-3, per FBC 1507.2.3,1507.2.4 or R905.2.3.
6.2 Asphalt Shineles-
6.2.1 Installation of asphalt shingles shall comply with the Owens Corning current published instructions, using
minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following
exceptions:
➢ Berkshire shingles require minimum five (5) nails per shingle.
➢ WeatherGuard®HP shingles require minimum six (6) nails per shingle.
➢ Devonshire TM shingles require minimum six (6) nails per shingle.
➢ Starter Strip Shingle and Starter Strip Plus require minimum five (5) nails per strip.
Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. See figures below for details.
6.2.5 Minimum Nailing — Starter Strip Shingle and Starter Strip Plus:
Felt underlayment Deck
Sell -adhered
WeatherLock°
underlayment
Dr Drip edge
9
Nails located
2"-r from eave
Install fnst Self-sealing adhesive
Starter Str�ipp positioned along eave
shingle vuilh
Ir removed
Starter Strip shingle overhangs eaves and rakes 'h =i'a
Felt ondedayment Deck Selkdhered
weathertack8
undedayment
Dr Drip edge
edge
Naffs located
Z`41' from eave
Ustal first Starter Strip MIS Self eearmg adhesive
widr Ir mmoved positiaud aMng eave
stMerStnPPbsoverimsseaves and rakes 114 V4"
Research and Design, U.C. Evaluation Report 037940.02-U-R8
r ojAuthorization J19503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL10674-1113
Owens Corning Asphalt Roof Shingles Revision 9:10/09/2017
Page 3 of 8
4 Nail Pattem
Esquema con 4 clavos
r r
I<— it rr
55/6"Exposure Nam 5516"Exposu!
FVw1dmt de SS/8pu14• cfauos l xposidb de 55/0pulg
Standard Fastening Pattern
6.2.1 Minimum Nailing — WeatherGuard® HP:
V TRINITY I ERD
8 Nail Patter
Esgaema con 6'clavos
r r
IF- � � {E— rr —i►{
lls
5 5W Expo4uR Maws 5 5f8" ExposuR
FxposWn de 55/8pufg Exposiddn de 5618 ping
6-Nail Fastening Pattern
s ingle Side Wow
Wh" Affft"W
: :ass :;ti Rolm e71nou Nd L!„r
Ciw� mirydsq=
for Research and Design, U.C. Evaluation Report 037940.02.12-R8
cafe ofAuthariration #9503 6EDITION (2017) FBC NON-HVHZ EVALUATION FL10674-R13
Owens Corning Asphalt Roof Shingles Revision 8, 20/09/2017
Page 6 of 8
Prevailing
Wind Direction Saelant Strip
AA/ 6° Exposure
Fasten 7yi
Cover Exposed
Fasteners with
Roof Cement
�i I RINITY I ERD
Standard
Fastening
Pattern
12°
Sealant
I
7tJz"
6° Exposure
1
6.3.6. Minimum Nailing — DuraRidgeTm Hip & Ridge Shingles:
Note: The drawings below pertain to minimum, as -tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
Prayaiing Wind Diractim
4- Dir9cdDndarniiontadirant
Diracdondal wiwpradarnimnta
Naito —a
a4at� 1 1
9
I I
f i J
A
Top Vlew
Yue en plan
II- ystawperfor
cl u
2 SAr j orrcnsComing snRNaa• c01O
I
I
l o,
ala d.
alm
Ulu
r
7.1
LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1 / R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9.' MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 QA
requirements.
10' QUALITY ASSURANCE ENTITY:
UL LLC—QUA9625; (631) 546-2458; Kanchi.Agrawala-Dokania@ul.com
END OF EVALUATION REPORT -
or Research and Design, LLC. Evaluation Report 037940.02-U-118
�ateofAu1110riz0t9on k9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 8 of 8