1. SCOPE:
Product Category:
Roofing
Sub -Category:
Modified Bitumen Roof Systems
Compliance Statement:
TRI-BUILT Modified Bitumen
Roof Systems, as produced
by TRI-BUILT Materials Group,
LLC, have demonstrated
compliance with the following sections of the 6th
Edition (2017) Florida Building Code
through testing in accordance with the following Standards.
Compliance is subject to the Installation Requirements
and Limitations / Conditions of Use set forth herein_
2. STANDARDS:
Section
Property
Standard
Year
1504.3.1
Wind
FM 4474
2011
1504.7
Impact
FM 4470
2012
1S07.11.2
Physical Properties
ASTM D6163
2008
1507.11.2
Physical Properties
ASTM D6164
2011
1507.11.2
Physical Properties
ASTM D6222
2011
3. REFERENCES:
Enifty
Examination
Reference
Date
ERD (TST6049)
Physical Properties
P10490.10.08-2
10/30/2008
ERD (TST6049)
FM 4470/4474
P13760.09.09
09/10/2009
ERD (TST6049)
FM 4470/4474
P13770.09.09
09/10/2009
ERD (TST6049)
FM 4470/4474
P30540.11.09-R1
11/30/2009
ERD (TST6049)
FM 4470/4474
P30550.12.09
12/02/2009
ERD (TST6049)
Physical Properties
P33960.12.10
12/30/2010
ERD (TST6049)
FM 4470/4474
P33970.03.11
03/1S/2011
ERD (TST6049)
Physical Properties
P37S90.03.13-3A
03/06/2013
ERD (TST6049)
FM 4470/4474
P39680.03.13
03/04/2013
ERD (TST6049)
Physical Properties
P37590.03.13-1-R1
06/26/2013
ERD (TST6049)
Physical Properties
P37590.03.13-2-R1
07/01/2013
ERD (TST6049)
Physical Properties
P37590.07.13-2
07/01/2013
ERD (TST6049)
Physical Properties
P37590.03.13-5-R1
07/01/2013
ERD (TST6049)
Physical Properties
P37590.07.13-1
07/02/2013
ERD (TST6049)
Physical Properties
P4594b.09.13
09/04/2013
ERD (TST6049)
Physical Properties
P44370.10.13
10/04/2013
FM Approvals (TST1867)
FM 4470
2W7A7.AM
08/04/1994
FM Approvals (TST1867)
FM 4470
'ODBA3.AM
04/04/1997
FM Approvals (TST1867)
FM 4470
2DOAO.AM
12/23/1998
FM Approvals (TST1867)
FM 4470
2D5A9.AM
06/22/1999
FM Approvals (TST1867)
FM 4470
3006646
01/04/2000
FM Approvals (TST1867)
FM 4470
3001334
01/25/2000
FM Approvals (TST1867)
FM 4470
3001334
02/15/2000
FM Approvals (TST1867)
FM 4470
3000857
01/12/2000
FM Approvals (TST1867)
FM 4470
3004091
01/12/2000
FM Approvals (TST1867)
FM 4470
3006115
05/02/2001
FM Approvals (TST1867)
FM 4470
3012321
07/29/2002
FM Approvals (TST1867)
FM 4470
3014692
08/05/2003
FM Approvals (TST1867)
FM 4470
3014751
08/27/2003
FM Approvals (TST1867)
FM 4470
3007170
01/13/2004
FM Approvals (TST1867)
FM 4470
3019317
06/30/2004
FM Approvals (TST1867)
FM 4470
3020703
07/30/2004
FM Approvals (TST1867)
FM 4470/4474
3018332
01/31/2006
FM Approvals(TST1867)
FM 4470/4474
3023368
03/20/2006
FM Approvals (TST1867)
FM 4470/4474
3024594
05/23/2006
Exterior Research and Design, LLC. Evaluation Report A42970.10.12-R2
Certificate afAuthorization #9503 6 SEDITION(2017)FBCNON-HVHZEVALUATION FL16027-R2
TRI-BUILT Modified Bitumen Roof Systems, (800) 516-1485 Revision 2: 09/25/2017
o�....o ..Fw
I
Enti
Examination
Reference
FM Approvals (TST1867)
FM 4470/4474
3023458
FM Approvals (TST1867)
FM 4470/4474
3030668
FM Approvals (TST1867)
FM 4470/4474
3032172
PRI (T5T5878)
Physical Properties
PUSA-062-02-01
PRI (T5T5878)
Physical Properties
PU5A-061-02-02
PRI (TST5878)
Physical Properties
PUSA-064-02-02
PRI (TST5878)
Physical Properties
PUSA-062-02-02
Miami -Dade (CER1592)
HVHZ Compliance
Various NOAs
Miami -Dade (CER1592)
Proposal for Review
10-0823
UL LLC (QUA9625)
Quality Control
ML Agreement
UL LLC (QUA9625)
Quality Control
ML Correlation, R27202
UL LLC (QUA9625)
Quality Control
Service Confirmation, R14571
TRINITY ERD
Date
07/18/2006
09/12/2007
06/12/2009
12/04/2007
01/28/2008
02/27/2008
12/04/2008
Various
10/12/2010
02/27/2012
08/20/2012
Exp.10/06/2018
4. PRODUCT DESCRIPTION:
This Evaluation Report covers TRI-BUILT Modified Bitumen Roof Systems installed in accordance with TRI-BUILT
Materials Group, LLC published installation instructions and the Limitations / Conditions of Use herein. The
following membranes make up the subject systems_
Table 1: it6ll-Go0-ds for TRI-BUILT Modified B1tdrsien`R6iif5ystems'
Type
Product
Specification
Reference
Grade
Type
SBS Membranes
TriBuilt SA 5135 Base
ASTM D6163, Table 2
5
1
TriBuilt SBS Granular
ASTM D6164
G
I
TriBuilt SA SBS Cap
ASTM D6164
G
I
APP Membranes
TriBuilt APP Smooth
ASTM D6222
5
I
TriBuilt APP Granular
ASTM D6222
G
I
TriBuilt SA APP Cap
ASTM D6222
G
I
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinitylERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Refer to a current Approved Roofing Materials Directory for fire ratings of this product.
5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance
with FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply.
5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural
members shall be in accordance with FBC requirements to the satisfaction of the Authority Having
Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC,
Agprcival.clocumentation_ _3---- —��" - _
5.7 Fo�'mecha'nically attached'ins9lation or membrane'-o s np- onded insulation, the maximum design pressure
for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with
FBC Chapter 16. Zones 2 and 3 shall employ an attachment density designed by a qualified design.
professional to resist the elevated pressure criteria_ Commonly used methods are ANSI/SPRI WDl, FM Loss
Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS
137. Assemblies marked with an asterisk" carry the limitations set forth in Section 2.2.10.1 of FM Loss
Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
ExtErior Re -search and Design, LLC. Evaluation Report A42970.10.12-112
Certificate of Authorization #9503 o'" EDITION (2017) FBC NON-HVHZ EVALUATION FL16027-R2
TRI-RIIILT ModiflPri Ritumon Rnnf SvctPmr. 19001 916-1ARS Revisinn 2: 09/25/2017
11
TRINITY ERD
5.8 For assemblies with all -components fully bonded in place, the maximum design pressure for the selected
assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No
rational analysis is permitted for these systems.
5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the
existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison
to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI
FX-1 or Testing Application Standard TAS 105.
5.10 For bonded insulation or membrane over existing substrates in a re -roof (tear off) or recover installation, the
existing deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If
any surface conditions exist that bring system performance into question, field uplift testing in accordance
with ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS
124 shall be conducted on mock-ups of the proposed new roof assembly.
5.11 For bonded insulation or membrane over existing substrates in a recover installation, the existing roof
system shall be capable of resisting project design pressures on its own merit to the satisfaction of the
Authority Having Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM
Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with
FBC Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or Roofing Application Standard
RAS 111, except the basic wind speed shall be determined from FBC Figure 1609.3(1), 1609.3(2) or
1609.3(3).
5.13 All products in the roof assembly shall have quality assurance in accordance with FAC Rule 61G20-3.
6. INSTALLATION:
6.1 TRI-BUILT Modified Bitumen Roof Systems shall be installed in accordance with TRI-BUILT Materials Group,
LLC published installation instructions, subject to the Limitations / Conditions of Use noted below.
6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum
Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects
the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been
applied). Refer to FBC 1609 for determination of design wind loads.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product-
S. MANUFACTURING PLANTS:
Contact the noted QA agency for information on product locations covered for F.A.C. Rule 61G20-3 QA
requirements.
9. QUALITY ASSURANCE ENTITY:
UL LLC —QUA9625; (314) 578-3406, k.chancellor@us.ul.com
- THE 26-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT -
Exterior Research and Design, LLC_ Evaluation Report A42970.10.12-R2
Certificate ofAuthad-ctioa #9503 6 'EDITION(2017)FBCNON-HVHZEVALUATION FL16027-R2
TRI-RI III T RA-4Ma4 Pn f C.r +f _ IAnrll C11r9 HRC Ra icin 7- nn/7G/7nl7
TRINITY
APPENDIX 1' ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE
Table
Deck
Application
Type
Description
1A-1
Wood
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
SA-2
Wood
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
1B
Wood
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
1C
Wood
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
1D
Wood
New, Reroof (Tear -Off) or Recover
D
Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover
1E-1
Wood
New or Reroof (Tear -Off) - ._
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
1E-2 Wood New, Reroof (Tear Off) Recover y E Non-Insulatgd, Mech. Attached Base Sheet, Bonded Roof Cover
Wood New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover
2A
Steel or Structural concrete
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
2B
Steel or Structural concrete
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
2C
Steel or Structural concrete
New, Reroof (Tear -Off) or Recover
D
Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover
3A
Structural concrete
New or Reroof (Tear -Off)
A-f
Bonded Insulation, Bonded Roof Cover
3B
Structural concrete
New or Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
4A
LWIC
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
4B
LWIC
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
4C
LWIC
New or Reroof (Tear -Off)
E
Non=insulated, Mech. Attached Base Sheet, Bonded Roof Cover
5A
CWF
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
5B
CWF
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
5C
CWF
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
SD
CWF
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
SE
CWF
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
6A
Gypsum
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
6B
Gypsum
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
6C
Gypsum
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
fiD
Gypsum
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
7A
Various
Recover
A-1
Bonded Insulation, Bonded Roof Cover
7B Various Recover F Non -Insulated, Bonded Base Sheet, Bonded Roof Cover
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Ju
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement:
Y Wood: Minimum 0.75-inch penetration.
➢ Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck.
➢ Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions.
3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite, gypsum -based roof board or mineral -wool roof board that meet
requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover.
Exterior Research and Design, LLC. d/b/a Trinity)ERD Evaluation Report A42970.10.12-R2 for FL
Certificate of Authorization #9503 6r"EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09
Prepared by: Robert Nieminen PE-5916fi TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Pal
4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby'
sheet fasteners are Installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof d
structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified ani
Approval documentation.
5. Preliminary Insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016).
6. Unless otherwise noted, Insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published Instru
Y HA (HA): Full coverage at 25-30 Ibs/square.
Y Dow INSTA STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-Inch wide ribbons, 12-inch o.c.
Y Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons,l2-inch o.c.
Y OMG OlyBond 500 (OB500): Continuous 0.75 to 1-Inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot). Note: OlyBond Green may be used where O1yBond SOO is referee
Y OlyBond Classic (OB Classic): Full coverage at 1 gal/square.
Y ICP Adhesive & Sealants CR-20: Continuous 2.5-3.5-Inch wide ribbons, 12-inch o.c.
Y Note: When multiple layers(s) of insulation and/or coverboard are installed In ribbon -applied adhesive, adhesive ribbons shall be staggered from layer -to -layer a distance of one-half the ribbon spacing.
Y Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7. Unless otherwise noted, all insulations are flat stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following N
Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tab
the thinner board listed below may be used as a drop -in forthe equivalent thicker material listed in the table:
Y Millennium One Step Foamable Adhesive (M-OSFA): MDP -157.5 psf (Min. 0.5-inch thick)
➢ OMG OlyBond 500 (OB500): MDP -45.0 psf (Min. 0.5-Inch thick Multi -Max FA-3)
Y OMG OlyBond 500 (013500): MDP -187.5 psf (Min. 0.5-inch thick ISO 95+GL)
Y OMG OlyBond 500 (OBSOO): MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3)
Y OMG OlyBond 500 (OB500): MDP -487.5 psf (Min. 0.5-inch thick ACFoam II)
Y ICP Adhesive & Sealants CR-20: MDP -117.5 psf (Min. 1.0-inch thick)
8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft.
9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance
Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1,
Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of
Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
10. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is pe
11. For mechanically attached components over existing decks, fasteners shall be tested In the existing deck for withdrawal resistance. A qualified design professional shall review the data for compariso
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12. For existing substrates In a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the
roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accorda
ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application.
14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to curr
Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness Is
For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1.
Exterior Research and Design, LLC. d/b/a Trinity(ERD Evaluation Report A42970.10.12-R2 for FL1
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Pag,
15. Unless otherwise noted, refer to the fallowing references for bonded base, ply or cap sheet applications.
TABLE•1: TRI-BUILT RooF-COVERS
Reference
Layer
Material
Application
BP -AA
(Base and Ply sheets, Asphalt -Applied)
Base Ply
FBC Approved ASTM D4601, Type II
HA at 20-40 Ibs/square
Ply
FBC Approved ASTM D2178, Type IV or VI
SBS-AA
(SBS, Asphalt -Applied)
Cap Ply
TriBuilt SBS Granular
HA at 20-40 Ibs/square
SBS-TA
(SBS, Torch -Applied)
Cap Ply
TriBuilt SBS Granular
Torch -Applied
SBS-SA
(SBS, Self -Adhering)
Base Ply
TriBuilt SA SBS Base
Self -Adhering
Cap Ply
TriBuilt SA SBS Cap
APP-TA
(APP, Torch -Applied)
I Base Ply or Ply
TriBuilt APP Smooth
Torch -Applied
Cap Ply
TriBuilt APP Smooth, TriBuilt APP Granular
APP-SA '
(APP, Self -Adhering)
Cap Ply
TriBuilt SA APP Cap
Self -Adhering
16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those in
applies:
VAPOR BARRIER OPTIONS; STRUCTURAL' CONCRETE DECK; ADHERED INSULATION PERTABLE-3A
Option ff
Primer
Vapor Barrier
Insulation Adhesive
p
Type
Attach
VB-1.
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Inta-Stik or CR-20, 12-Inch o.c.
VB-2.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Insta-Stik, 12-inch o.c.
VB-3.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Millennium One Step Foamable Adhesive, 12-inch o.c.
VB-4.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
CR-20, 12-inch o.c.
VB-5.
ASTM D41
TriBuilt SA SBS Base
Self Adhering
Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade
Adhesive, OlyBond 500 or CR-20, 12-inch D.C.
17. Dens Deck shall be field -primed with PG100 prior to self -adhering membrane application. Refer to tables herein for other priming requirements.
18. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for FL
Certificate of Authorization #9503 6t" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Pal
•TABLE M-1::WOOD DECKS —NEW CONSTRUCTION OR REROOP(TEAR-OFF)
SYSTEM TYPE A-2:•. MECHANICALLY ATTACHED ANCHOR'SHEET, BONDED.INSULATION;'BONDED ROCIPCOVER
System
Deck
Anchor Sheet
Base Insulation
Top Insulation
Roof Cover (Note 15)
No.
(Note 1)
Type
Fasteners
Attach
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply
Min. 0.25-inch Dens
8-inch o.c. in 4-
Deck, Dens Deck Prime,
Polyglass G2 Base,
32 ga., 1-5/8-
inch lap and 8-
(Optional) FBC
SECUROCK Gypsum -
Min. 19/32-
CertainTeed Glasbase,
Inch diameter
inch o.c. in
Approved,
Fiber Roof Board, Min.
(Optional)
SBS-AA,
yy-1
inch plywood
Firestone MB Base, JM
tin caps with 11
three, equally
ASTM C1289,
HA
0.75-inch FescoBoard
HA
BP -AA
BP AA
SBS-TA,
at max. 24-
Perma-Ply 28, Tamko
ga. annular ring
spaced,
a II of iso-
type p y'
(homogeneous) or min.
( g 1
APP-TA
Inch spans
Glass Base or
or
shank nails
staggered
cyanurate
0.5-inch Structodek
GAFGLAS
center rows
High Density Fiberboard
Roof Insulation
8-inch o.c. in 4-
Polyglass G2 Base,
32 ga ., 1-5/8
inch lap and 8-
(Optional) FBC
Min. 0.25-inch Dens
(Optional)
SBS-SA,
Min. 19/32-
CertainTeed Glasbase,
inch diameter
inch o.c. in
Approved,
Deck, Dens Deck Prime,
One or
APP-SA,
W-2
inch plywood
Firestone MB Base, JM
tin caps with 11
three, equally
ASTM C1289,
HA
SECUROCK Gypsum-
HA
SBS-SA
more SBS
SBS-TA or
at max. 24-
Perma-Ply 28, Tamko
ga. annular ring
spaced,
type II polyiso-
Fiber Roof Board
SA or
APP TA
inch spans
Glass Base or
shank nails
staggered
cyanurate
APP-TA
GAFGLAS #75
center rows
6-inch o.c. in 4-
Min. 2-inch
D-IS, OB500,
Min. 19/32-
32 ga., 1-5/8-
inch lap and 6-
ACFoam II, III,
CR-20 or M-
Min. 0.25-Inch Dens
D-15,
S85-AA,
Inch plywood
Polyglass Elastobase
inch diameter
inch o.c. in
H-Shield, H-
OSFA, atop
Deck, Dens Deck Prime
OB500,
BP AA
(Optional)
SBS-TA,
W-3
at max. 24-
or Polyglass
tin caps with 12
four, equally
Shield CG,
fastener
or SECUROCK Gypsum-
CR-20 or
BP -AA
APP-TA
inch spans
Elastobase Poly
ga. annular ring
spaced,
Multi -Max FA3
rows, 7-inch
Fiber Roof Board
M-OSFA
shank nails
staggered
or ENRGY-3
oc
center rows
6-inch o.c. in 4-
Min. 2-inch
D-IS, OB500,
(Optional)
Min. 19/32-
32 ga., 1-5/8-
inch lap and 6-
ACFoam II, III,
CR-20 or M-
D-IS,
One or
SBS-SA,
inch plywood
Polyglass Elastobase
inch diameter
inch o.c. in
H-Shield, H-
OSFA, atop
(Optional) Additional
OB500,
SBS-SA
more SBS-
APP-SA,
W-4
at max. 24-
or Polyglass
tin caps with 12
four, equally
Shield CG,
fastener
layers of base insulation
CR-20 or
SA or
SBS-TA or
Inch spans
Elastobase Poly
ga. annular ring
spaced,
Multi -Max FA3
rows, 7-inch
M-OSFA
APP TA
APP-TA
shank nails
staggered
or ENRGY-3
oc
center rows
Exterior Research and Design, LLC. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 for I
Certificate of Authorization #9503 6'"EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: (
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, P
TABLE-IA-2: WOOD DECKS —NEW CONSTRUCTION,.REROOF (TEAR -OFF) OR RECOVER
-SYSTEM TYPEA-2: MECHANICALLYATTACHED.ANCHORSHEET,BONDEDINSUTATIONACINDEDROOF:COVER
System
Deck
Anchor Sheet
Base Insulation
Top Insulation
Roof Cover (Note 15)
No.
(Note 1)
Type
Fasteners
Attach
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply
Min. 0.25-inch Dens Deck,
Polyglass
12-inch o.c. in 4
(Optional) FBC
Dens Deck Prime, SECUROCK
Min. 19/32-
Elastobase or
OMG Flat
Inch lap and 12-
Approved,
Gypsum -Fiber Roof Board,
(Optional)
SBS-AA, SBS-
W-5
inch plywood
Polyglass
Bottom Plates
inch o.c. in two,
ASTM C1289,
HA
Min. 0.75-inch FescoBoard
HA
BP -AA
BP -AA
TA, APP-TA
at max. 24-
Elastobase
(square) with
equally Spaced,
type II poiyiso-
(homogeneous) or min. 0.5-
inch spans
Poly
Roofgrip #12
staggered center
cyanurate
Inch Structodek High Density
rows
Fiberboard Roof Insulation
Polyglass
12-inch o.c, in 4-
(Optional) FBC
(Optional)
Min. 19/32-
Elastobase or
OMG Flat
inch lap and 12-
Approved,
Min. 0.25-inch Dens Deck,
One or
SBS-SA, APP-
W 6
inch plywood
Polyglass
Bottom Plates
inch o.c. in two,
ASTM C1289,
HA
Dens Deck Prime, SECUROCK
HA
SBS-SA
more SBS-
SA, SBS-TA
at max. 24-
Elastobase
(square) with
equally spaced,
type 11 polyiso-
Gypsum -Fiber Roof Board
SA or APP-
or APP-TA
inch spans
Poly
Roofgrip412
staggered center
cyanurate
TA
rows
TABLE 1B: WOOD DECKS —NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER
SYSTEM TYPE B: MECHANICALLY.ATTACHED BASE INSULATION; BONDED TOP INSULATION; BONDED ROOF COVER
System
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 15)
No.
Deck (Note 1)
Type
Fasteners
Attach
Type
Attach
Base Ply
Ply
Cap Ply
Min. 0.75-inch FescoBoard
(Optional if
(Optional if using
Min. 19/32-inch
Min. 1.5-inch
Dekfast Hex with
1 per
(homogeneous) or min. 0.5-inch
HA
using AA Ply)
AA Base) One or
SBS-AA, SBS-TA,
W-7
plywood at max. 24-Inch
ENRGY 3, H Shield
Dekfast #12 or TruFast
1.33 ft z
Structodek High Density Fiberboard
more . or
APP-TA
spans
or Polytherm
MP-3 with TruFast DP
Roof Insulation
BP AA
APP-TA1.
Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 for FI
Certificate of Authorization #9503 CH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 0!
- Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, N
h
TRINIn
TABLE 1C: WOOD DECKS —NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER
SYSTEM TYPE C:WECHANICALLY ATTACHED INSULATION; BONDED ROORCOVER•
System
Base Insulation
Top Insulation Layer
Roof Cover (Note 15)
No.
Deck (Note 1)
Layer
Type
Fasteners
Attach
Base Ply
Ply
Cap Ply
Min. 19/32-Inch
(Optional)
One or more layers,
Min. 0.5-inch Structodek High Density
Fiberboard Roof Insulation or min. 0.25-
Dekfast Galvalume
1 per 1.33
ti
(Optional
l
using
(Optionalg
SBS-AA, SBS-TA, APP-
W-8
plywood at max.
Steel Hex with
z
ft
us AA
using AA Ply)
Onif
Base) One or more BP -AA
Base) e B
TA
24-inch spans
any combination,
Inch Dens Deck, Dens Deck Prime or
Dekfast #12 DP
BP -AA
or APP-TA
loose laid
SECUROCK Gypsum -Fiber Roof Board
Dekfast Galvalume
Min.19/32-Inch
(Optional)
One or more layers,
Min. 1.5-inch ENRGY 3, H-Shield or
Steel Hex with
1 per 1,33
(Optional) One or more
SBS-SA, APP-SA, SBS-
W-9
plywood at max.
any combination,
Polytherm
Dekfast #12 DP or
ftz
SBS-SA
SBS-SA or APP-TA
TA or APP-TA
24-Inch spans
TruFast MP-3 with
loose laid
TrUFast DP
TABLE ID: WOOD DECKS —NEW CONSTRUCTION; REROOF.(TEAR-OFF) OR RECOVER
SYSTEM TYPED: PRELIMINARILY ATTACHED INSULATION,,MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
Insulation Layer(s)
Base Sheet
Roof Cover (Note 15)
No.
Deck (Note 1)
Type
Attach
Base
Fasteners
Attach
Base Ply
Cap Ply
Polyglass Elastobase, Polyglass
OMG Flat Bottom Plates
Min.19/32-inch
Elastobase Poly, Polyglass G2 Base,
(square) with Roofgrip
12-inch o.c. in 4-inch lap and 12-
(Optional) One
SBS-AA,
W-10
plywood at inax.
One or more layers,
Prelim.
CertalnTeed Glasbase, Firestone MB
#14, Dekfast Hex with
inch o.c. in two, equally spaced,
or more BP -AA
SBS-TA,
24-inch spans
any combination
Attached
Base, JM Perma-Ply 28, Tamko Glass
Dekfast #14 or TruFast
staggered center rows
or APP-TA
APP-TA
Base or GAFGLAS #75
MP-3 with TruFast HD
SBS-SA;
Min. 19/32-inch
One or more layers,
Prelim.
Polyglass Elastobase or Polyglass
Dekfast Hex with Dekfast
12-Inch o.c. In 4-Inch lap and 12-
One or more
APP-SA,
W-11
plywood at max.
any combination
Attached
Elastobase Poly with poly top surface
#14 or TruFast MP-3 with
Inch o.c. in two, equally spaced,
SBS-SA
SBS-TA or
24-inch spans
TruFast HD
staggered Center rows
APP-TA
Min. 19/32-inch
One or more layers,
Prelim.
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates
12-Inch o.c. in 4-Inch lap and 12-
inch o.c. In two, equally spaced,
(Optional) One
or more BP -AA
SBS-AA,
SBS-TA,
W-12
plywood at max.
24-Inch spans
any combination
Attached
Elastobase Poly
(square) with Roofgrip #12
staggered center rows
or APP-TA
APP-TA
SBS-SA,
19/32-inch
One or more layers,
Prelim.
Polyglass Elastobase or Polyglass
lates
OMG Fiat Bottom Plates
12-inch o.c. in 4-inch lap and 12-
inch o.c. in two, equally spaced,
One or more
APO -SA,
W-13
plywood at max.
any combination
Attached
Elastobase Poly with poly top surface
(square) with Roofgrip #12
staggered center rows
SBS-SA
SBS-TA or
24-inch spans
APP-TA
Exterior Research and Design, LLC. d/b/a Trinity ( ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6TH EDITION (2017) FBC NON-HVHZ EVALUATION
TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485
Evaluation Report A42970.10.12-R2 for
Revision 2:
Appendix 1,
. TABLE 1E-1:.WOOD DECKS —NEW CONSTRUCTION OR REROOF (TEAR -OFF).
SYSTEM TYPE E: NON -INSULATED, MECHANICALLY ATTACHED BASESHEET, BONDED ROOF COVER
System
Base Sheet
Roof Cover (Note 15)
No.
Deck (Note 1)
Base
Fasteners
Attach
Base Ply
Cap Ply
Min. 15/32-inch
9-inch o.c. at lap and 18-inch In two,
(Optional) BP -AA or
SBS-AA, SBS-TA
W-14
plywood at max. 24-
Polyglass Elastobase
Simplex MAXX Cap
d,inch
s
equally spaced, staggered center rows
APP-TA
or APP-TA
or
inch spans
Min. 15/32-Inch
o.c. at lap and in two,
(Optional) BP -AA or
, 585-TA
W-15
plywood at max. 24-
Polyglass Elastobase
Simplex MAXX Cap
d,Inch
s
enter rows
equally spaced, staggered center rows
equally
APP-TA
or APP
or APP-TA
inch spans
Miwood 2-Inch
Polyglass Elastobase, Polyglass Elastobase
Poly, Polyglass G2 Base, CertainTeed
32 ga., 1-5/8-inch diameter tin caps
8-Inch o.c. in 4-inch lap and 8-inch o.c. in three,
(Optional) One or
more BP -AA or
SBS-AA, SBS-
W-16
plywood at max.
Glasbase, Firestone MB Base, JM Perma-
with 11 ga, annular ring shank nails
equally spaced, staggered center rows
APP-TA
TA, APP-TA
24-inch spans
ply 28, Tamko Glass Base or GAFGLAS N75
Min. 19/32-inch
Polyglass Elastobase or Polyglass
32 ga., 1-5/8-inch diameter tin caps
8-inch o.c. in 4-inch lap and B-inch o.c. in three,
(Optional) One or
more SBS-SA or
SBS-SA, APP-
SA, SBS-TA or
W-17
plywood at max.
Elastobase Poly with poly top surface
with 11 ga. annular ring shank nails
equally spaced, staggered center rows
APP-TA
APP-TA
24-Inch spans
Min. 15/32-inch
6-inch o.c. at 2-inch lap and o.c. in two,
(Optional) BP -AA or
, SBS-TA
W-18
plywood at max, 24-
Polyglass Elastobase
Simplex MAXX Cap
enter r
equally spaced, staggered center rows
APP-TA
or APP-TA
or APP
inch spans
Min. 19/32-inch
Polyglass Elastobase or Polyglass
32 ga., 1-5/8-inch diameter tin caps
4-inch o.c. in 4-inch lap and 4-inch o.c. in four,
(Optional) One or
more SBS-SA or
SBS-SA, APP-
SA, SB5-TA or
W-19
plywood at max.
Elastobase Poly with poly top surface
with 11 ga. annular ring shank nails,
equally spaced, staggered center rows
APP-TA
APP-TA
24-inch spans
Min. 15/32-inch
6-Inch o.c, at 2-inch lap and o.c. in three,
(Optional) BP -AA or
SB5-TA
W-20
plywood at max. 24-
Polyglass Elastobase
Simplex MAXX Cap
enter r
equally spaced, staggered center rows
APP-TA
or APPSBS-AA,
or APP-TA
inch spans
Min. 19/32-inch
Polyglass Elastobase or Polyglass
32 ga., 1-5/8-inch diameter tin caps
6-Inch o.c. in 4-inch lap and 6-inch o.c. In four,
(Optional) One or
more BP -AA or
SB5-AA, 5135-
W-21
plywood at max.
Elastobase Poly
with 11 ga. annular ring shank nails
equally spaced, staggered center rows
APP-TA
TA, APP-TA
24-Inch spans
Min. 19/32-inch
32 ga., 1-5/8-inch diameter tin caps
SBS-SA, APP-
Polyglass Elastobase or Polyglass
with 11 ga, annular ring shank nails.
6-inch o.c. in 4-inch lap and 6-inch o.c. in four,
(Optional) One or
SA, SBS-TA or
W-22
plywood at max.
Elastobase Poly with poly top surface
Note: Tin caps are to be primed with
equally spaced, staggered center rows
more APP-TA
APP TA
24-inch spans
ASTM D41 primer.
Exterior Research and Design, LLC. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 for Fl.
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: OS
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-148S Appendix 1, Pa
TABLE 1E-2::WOOD DECKS —NEW.CONSTRUCTION; REROOF.(TEAR-OFF) OR RECOVER "� z
'SYSTEMTYPE E: NON -INSULATED; MECHANICALLY -ATTACHED BASE SHEET; BONDED'ROOF COVER.
Base Sheet
Roof Cover (Note 15,
System
No.
Deck (Note 1)
Base Ply Cap Ply
Base
Fasteners
Attach
Min. Inch
Polyglass Elastobase, Polyglass Elastobase
OMG Flat Bottom Plates s with
(square)
12-Inch o.c. in 4-inch lap and 12-inch
(Optional) One or
SBS-AA, SBS
W-1
plyw000dd aat t max.
poly, Polyglass G2 Base, CertalnTeed
Roofgrip #14, Dekfast Hex with Dekfast q14
o.c. in two, equally spaced, staggered
more BP -AA or
TA, APP-TA
24-inch spans
as
Glasbase, Firestone MB Base, JM Perma-
or TruFast MP-3 with TruFast HD
center rows
APP-TA
Ply 28, TamkGlass Base GAFGLAS #75
Min. 19/32-Inch
Polyglass Elastobase or Polyglass
Dekfast Hex with Dekfast #14 or TruFast MP-
12-inch o.c. in 4-Inch lap and 12-Inch
o.c. in two, equally spaced, staggered
One or more SBS-
SBS-SA, APP-
SA, SBS-TA or
W-2
plywood at max.
Elastobase Poly with poly top surface
3 with TruFast HD
center rows
SA
APP-TA
24-inch spans
Min. 19/32-Inch
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates (square) with
12-Inch o.c. in 4-inch lap and 12-Inch
o.c. in two, equally spaced, staggered
(Optional) One or
more BP -AA or
SBS-AA, SBS-
W-3
plywood at max.
Elastobase Poly
Roofgrip #12
center rows
APP-TA
TA, APP TA
24-inch spans
Min. 19/32-inch
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates (square) with
12-inch o.c. in 4-inch lap and 12-inch
o.c. in two, equally spaced, staggered
One or more SBS-
SBS-SA, APP-
SA SBS-TA or
W-4
plywood at max.
Elastobase Poly with poly top surface
Roofgrip #12
center rows
SA
APP-TA
24-inch spans
TABLE 1F: WOOD DECKS —NEW CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE F: NON -INSULATED, BONDED ROOF COVER
System Roof Cover (Note 15)
Deck Primer I I n— o Cap Ply----
Vy 5 f�in..15/32-1ncn plywood (OptionalJASTIVM~� D4 ,None' G ^ — --- =`585 5A' _._ orAPP-TA-
eat:max 24=inch spans N:. • -- n _ ..� -APP TA, u
W 6 Min. 15/32-inch plywood (Optional) ASTM D41 Plywood joints are covered with 4-Inch wide strips of TriBuilt SA TriBuilt SA SBS Base (Optional) SBS SA or SBS SA, APP-SA, SBS-TA
APP-TA or APP-TA
at max. 24-Inch spans SBS Base, rolled Into place to create continuous bond.
Exterior Research and Design, U.C. d/b/a Trinity ) ERD Evaluation Report A42970.10.12-R2 for 1
Certificate of Authorization #9503 Gr" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: (
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, F
TRIM
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS —NEW CONSTRUCTION, REROOF (TEAR -OFF) oR, RECOVER
'SYSTEM TYPEIB: MECHANICALLY ATTACHED BASE INSUL . ATION;BONDEDIOPINSULATIONF BONDED ROORCOVER
System
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 15)
No.
Deck (Note 1)
Type'
Fasteners
Attach
Type
Attach
Base Ply
Ply
Cap Ply
Min. 22 ga., type B,
Min. 1.5-inch
Dekfast Hex with
Min. 0.75-inch FescoBoard
(Optional if using
Grade 33 steel or
ACFoam II, ENRGY
Dekfast 414, Trufast
MP-3 Trufast HD
,
1 2 ft
(homogeneous) or min. 0.5-inch
HA
(Optional if using
AA Base) One or
SBS-AA, SBS
SC-1.
min, 2,500 psi
3, H-Shield or
with or
per
Structodek High Density
AA Ply) BP -AA
more BP -AA or
TA, APP-TA
structrual concrete
Polytherm
OMG 3-inch Galy Plate
Fiberboard Roof Insulation
APP-TA
with OMD HD
Min. 22 ga., type B,
Min. 2-inch
Dekfast Hex with
Min. 0.75-inch FescoBoard
(Optional if using
Grade 33 steel or
ACFoam II ENRGY
Dekfast #14, Trufast
MP-3 Trufast HD
z
1 4 ft�
(homogeneous) or min. 0.5-inch
HA
(Optional if using
AA Base) One or
SBS-AA, SBS
SC-2,
min. 2,500 psi
3, H-Shield or
with or
per
Structodek High Density
AA Ply) BP -AA
more BP -AA or
TA, APP-TA
structrual concrete
Polytherm
OMG 3-inch Galy Plate
Fiberboard Roof Insulation
APP-TA
with OMD HD
Min. 22 ga., type B,
Grade 33 steel or
Min. 1.5-inch
Dekfast Hex with
1 per 1.33
Min. 0.75-Inch FescoBoard
(homogeneous) or min. 0.5-inch
(Optional if using
(Optional if using
AA Base) One or
SBS-AA, SBS
SC-3.
min. 2,500 psi
ENRGY 3, H-Shleld
Dekfast #14 or TruFast
ftz
Structodek High Density
HA
AA Ply) BP -AA
more BP -AA or
TA, APP-TA
structrual concrete
or Polytherm
MP-3 with TruFast HD
Fiberboard Roof Insulation
APP-TA
Min. 22 ga., type B,
Min. 1.5-Inch
Dekfast Hex with
Min. 0.75-inch FescoBoard
(Top BP -AA
To surface
One or more
SBS- A, APF
SC-4.
Grade 33 steel or
ENRGY 3, H-Shield
Dekfast #14 or
1 per z 1.33
(homogeneous) or min. 0.5-inch
HA
P rimed with ASTM
layers, SBS-SA or
SA, SBS-TA
min. 2,500 psi
or Polytherm
MP-3 with TruFast HD
ft
Structodek High Density
D41 primer)
APP-TA
or APP-TA
structrual concrete _
Fiberboard Roof Insulation
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS— NEW..CONSTRUCTION, REROOF (TEAR-OFF)OR RECOVER
SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
Base Insulation
Top Insulation Layer
Roof Cover (Note 15)
No
Deck (Note 1)
Layer
Type
Fasteners
Attach
Base Ply
Ply
Cap Ply
Min. 22 ga., type B,
(Optional) One or
(Optional if
(Optional if using AA
SC 5.
Grade 33 steel or
more layers, any
Min. 0.5-inch SECUROCK Gypsum-
OMG 3-inch Galvalume Steel
1 per 1.78
using AA Ply)
Base) One or more BP-
SBS-AA, SBS
min. 2,500 psi
combination, loose
Fiber Roof Board
Plate with OMG #14 HD
ftz
BP -AA
AA or APP-TA
TA, APP-TA
structrual concrete
laid
Min. 0.5-inch Structodek High
Min. 22 ga., type B,
One or more layers,
Density Fiberboard Roof
Dekfast Galvalume Steel Hex with
(Optional If
(Optional if using AA
( P g
SC-6.
Grade 33 steel or
any combination,
Insulation or min. 0.25-inch Dens
Dekfast 412 (steel only) or #14 or
1 per 1.33
using AA Ply)
Base) One or more BP-
SBS-AA, SBS
min. 2,500 psi
loose laid
Deck, Dens Deck Prime or
TruFast MP-3 with TruFast DP
ftz
BP -AA
AA or APP-TA
TA, APP-TA
structrual concrete
SECUROCK Gypsum -Fiber Roof
(steel only) or HD
Board
Min. 22 ga., type B,
(Optional)
Dekfast Galvalume Steel Hex with
SBS-AA, SBS
Grade 33 steel or
One or more layers,
Min. 1.5-inch ENRGY 3, H-Shield
Dekfast #12 (steel only) or #14 or
1 per 1.33
SBS-SA
(Optional) One or more
TA, SBS-SA,
SC-7.
min. 2,500 psi
any combination,
or Polytherm
TruFast MP-3 with TruFast DP
ftz
SBS-SA or APP-TA
APP-TA, APF
structrual concrete
loose laid
(steel only) or HD
SA
Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report A42970.10A2-112 for
Certificate of Authorization #9503 a"EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2:
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1,
TRIN17
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS NEW CONSTRUCTION,' REROOF (TEAR -OFF) OR RECOVER
SYSTEM TYPE B:. MECHANICALLY ATTACHED. BASE INSULATION; BONDED TOP INSULATION; BONDED:ROOF COVER
System
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 15)
No.
Deck (Note i)
Type
Fasteners
Attach
Type
Attach
Base Ply
Ply
Cap Ply
Min. 22 ga., type B,
Min. 1.5-inch
Dekfast Hex with
Dekfast #14, Trufast
Min. 0.75-inch FescoBoard
(Optional if using
SC-1.
Grade 33 steel or
ACFoam II, ENRGY
MP-3 with Trufast HD or
,
1 per 2 ft'
(homogeneous) or min. 0.5-inch
HA
(Optional if using
AA Base) One or
SBS-AA, SB'
min. 2,500 psi
3, H-Shield or
Structodek High Density
AA Ply) BP -AA
more BP -AA or
TA, APP-TA
structrual concrete
Polytherm
OMG 3-inch Galy Plate
Fiberboard Roof Insulation
APP-TA
with OMD HD
Min. 22 ga., type B,
Min. 2-inch
Dekfast Hex with
Min. 0.75-inch FescoBoard
(Optional if using
Grade 33 steel or
ACFoam II, ENRGY
Dekfast 414, Trufast
MP-3 Trufast HD
,
1 4 ft'
(homogeneous) or min. 0.5-inch
HA
(Optional if using
AA Base) One or
SBS-AA, SB:
SC-2.
min. 2,500 psi
3, H-Shield or
with or
per
Structodek High Density
AA Ply) BP -AA
more BP -AA or
TA, APP-TA
structrual concrete
Polytherm
OMG 3-inch Galy Plate
Fiberboard Roof Insulation
APP-TA
with OMD HD
Min. 22 ga., type B,
Grade 33 steel or
Min. 1.5 inch
Dekfast Hex with
1 per 1.33
Min. 0.75-inch FescoBoard
(homogeneous) or min. 0.5-inch
(Optional if using
(Optional if using
AA Base) One or
SBS-AA, SB.
SC-3.
min. 2,500 psi
ENRGY 3, H-Shield
Dekfast #14 or Trufast
z
ft
Structodek High Density
HA
AA Ply) BP -AA
more BP -AA or
TA, APP-TA
structrual concrete
or Polytherm
MP-3 with TruFast HD
Fiberboard Roof Insulation
APP-TA
Min. 22 ga., type B,
Min. 1.5-Inch
Dekfast Hex with
Min. 0.75-Inch FescoBoard
BP -AA (Top surface
One or more
SBS-SA, APf
SC-4.
Grade 33 steel or
ENRGY 3, H-Shield
Dekfast #14 or TruFast
1 per 1.33
z
(homogeneous) or min. 0.5-inch
High Density
HA
P rimed with ASTM
layers, SBS-SA or
Y
SA, SBS-TA
min. 2,500 psi
or Polytherm
MP-3 with Trufast HD
ft
Structodek
D41 primer)
APP-TA
or PP -TA
structrual concrete
Fiberboard Roof Insulation
TABLE 2B:. STEEL OR STRUCTURAL CONCRETE DECKS— NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER
SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
Base Insulation
Top Insulation Layer
Roof Cover (Note 15)
T
Type
Fasteners
Attach
Base Ply
PI Y
Ca Ply
P
No
Deck (Note 1)
Layer
y
Min. 22 ga., type B,
(Optional) One or
(Optional if
(Optional if using AA
SC-5.
Grade 33 steel or
more layers, any
Min. 0.5-inch SECUROCK Gypsum-
OMG 3-inch Galvalume Steel
1 per 1.78
using AA Ply)
Base) Oise or more BP-
SBS-AA, SB!
min. 2,500 psi
combination, loose
. Fiber Roof Board
Plate with OMG #14 HD
ft,
BP -AA
AA or APP-TA
TA APP-TA
structrual concrete
laid
Min. 0.5-Inch Structodek High
Min. 22 ga., type B,
One more layers,
Density Fiberboard Roof
Dekfast Galvalume Steel Hex with
(Optional if
(Optional if using AA
( P g
SBS-AA, SB'-
SC-6.
Grade 33 steel or
any combination,
o
Insulation or min. 0.25-inch Dens
Dekfast #12 (steel only) or #14 or
1 per 1.33
using AA Ply)
Base) One or more BP-
TA, APP-TA
min. 2,500 psi
loose laid
Deck, Dens Deck Prime or
TruFast MP-3 with TruFast DP
ft,
BP -AA
AA or APP-TA
structrual concrete
SECUROCK Gypsum -Fiber Roof
(steel only) or HD
Board
Min. 22 ga., type B,
(Optional)
Dekfast Galvalume Steel Hex with
SBS-AA, SB!
Grade 33 steel or
One or more layers,
Min.1.5-inch ENRGY 3, H-Shield
Dekfast #12 (steel only) or #14 or
1 per 1.33
SBS 5A
(Optional) One or more
TA, SBS-SA,
SC-7.
min. 2,500 psi
any combination,
or Polytherm
TruFast MP-3 with Trufast DP
ft,
SBS-SA or APP-TA
APP-TA, AN
structrual concrete
loose laid
(steel only) or HD
SA
Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 fo
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVH2 EVALUATION Revision 2
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1,
TABLE 2C: STEEL OR -STRUCTURAL CONCRETE DECKS —NEW CONSTRUCTION, REROOF (TEAR=OFF) oR RECOVER
SYSTEM TYPE D: PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ATTACHED BASE SHEET, BONDED.ROOF COVER
NOTE:INSULATION IS OPTIONAL FOR RECOVER -APPLICATIONS
System
insulation Layer(s)
Base Sheet
Roof Cover (Note 15)
No.
Deck (Note 1)
Type
Attach
Base
Fasteners
Attach
Base Ply
Cap Ply
Min. 22 ga., type B,
One or more
Polyglass Elastobase, Polyglass
OMG Flat Bottom Plates (square)
12-inch o.c. in 4-Inch lap
(Optional) One or
c
SC 8.
Grade 33 steel or min.
layers, any
Prelim.
Elastobase Poly or JM Perma-
with Roofgrip #14, Dekfast Hex
and 18-inch o.c. in two,
more BP -AA or APP-
SBS-AA, SM
2,500 psi structrual
Attached
with Dekfast #14 or TruFast MP-3
equally spaced, staggered
TA
TA, APP-TA
concrete
combination
Ply 28
with TruFast HD
center rows
Polyglass Elastobase, Polyglass
Min. 22 ga., type B,
Elastobase Poly, Polyglass G2
OMG Flat Bottom Plates (square)
12-Inch o.c. in 4-inch lap
(Optional) One or
Grade 33 steel or min.
One more
Prelim.
Base, CertainTeed Glasbase,
with Roofgrip #14, Dekfast Hex
and 12-inch o.c. in two,
more BP -AA or APP-
SBS-AA, SBS
SC-9.
2,500 psi structrual
layers, any
Attached
Firestone MB Base, JM Perma-
with Dekfast #14 or TruFast MP-3
equally spaced, staggered
TA, APP-TA
concrete
combination
Ply 28, Tamko Glass Base or
with Trufast HD
center rows
GAFGLAS #75
Min. 22 ga., type B,
One or more
Polyglass Elastobase or
OMG Flat Bottom Plates (square)
12-Inch o.c. in 4-Inch lap
SBS-SA, APF
SC-10.
Grade 33 steel or min.
layers, any
Prelim,
Polyglass Elastobase Poly with
with Roofgrip #14, Dekfast Hex
and 12-inch o.c. in two,
One or more SBS-SA
SA, SBS-TA
2,500 psi structrual
combination
Attached
poly top surface
with Dekfast #14 or TruFast MP-3
equally spaced, staggered
or APP-TA
concrete
with TruFast HD
center rows
Min. 22 ga., type B,
Grade 33 steel or min.
One or more
Prelim.
Polyglass Elastobase or
OMG Flat Bottom Plates (square)
12-inch o.c. in 4-inch lap
and 12-inch o.c. in two,
(Optional) One or
SBS-AA, SBS
SC-11.
2,500 psi structrual
layers, any
Attached
Polyglass Elastobase Poly
with Roofgrip #12 (steel only) or
equally spaced, staggered
more BP -AA or APP
TA, APP-TA
concrete
combination
#14
center rows
TA
Min. 22 ga., type B,
One or more
Polyglass Elastobase or
OMG Flat Bottom Plates (square)
12-inch c.c. in 4-inch lap
SBS-SA, APF
SC-12.
Grade 33 steel or min.
layers, any
Prelim.
Polyglass Elastobase Poly with
with Roofgrip #12 (steel only) or
and 12-inch o.c. in two,
equally s aced,
or more SBS-SA
SA, SBS-TA
2,500 psi structrual
combination
Attached
poly top surface
#14
pstaggeredOne
or,APP TA
concrete
center rows
Min. 22 ga., type B,
Grade 80 steel or min.
One or more
Prelim.
Dekfast Isofast IF-2.375-AT Plates
12-inch o.c, in the 5-inch
(Optional) APP-TA
SBS-TA, APF
SC-13.
2,500 psi structrual
layers, any
Attached
TriBuilt APP Smooth
with Dekfast #15 HS
wide, heat -welded side lap
TA
combination
concrete
SC-14.
Min. 22 ga., type B,
Grade 80 steel or min.
One or more
layers, any
Prelim.
TriBuilt APP Smooth
Trufast 2.4 in. Barbed Seam
12-inch o.c. in the 6-inch
(Optional) APP-TA
SBS-TA, APP
2,500 psi structrual
Attached
Plates with Trufast EHD Fasteners
wide, heat -welded side lap
TA
combination
concrete
Min. 22 ga., type B,
Grade 33 steel or min.
One or more
Prelim.
Dekfast Hex with Dekfast #14 or
12-inch o.c, in the 4-inch
lap and 18-inch o.c. in two,
(Optional) BP -AA or
SBS-AA, SBS
SC-15,
2,500 psi structrual
layers, any
Attached
TriBuilt APP Smooth
OMG Flat Bottom Plates with
equally spaced, staggered
APP-TA
TA, APP-TA
concrete
combination
OMG Roofgrip 414
center rows
Exterior Research and Design, LLC, d/b/a Trinity)ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
Evaluation Report A42970.10.12-R2 fe
6r" EDITION (2017) FBC NON-HVHZ EVALUATION Revision ;
TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1,
TRINITY
TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS —NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER
SYSTEM TYPED: PRELIMINARILY.ATTACHED.INSULATION, MECHANICALLY ATTACHED. BASE SHEET, BONDED ROOF COVER
NOTE: INSULATION IS OPTIONAL'' FOR RECOVER -APPLICATIONS
System
Insulation Layer(s)
Base Sheet
Roof Cover (Note 15)
No.
Deck (Note 1)
Type
Attach
Base
Fasteners
Attach
Base Ply
Cap Ply
Min. 22 ga., type B,
One or more
Polyglass Elastobase, Polyglass
OMG Flat Bottom Plates (square)
12-inch o.c. in 4-inch lap
(Optional) One or
SC-8,
Grade 33 steel or min.
layers, any
Prelim.
Elastobase Poly or JM Perma-
with Roofgrip #14, Dekfast Hex
and 18-inch o.c. in two,
more BP -AA or APP-
SBS-AA, SBS-
2,500 psi structrual
Attached
with Dekfast #14 or TruFast MP-3
equally spaced, staggered
TA
TA, APP-TA
concrete
combination
Ply 28
with TruFast HD
center rows
Polyglass Elastobase, Polyglass
Min. 22 ga., type B,
One or more
Elastobase Poly, Polyglass G2
OMG Flat Bottom Plates (square)
12-Inch o.c. in 4-inch lap
(Optional) One or
SC-9.
Grade 33 steel or min.
layers, any
Prelim.
Base, CertainTeed Glasbase,
with Roofgrip #14, Dekfast Hex
and 12-inch o.c. in two,
more BP-AAorAPP-
SBS-AA, SBS-
2,500 psi structrual
Attached
Firestone MB Base, JM Perma-
with Dekfast #14 or TruFast MP-3
equally spaced, staggered
TA
TA, APP-TA
concrete
combination
Ply 28, Tamko Glass Base or
with TruFast HD
center rows
GAFGLAS #75
Min. 22 ga., type B,
One or more
Polyglass Elastobase or
OMG Flat Bottom Plates (square)
12-inch o.c. In 4-Inch lap
SBS-SA, APP-
5C-10.
Grade 33 steel or min.
layers, any
Prelim.
Polyglass Elastobase Poly with
with Roofgrip #14, Dekfast Hex
and 12-Inch o.c. in two,
One or more SBS-SA
SA, SBS-TA
2,500 psi structrual
combination
Attached
poly top surface
with Dekfast #14 orTruFast MP-3
equally spaced, staggered
or APP-TA
concrete
with TruFast HD
center rows
Min. 22 ga., type B,
Grade 33 steel or min.
One or more
Prelim.
Polyglass Elastobase or
OMG Flat Bottom Plates (square)
12-inch o.c. in 4-inch lap
and 12-inch o.c. in two,
(Optional) One or
SBS-AA, SBS-
SC-11.
2,500 psi structrual
layers, any
Attached
Polyglass Elastobase Poly
with Roofgrip #12 (steel only) or
equally spaced, staggered
more BP -AA or APP-
TA, APP-TA
concrete
combination
#14
center rows
TA
Min. 22 ga., type B,
One or more
Polyglass Elastobase or
OMG Flat Bottom Plates (square)
12-inch o.c. In 4-inch lap
and 12-Inch o.c. in two,
SBS-SA, APP-
SC-12,
Grade 33 steel or min.
2,500 psi structrual
layers, any
Prelim.
Attached
Polyglass Elastobase Poly with
with Roofgrip #12 (steel only) or
equally spaced, staggered
One or more SBS-SA
SA, SBS-TA
concrete
combination
poly top surface
#14
center rows
or APP-TA
Min. 22 ga., type B,
Grade 80 steel or min.
One or more
Prelim.
Dekfast isofast IF-2.375-AT Plates
12-inch o.c. in the 5-inch
(Optional) APP TA
SBS-TA, APP-
SC 13.
2,500 psi structrual
layersany
Attached
Trieuilt APP Smooth
with Dekfast #15 HS
wide, heat -welded side lap
TA
concrete
combination
Min. 22 ga., type B,
SC-14.
Grade 80 steel or min.
One or more
layersany
Prelim.
TriBuilt APP Smooth
Trufast 2.4 in. Barbed Seam
12-inch o.c. in the 6-Inch
(Optional) APP TA
SBS-TA, APP-
2,500 psi structrual
Attached
Plates with Trufast EHD Fasteners
wide, heat -welded side lap
TA
combination
concrete
Min. 22 ga., type B,
One or more
Dekfast Hex with Dekfast 414 or
12-inch o.c. in the 4-Inch
SC-15.
Grade 33 steel or min.
layers, any
Prelim.
Trieullt APP Smooth
OMG Flat Bottom Plates with
lap and 18-Inch o.c. in two,
(Optional) BP -AA or
SBS-AA, SB5-
2,500 psi structrual
combination
Attached
OMG Roofgrip #14
equally spaced, staggered
APP-TA
TA, APP-TA
concrete
center rows
Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report A42970,10.12-112 for FI
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 0�
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Pag
TRINIT
I TABLE 3A: STRUCTURALCONCRETE DECKS— NEW CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE A-1: BONDED INSULATION; BONDED ROOF COVER
Cee IU_. 7 A m Arwnne R....— A.—
System
Deck
Primer
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 15)
Type Attach
Type Attach
Base Ply Ply Cap Ply
No.
SELF -ADHERING SYSTEMS WITH BASE INSULATION AND OPTIONALTOPINSULATION OFTHESAMETYPE:
C-1
Structural
(Optional)
Min. 1.5-inch H-Shield or Multi -Max
(Optional) additional layers(s) of
(Optional) One or more
SBS-SA, APP-SA,
concrete
ASTM D41
FA3
D-IS
base insulation
D-IS
SBS-SA
SBS-SA or APP-TA
SBS-TA or APP-T/
C 2
Structural
(Optional)
Min. 1.5-inch ACFoam II or ENRGY 3
D-IS
(Optional) additional layers(s) of
D-IS
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
ASTM D41
base Insulation
SBS-SA or APP-TA
SBS-TA or APP-T)
C-3
Structural
None
Min. 1.5-inch, min. 1.5 pcf Insulfoam
D-IS
(Optional) additional layers of base
D-IS
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
insulation
SBS-SA or APP-TA
SBS-TA or APP-T<
C-4
Structural
None
Min. 1.5-inch, min. 2.0 pcf Insulfoam
OB500
(Optional) additional layers of base
OB500
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
insulation
SBS-SA or APP-TA
SBS-TA or APP-T1
:C:-5
Structural
None
Min. 1.5-inch ENRGY 3
OB500
(Optional) additional layers(s) of
OB500
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
base Insulation
SBS-SA or APP-TA
SBS-TA or APP-TA
C-6
Structural
None
Min, 1.5-inch ACFoam II or ii-Shield
OB500
(Optional) additional layers(s) of
OB500
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
base Insulation
SBS-SA or APP-TA
SBS-TA or APP-TP
C 7
Structural
None
Min. 1.5-Inch ACFoam II, ENRGY 3, H-
M-OSFA
(Optional) additional layers(s) of
M-OSFA
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
Shield or Multi -Max FA3
base insulation
SBS-SA or APP-TA
SBS-TA or APP-TA
C 8
Structural
None
Min. 1.5-inch, min, 2.0 pcf Insulfoam
CR-20
(Optional) additional layers of base
CR-20
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
insulation
SBS-SA or APP-TA
SBS-TA or APP-TA
C-9
Structural
Min. 1.5-inch ACFoam 11, ACFoam III,
(Optional) additional layers(s)of
(Optional) One
SBS-SA, APP-SA,
concrete
None
ENRGY 3, H-Shield, H-Shieid CG , Multi-
CR-20
base insulation
CR-20
SBS-SA
Amore
SBS-SA or APP-TA
SBS-TA or APP-TA
Max FA3 or ISO 95+ GL
C-10
Structural
None
Min. 2-inch ACFoam II or H Shield
COlassic
(Optional) additional layers(s) of
Oiasslc
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
(FULL)
base insulation
(FULL)
SBS-SA or APP-TA
SBS-TA or APP TA
C-11
Structural
ASTM D41
Min. 1.5-inch ACFoam II, ACFoam 111,
ENRGY 3, H-Shield, H-Shield CG or
HA
(Optional) additional layers(s)of
HA
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
Multi -Max FA3
base Insulation
SBS-SA or APP-TA
SBS-TA or APP-TA
SELF -ADHERING SYSTEMS WITH BASE INSULATION AND COVERBOARD:
C-12
Structural
None
Min. 1.5-inch Multi -Max FA3
D-IS
Min. 0.25-Inch SECUROCK Gypsum-
D-IS
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
Fiber Roof Board
SBS-SA or APP-TA
SBS-TA or APP-TA
C-13
Structural
None
Min. 1.5-inch, min. 2.0 pcf Insulfoam
D-IS
Min. 0.25-inch Dens Deck, Dens
D-IS
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
Deck Prime
5B5-5A or APP-TA
SBS-TA or APP-TA
C-14
Structural
None
Min. 2-inch ACFoam 11, ENRGY-3 or H-
Min. 0.25-inch SECUROCK Gypsum-
(Optional) One or more
SBS-SA, APP-SA,
concrete
Shield
D-IS
Fiber Roof Board
DAS
SBS-SA
SBS-SA or APP-TA
SBS-TA or APP-TA
C-15
Structural
None
Min. 1.5-inch ENRGY 3
OB500
Min. 0.25-inch Dens Deck, Dens
OB500
5B5-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
Deck Prime
SBS-SA or APP-TA
SBS-TA or APP-TA
Exterior Research and Design, L.I.C. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 for
Certificate of Authorization #9503 6T"EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2:1
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Pi
. Tf�li�11T
TABLE 3A: STRUCTURAL CONCRETE DECKS NEW CONSTRUCTION OR REROOF(TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION; BONDED ROOF COVER
SEE NOTE 16 FOR VAPOR BARRIER OPTIONS*
System
Deck
Primer
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 15)
No.
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply
C-16
Structural
None
Min. 1.5-inch ACFoam II, H-Shield or
Min. 0.25-inch Dens Deck, Dens
(Optional) One or more
SBS-SA, APP-SA,
concrete
ISO 95+GL
08500
Deck Prime
OB500
585-SA
SBS-SA or APP-TA
SBS-TA or APP-T
C-17
Structural
None
Min. 2-inch ACFoam II, ENRGY-3 or H-
OB500
Min. 0.25-inch SECUROCK Gypsum-
(Optional) One or more
SBS-SA, APP-SA,
concrete
Shield
Fiber Roof Board
OB500
SBS-SA
SBS-SA or APP-TA
SBS-TA or APP-T
C-18
Structural
None
Min. 1.5-inch ACFoam II, ENRGY 3, H-
M-OSFA
Min. 0.25-inch SECUROCK Gypsum-
M-OSFA
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
Shield or Multi -Max FA3
Fiber Roof Board
SBS-SA or APP-TA
SBS-TA or APP-T,
C-19
Structural
None
Min. 2-inch ACFoam II, ENRGY-3 or H-
M-OSFA
Min. 0.25-inch SECUROCK Gypsum-
M-OSFA
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
Shield
Fiber Roof Board
SBS-SA or APP-TA
SBS-TA or APP-T,
C-20
Structural
None
Min. 1.5-inch, min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch Dens Deck, Dens
CR-20
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
Deck Prime
SBS-SA or APP-TA
SBS-TA or APP-Tj
Min.1.5-inch Ultra -Max or Multi -Max
C-21
Structural
None
FA-3, min. 1.3-Inch ACFoam III or min.
Min. 0.25-Inch SECUROCK Gypsum-
(Optional) One or more
SBS-SA, APP-SA,
concrete
1.0-inch ISO 95+GL, H-Shield, H-Shield
CR-20
Fiber Roof Board
CR-20
SBS-SA
SBS-SA or APP-TA
SBS-TA or APP-T)
CG or ENRGY 3
C 22
Structural
Min. 2-inch ACFoam 11, ENRGY-3 or H-
Min. 0.25-inch SECUROCK Gypsum-
(Optional) One or more
SBS-SA, APP-SA,
concrete
None
Shield
CR-20
Fiber Roof Board
CR-20
SBS-SA
SBS-SA or APP-TA
SBS-TA or APP-TI
C-23
Structural
None
Min. 2-inch ACFoam II or H-Shield
OB
Classic
Min. 0.25-inch SECUROCK Gypsum-
OB
Classic
SBS-SA
(Optional) One or more
SBS-SA, APP-SA,
concrete
(FULL)
Fiber Roof Board
(FULL)
SBS-SA or APP-TA
SBS-TA or APP-Ti
Structural
Min. 1.5-inch ACFoam 11, ACFoam III,
0 Min. .25-inch SECUROCK Gypsum-
(Optional) One more
SBS-SA, APP SA,
C-24
ASTM D41
ENRGY 3, H-Shield, H-Shield CG or
HA
HA
SBS-SA
concrete
Multi -Max FA3
Fiber Roof Board
SBS-SA or APP-TA
SBS-TA or APP-TE
ASPHALT AND/ORTORCH APPLIED SYSTEMS:
C-25
Structural
None
Min. 2-inch ACFoam II or H-Shield
D-IS
Min. 0.25-inch SECUROCK Gypsum-
D-IS
BP -AA
(Optional) One or more
SBS-AA
concrete
Fiber Roof Board
BP -AA
C-26
Structural
None
Min. 2-inch ACFoam II or H-Shield
D-IS
Min. 0.25-inch SECUROCK Gypsum-
D-I5
APP-TA
(Optional) One or more
APP-TA
concrete
Fiber Roof Board
APP-TA
C 27
Structural
None
Min. 2-Inch ACFoam 11 or H-Shield
OB500
Min. 0.25-inch SECUROCK Gypsum-
OB500
BP -AA
(Optional) One or more
SOS -AA
concrete
Fiber Roof Board
BP -AA
C 28
Structural
None
Min. 2-inch ACFoam 11 or H-Shield
OB500
Min. 0.25-inch SECUROCK Gypsum-
OB500
APP-TA
(Optional) One or more
APP-TA
concrete
Fiber Roof Board
APP-TA
None
Min. 2-inch ACFoam II or H-Shield
M-OSFA
Min. 0.25-inch SECUROCK Gypsum
M-OSFA
BP -AA
(Optional) One or moreSBS-AA
EStructural
concrete
Fiber Roof Board
BP-AAStructural
None
Min. 2-inch ACFoam II or H-Shield
M-OSFA
Min. 0.25-inch SECUROCK Gypsum-
I
M-OSFA
APP-TA
i
(Optional) One or more
APP-TA
concrete
Fiber Roof Board
APP-TA
Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 fol
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2:
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, F
TRINIT
TABLE3A: STRUCTURAL CONCRETE DECKS —NEW CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE A-1: BONDED INSULATION; BONDED ROOF COVER, .
SFF Nnrr 16 cnw \/eono RAGUICC noT me
System
Deck
Primer
Base Insulation Layer
Top Insulation Layer-
Roof Cover (Note 15)
No.
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply
Min.1.5-inch Ultra -Max or Multi -Max
C-31
Structural
None
FA-3, min. 1.3-inch ACFoam III or min.
CR-2D
Min, 0.25-inch SECUROCK Gypsum-
(Optional) One or more
concrete
1.0-inch ISO 95+GL, H-Shleld, H-Shield
Fiber Roof Board
CR-20
BP -AA
BP AA
SBS-AA
CG or ENRGY 3
Min. 1.5 -in ch Ultra -Max or Multi -Max
C-32
Structural
None
FA-3, min. 13-inch ACFoam III or min.
CR-20
Min. 0.25-inch SECUROCK Gypsum
(Optional) One or more
concrete
1.0-Inch ISO 95+GL, H-Shield, H-Shield
Fiber Roof Board
CR-20
APP-TA
APP-TA
APP-TA
CG or ENRGY 3
C•33
Structural
None
(Optional) Min. 2-inch ACFoam II or H-
OB
Classic
Min. 0.25-inch SECUROCK Gypsum-
yp
OB
(Optional) One or more
concrete
Shield
Fiber Roof Board
Classic
BP -AA
BP -AA
SBS-AA
(FULL)
(FULL)
C-34
Structural
None
(Optional) Min. 2-inch ACFoam II or H-
OB
Classic
Min. 0.25-Inch SECUROCK Gypsum-
yp
OB
(Optional) One or more
concrete
Shield
Fiber Roof Board
Classic
APP-TA
APP-TA
APP-TA
(FULL)
(FULL)
C-35
Structural
ASTM D41
Min. 1.5-inch ACFoam 11, ACFoam III,
ENRGY 3, H-Shield, H-Shield CG or
HA
Min. 0.25 inch SECUROCK Gypsum-
HA
(Optional) One or more
concrete
Multi -Max FA3
Fiber Roof Board
BP -AA
BP -AA
SBS-AA
Structural
Min. 1.5-inch ACFoam II, ACFoam III,
C-3G
ASTM D41
ENRGY 3, H-Shield, H-Shield CG or
HA
Min. 0.25-Inch SECUROCK Gyp sum
HA
APP-TA
(Optional) One or more
concrete
Multi -Max FA3
Fiber Roof Board
APP-TA
APP-TA
(Optional if
C-37
Structural
ASTM D41
Min. 0.75-Inch FescoBoard
HA
None
N/A
using AA Ply)
(Optional if using AA
SBS-AA, SBS-TA,
concrete
(homogeneous)
One or more
Base) One or more BP-
APP-TA
BP -AA
AA or APP TA
Structural
Min. 1.5-inch ACFoam II, ACFoam III,
(Optional if
(Optional if using AA
C-38
concrete
ASTM D41
ENRGY 3, H-Shield, H-Shield CG or
HA
Min. 0.75-inch Fesco Board
HA
using AA Ply)
Base) One or moree BP-
SBS-AA, SBS-TA,
Multi -Max FA3
One or more
AA or APP-TA
APP-TA
BP -AA
(Optional if
C-39
Structural
ASTM D41
Min. 0.5-inch Structodek High(Optional
Densit y
HA
None
NSA
using AA Ply)
if using AA
SBS-AA, SBS-TA,
concrete
Fiberboard Roof Insulation
One or more
Base) One or more BP-
APP-TA
BP -AA
AA or APP-TA
Structural
Min. 1.5-inch ACFoam 11, ACFoam III,
(Optional if
(Optional if using AA
C-40
concrete
ASTM D41
ENRGY 3, H-Shield, H-Shield CG or
HA
Min. 0.5-inch Structodek High
HA
using AA Ply)
Base) One or more BP-
SBS-AA, SBS-TA,
Multi -Max FA3
Density Fiberboard Roof Insulation
One or more
APP-TA
BP AA
AA or APP-TA
Exterior Research and Design, I.I.C. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for F
Certificate of Authorization 49503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 0
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Pal
i TRINIP
TABLE 3A: STRUCTURAL CONCRETE DECKS —NEW CONSTRUCTION OR REROOF (TEAR -OFF)
.SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
SEE NOTE 16 FOR VAPOR BARRIER OPTIONS
System
Deck
Primer
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 15)
No.
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply
Structural
Min. 1.5-Inch ACFoam II, ACFoam III,
(Optional if
(Optional if using AA
C-41
concrete
ASTM D41
ENRGY 3, H-Shield, H-Shield CG or
HA
Min. 0.25-Inch Dens Deck Prime
HA
using AA Ply)
Base) One or more BP-
SBS-AA, SBS-TA,
Multi -Max FA3
One or more
AA or APP-TA
APP-TA
BP -AA
(Optional if
C 42
Structural
concrete
ASTM D41
Min. 0.25-inch Dens Deck Prime
HA
None
N/A
using AA Ply)
(Optional if using AA
Base) One or more BP-
SBS-AA, SBS-TA,
One or more
AA or APP-TA
APP -TA
BP -AA
TABLE3B: STRUCTURAL CONCRETE DECKS —NEW CONSTRUCTION.OR REROOF (TEAR -OFF)
SYSTEM TYPE F: NON -INSULATED, BONDED BASE SHEET; BONDED ROOF COVER
System No.
Deck
Primer
Roof Cover (Note 15)
Base Ply
Ply
Cap Ply
C-43
Structural concrete
ASTM D41
SBS-SA
(Optional) SBS-SA or APP-TA
SBS-SA, APP-SA, SBS-TA or APP-TA
C-44
Structural concrete
ASTM D41
BP -AA (Optional if using asphalt applied Ply)
(Optional if using asphalt applied Base) BP -AA or APP-TA
SBS-AN SBS-TA, APP-TA
Exterior Research and Design, LLC. d/b/a Trinity(ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
C" EDITION (2017) FBC NON-HVHZ EVALUATION
TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485
Evaluation Report A42970.10.12-R2 for F
Revision 2: 0
Appendix 1, Pai
TRINI ■
TABLE4A: LIGHTWEIGHT CONCRETE DECKS —NEW CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE A-1:,.B6NDED INSULATION, BONDED. ROOF COVER
System
Deck
Lightweight
Base Insulation Layer
Coverboard
Roof Cover (Note 15)
No.
(Note 1)
Concrete (Note 14)
Type Attach
Type Attach
Base Ply Ply Cap PIV
SELF -ADHERING SYSTEMS WITH -BASE INSULATION AND OPTIONAL TOP INSULATION OF THE SAME TYPE:
LWC-1
Structural
Min. 200 psi, min 2-
Min. 1.5-inch, min. 2.0 pcf Insulfoam
OB500
(Optional) Additional
OB500
SBS-SA
(Optional) One or
SBS-SA, AF
concrete
inch Elastizell
layers of base insulation
more SBS-SA
SA
LWC-2
Structural
Min. 200 psi, min 2-
Min. 1.5-inch ACFoam II, ENRGY 3, ISO 95+ GL
(Optional) Additional
(Optional) One or
SBS-SA, AF
concrete
inch Elastizell
or H-Shleld
OB500
layers of base insulation
OB500
5BS-SA
more SOS SA or
SA, SBS TA
APP-TA
or APP-TA
LWC-3
Structural
Min. 200 psi, min.
Min. 2.0 pcf Insulfoam
CR-20
(Optional) Additional
CR-20
SBS-SA
(Optional) One or
SBS-SA, AF
concrete
2-inch Elastizell
layers of base insulation
more SBS-SA
SA
Structural
Min. 200 psi, min.
Min.1.5-inch ACFoam II, ACFoam III, ENRGY 3,
(Optional) Additional
(Optional) One or
SBS-SA, AP
LWC-4
concrete
2 Inch Elastizell
SO 95+ GL, H-Shield, H-Shield CG, Multi -Max
CR-20
layers of base insulation
CR-20
SBS-SA
more SBS-SA or
SA, SBS-TA
APP-TA
or APP-TA
LWC-5
Structural
Min. 200 psi, min.
2-inch Celcore or
Min. 2.0 pcf Insulfoam
CR-20
(Optional) Additional
)
CR-20
SBS-SA
(Optional) One or
SBS-SA, AP
concrete
Mearlcrete
layers of base insulation
more SBS-SA
SA
Structural
Min. 200 psi, min.
Min. 1.5-inch ACFoam II, ACFoam III, ENRGY 3,
(Optional) Additional
(Optional) One or
SBS-SA, AP
LWC-6
concrete
2-Inch Celcore or
ISO 95+ GL, H-Shield, H-Shield CG, Multi -Max
CR-20
la yers of base insulation
CR-20
SBS-SA
more SBS-SA or
SA, SBS-TA
Mearlcrete
FA3
APP-TA
or APP-TA
SELF -ADHERING SYSTEMS WITH BASE INSULATION AND•COVERROARD:
Structural
Min. 200 psi, min 2-
Min. 0.25-inch SECUROCK
(Optional) One or
SBS-SA, API
LWC-7
concrete
inch Elastizell
Min. 1.5-inch, min. 2.0 pcf Insulfoam
OB500
Gypsum -Fiber Roof Board
OB500
SBS-SA
more 5BS-SA or
SA, SBS-TA
APP-TA
or APP-TA
Structural
Min. 200 psi, min 2-
Min. 1.5-inch ACFoam 11, ENRGY 3, ISO 95+ GL
Min. 0.25-inch SECUROCK
(Optional) One or
5BS-SA, APi
LWC-8
concrete
inch Elastizell
or H-Shield
OB500
Gypsum -Fiber Roof Board
OB500
SBS-SA
more SBS-SA or
SA, 5BS-TA
APP-TA
or APP-TA
Structural
Min. 200 psi, min.
Min. 1.5-Inch ACFoam 11, ACFoam III, ENRGY 3,
Min. 0.25-inch SECUROCK
(Optional) One or
SBS-SA, APF
LWC-9
concrete
2-inch Elastizell
ISO 95+ GL, H-Shield, H-Shield CG, Multi -Max
CR-20
Gypsum -Fiber Roof Board
CR-20
SBS-SA
more SBS-SA or
SA, SBS-TA
FA3 or min. 2.0 pcf Insulfoam
APP-TA
or APP-TA
Structural
Min. 200 psi, min.
Min. 1.5-inch ACFoam II, ACFoam III, ENRGY 3,
Min. 0.25-inch SECUROCK
(Optional) One or
SBS-SA, APF
LWC-10
2-inch Celcore or
ISO 95+ GL H-Shield, H-Shield CG, Multi -Max
CR-20
CR-20
5BS-SA
more 5BS-SA or
SA, SBS-TA
concrete
Mearlcrete
FA3 or min. 2.0 pcf Insulfoam
G ypsum-Fiber Roof Board
APP-TA
or APP-TA
ASPHALT ANIJ/OR TORCH APPLIED SYSTEMS:
LWC-11
Structural
Min. 200 psi, min 2-
Min. 1.5-inch ACFoam II, ENRGY 3, ISO 95+ GL
Min. 0.25-inch SECUROCK
BP -AA,
(Optional) One or
SBS-AA, 5BS
concrete
Inch Elastizell
or H-Shield
OB500
Gypsum -Fiber Roof Board
OB500
APP-TA
TA re BP -AA or APP-
TA, APP-TA
Structural
Min. 200 psi, min.
Min. 1.5-inch ACFoam II ACFoam III, ENRGY 3
'
Min. 0.25-inch SECUROCK
BP -AA,
(Optional) One or
5BS-AA, 5BS
LWC-12
concrete
2-inch Elastizell
ISO 95+ CG, Multi -Max
CR-20
Gypsum -Fiber Roof Board
CR 20
APP-TA
more OP -AA or APP-
TA, APP-TA
in. 2.Shleld, ulfoarld
FA3 or min. 2.0 pcf Insulfoam
TA
Exterior Research and Design, LLC. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 for
" Certificate of Authorization 49503 C" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2:
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, F
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS —NEW CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE A-1: BONDED INSULATION; BONDED ROOF COVER
System Deck
Lightweight
Base Insulation Layer
Coverboard
Roof Cover (Note 15)
No. (Note 1)
Concrete (Note 14)
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply
Structural
Min. 200 psi, min.
Min. 1.5-inch ACFoam II, ACFoam III, ENRGY 3,
(Optional) One or
LWC-13
concrete
2-inch Celcore or
150 95+ GL, H-Shield, H-Shield CG, Multi -Max
CR-20
Min. 0.25-inch SECUROCK
CR-20
_AA,
more BP -AA or APP-
SBS-AA, SBS-
Mearlcrete
FA3 or min. 2.0 pcf Insuifoam
Gypsum Fiber Roof Board
APP-TA
TA
TA, APP-TA
TABLE4B: LIGHTWEIGHT CONCRETE DECKS —NEW CONSTRUCTION ORREROOF,(TEAR-OFF)'
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION; BONDED. ROOF COVER
System
Deck
Lightweight
Anchor Sheet
Base Insulation
Top Insulation
Roof Cover (Note 15)
No.
(Note 1)
Concrete
(Note 14)
Type
Fasteners
Attach
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply
Min. 1.5-Inch
Min. 22 ga.,
7-inch o.c. at
(Optional) Min.
Thermaroof Composite,
Type B,
Min. 300 psi
4-inch lap and
1.5-inch
Polytherm Composite or
(Optional If
LWC-14
vented steel
Approved
GAFGLAS
OMG CR
7-inch o.c. in
ACFoam II, H-
HA
min. 0,5-Inch Structodek
(Optional if
using AA Base)
SBS-AA, SBS-
at max. 5 ft
cellular LWC
N75
BSF
two, equally
Shield, Multi-
High Density Fiberboard
g y
HA
using AA Ply)
One or more
TA, APP-TA
spans
spaced center
Max FA3 or
Roof Insulation or min.
BP -AA
BP -AA orFlPP-
rows
Polytherm
0.75-inch FescoBoard
TA
(homogeneous)
Min. 22 ga.,
7-inch o.c. at
Min. 1.5-inch
LWC-15
Type B,
vented steel
Min. ve psi
Approved
GAFGLAS
OMG CR
4-inch lap and
7-inch o.c, in
ACFoam II, H-
(Optional) One
SBS-SA, APP-
at max. 5 ft
cellular LWC
k75
BSF
two, equally
Shield, Multi-
HA
None
N/A
SBS-SA
or more SBS-SA
SA, SBS-TA
spans
spaced center
Max FA3 or
or APP-TA
or APP-TA
Polytherm
rows
Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 for FL
Certificate of Authorization #9503 6r"EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Pag(
TRINIT
TABLE 4C: • LIGHTWEIGHT CONCRETE DECKS —NEW CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE E:'.MECHANICALLY ATTACHED BASE SHEET;`BONDED ROOF.COVER
System Deck Base Sheet (Note A below) Roof Cover (Note 15)
No Lightweight Concrete (Note 14) Type
(Note 1) (Note A) Fasteners Attach Base Ply A�C-p
GENERIC CELLULAR LIGHTWEIGHT INSULATING CONCRETE:
Min. 300 psi, min. 2-inch thick cellular
Min. 22 ga., type B steel
LWC. Note: To qualify the LWIC under this
7=inch o.c. in a 3-inch lap and 7-inch o.c. in
(Optional)
LWC-16
at max 5 ft spans or
assembly, an OMG CR BPF shall achieve
B3
OMG CR BPF
two, equally spaced, staggered rows in the
One or more
58SB S AA, Al
structural concrete
an average withdrawal of 53 lbf when
field of the sheet
BP -AA
TA
tested per TAS 105 or ANSI/SPRI FX-1
CELCORE CELLULAR LIGHTWEIGHT INSULATING CONCRETE:
Min. 0.0179-inch
Tensilform 5-75 or min.
LWC-17
0.0205-inch Tensilform
Min. 200 psi, min. 2-inch thick Celcore
75 at max. 5 ft spans or
structural concrete
Min. 22 ga., type B steel
LWC-18
at max 5 ft spans or
Min. 200 psi, min. 2-inch thick Celcore
structural concrete
Min. 26 ga., type HF
LWC-19
steel at max 5 ft spans
Min. 225 psi, min. 2-inch thick Celcore
or structural concrete
Min. 22 ga., type B steel
LWC-20
at max 6 ft spans or
Min. 225 psi, min. 2-Inch thick Celcore
structural concrete
Min. 22 ga., type B steel
LWC-21
at max 6 ft spans or
Min. 225 psi, min. 2-Inch thick Celcore
structural concrete
Min. 22 ga., type B steel
LWC-22
at max 5 ft spans or
Min. 225 psi, min. 2-Inch thick Celcore
structural concrete
Min. 22 ga., type B steel
LWC-23
at max 5 ft spans or
Min. 225 psi, min. 2-Inch thick Celcore
structural concrete
Min. 22 ga., type B steel
LWC-24
at max 5 ft spans or
Min. 300 psi, min. 2-inch thick Celcore
structural concrete
Min. 22 ga., type B steel
LWC-25
at max 5 ft spans or
Min. 300 psi, min. 2-inch thick Celcore
structural concrete
B1, 82, B3 or B7 Trufast FM-90 or
OMG CR BPF
Bl through B12
Trufast FM-90 or
OMG CR BPF
B1, B2, B3, B4,
MF
B7, B8, B10, B11
OMG CR BPF
or B12
B1, B2, B3, B4,
MF
B7, B8, B10, 811
OMG CR BPF
or 812
B1, B2, B3, 84,
MF
B7, 138, B10, B11
OMG CR BPF
or B12
Trufast Twin Loc-
MF
Bl or B2
Nail
132 (with poly-
Trufast Twin Loc-
MF
film top surface)
Nail
MF I B2 I Trufast FM-90
MF IB2 (with poly- I Trufast FM-90
film top surface)
8-inch o.c. in a 3-inch lap and 16-inch o.c. in
two, equally spaced, staggered rows in the
One or more
SBS-AA
field of the sheet
BP AA
7-inch o.c. in a 3-inch lap and 7-inch o.c. in
two, equally spaced, staggered rows in the
One or more
SBS-AA
field of the sheet
BP AA
9-inch o.c. in a 3-inch lap and 9-inch o.c. In
two, equally spaced, staggered rows in the
One more
SBS-AA
field of the sheet
BP AAA
7-inch o.c. in a 3-inch lap and 14-Inch o.c. In
two, equally spaced, staggered rows In the
One or more
SBS-AA
field of the sheet
BP AA
9-inch o.c. in a 3-inch lap and 9-inch o.c. in
two, equally spaced, staggered rows in the
One or more
SBS-AA
field of the sheet
BP AA
9-inch o.c. in a 4-Inch lap and 18-inch o.c. in
One or more
two, equally spaced, staggered rows in the
BP -AA or APP-
SBS-AA, SB
field of the sheet
TA
TA or APP-'
9-inch o.c. in a 4-inch lap and 18-inch o.c. in
One or more
SBS-SA, API
two, equally spaced, staggered rows in the
SBS-SA or
SA, SBS-TA
field of the sheet
APP-TA
or APP-TA
8-Inch o.c. In a 4-inch lap and 8-Inch o.c. in
BP -AA or APP-
SBS-AA, SB;
three equally spaced, staggered center rows
TA
TA or APP
8-Inch o.c. in a 4-inch lap and 8-inch o.c. In
One or more
SBS-SA, API
SBS-SA or
SA, SBS-TA
three equally spaced, staggered center rows
APP-TA
or APP-TA
Exterior Research and Design, I.I.C. d/b/a Trinity)ERD Evaluation Report A42970.10.12-R2 fo
Certificate of Authorization N9503 C" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1,
TRI VIT
I TABLE 4C: - LIGHTWEIGHT CONCRETE DECKS —NEW CONSTRUCTION oR REROOF,(TEAR-OFF),
SYSTEM TYPESrMECHANICALLYATTACHED BASESHEET: BONDED ROOF:COVFR
System
Deck
Base Sheet (Note A below)
Roof Cover (Note 15)
Type
No.
(Note 1)
Lightweight Concrete (Note 14)
(Note A)
Fasteners
Attach
Base Ply
Cap Ply
Min. 22 ga., type B steel
Trufast FM-90 or
7-inch o.c. in a 3-inch lap and 7-Inch o.c. in
One or more
LWC-26
at max 5 ft spans or
Min. 300 psi, min. 2-inch thick Celcore
B1 through B12
two, equally spaced, staggered rows in the
S135-AA
structural concrete
OMG CR BPF
field of the sheet
BP AA
Min. 22 ga., type B steel
LWC-27
at max 5 ft spans or
Min. 300 psi, min. 2-inch thick Celcore MF
Pol lass
yg
Trufast FM-260
10-inch o.c. in a 4-inch la and 10-Inch o.c. in
P
(Optional) BP-
SBS-AA, Se
structural concrete
Elastobase Poly
three equally spaced, staggered center rows
AA or APP-TA
TA, APP TE
I: ASTIZELL CELLULAR LIGHTWEIGHT INSULATING CONCRETE:
Min. 0.0179-inch
Tensilform S-75 or min.
Min. 200 psi, min. 2-1nch thick Elastizell
Trufast FM-90 or
7.5-inch o.c. in a 3-Inch lap and 7.5-Inch o,c.
One or more
SBS-AA, SB
LWC-28
0.0205-Inch Tensilform
Range II
81 through B12
OMG CR BPF
in two, equally spaced, staggered rows in the
BP -AA or APP-
TA or APP=
75 at max. 5 ft spans or
field of the sheet
TA
-
structural concrete
Min. 0.0179-inch
Tensllform 5-75 or min.
Min. 200 psi, min. 2-inch thick Elastizell
B2 (with poly-
Trufast FM-90 or
7.5-inch o.c. in a 3-inch lap and 7.5-inch o.c.
One or more
5BS-SA, AP
LWC-29
0.0205-Inch Tensilform
Range II
film top surface)
OMG CR BPF
in two, equally spaced, staggered rows in the
SBS-SA or
SA, SB5-TA
7S at max. 5 ft spans or
field of the sheet
APP-TA
or APP-TA
structural concrete
Min. 22 ga., type B steel
Min. 200 psi, rein. 2-inch thick Elastizell
Trufast FM-90 or
7-Inch o.c. In a 3-inch lap and 7-inch o.c. in
One or more
513S-AA, SB.
LWC-30
at max 5 ft spans or
Range II
Bl through B12
OMG CR BPF
two, equally spaced, staggered rows in the
BP -AA or APP-
TA or APP=
structural concrete
field of the sheet
TA
Min. 22 ga., type B steel
Min. 200 psi, min. 2-inch thick Elastizell
82 (with poly-
Trufast FM-90 or
7-inch o.c. in a 3-inch lap and 7-inch o.c. in
One or more
SBS-SA, API
LWC-31
at max 5 ft s
spans or
P
Range it
film top surface)
OMG CR BPF
two, equally spaced, staggered rows in the
SBS-SA or
SA, SBS-TA
structural concrete
field of the sheet
APP-TA
or APP-TA
Min. 22 ga., type B steel
Min. 350 psi, min. 2-inch thick Elastizell
Trufast Twin Loc-
6-inch o.c, in a 4-inch lap and 6-inch o.c. In
SB5-AA, SB'
LWC-32
at max 5 ft spans or
with Zell -Crete Fibers, supple -mentally
pple-mental) y
82
Nails (min. 1.8-
three, equally spaced, staggered rows in the
One or more
TA, SBS-SA,
structural concrete
attached with Roofgrip N21 and 3-inch
Inch)
field of the sheet
BP -AA
APP-TA or
plates at 1 per 8 ft2
APP-SA
Min. 22 ga., type 8 steel
Min. 350 psi, min. 2-inch thick Elastizell
Trufast Twin Loc-
6-inch o.c. in a 4-inch lap and 6-inch o.c. in
SB5-SA, API
LWC-33
max 5 ft spans or
with Zell -Crete Fibers, supple -mentally
82 (with poly-
Nails (min. 1.8-
three, equally spaced, staggered rows in the
SBS-SA or
SA, 585-TA
structural concrete
t
attached with Roofgrip #21 and 3-inch
film top surface)
inch}
field of the sheet
AI'P-TA
or APP-TA
plates at 1 per 8 ft2
MEARLCRETE CELLULAR LIGHTWEIGHT INSULATING CONCRETE:
Min. 24 ga., type B steel Trufast FM-90 or 7.5-inch o.c. in a 3-Inch lap and 10-inch o.c. One or more
LWC-34 at max 5 ft spans or Min. 200 psi, min. 2-Inch thick Mearlcrete Bl through B12 OMG CR BPF in two, equally spaced, staggered rows in the BP AA SBS-AA
structural concrete field of the sheet
Exterior Research and Design, LLC. d/b/a Trinity)ERD Evaluation Report A42970.10.12-R2 for
Certificate of Authorization 49503 G'" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2:
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, r
.6 -
TRINIT
TABLE4C: LIGHTWEIGHT CONCRETE DECKS -NEW CONSTRUCTION ORREROOF(TEAR-OFF)
SYSTEM TYPE E: MECHANICALLY ATTACHED BASE:SHEET; BONDED ROOF COVER
System
Deck
Base Sheet (Note A below)
Roof Cover (Note 15)
Type
No.
(Note 1)
Lightweight Concrete (Note 14)
(Note A)
Fasteners
Attach
Base Ply
Cap Ply
Min. 22 ga., type B steel
Trufast FM-90 or
7-inch o.c. in a 4-Inch lap and 7-inch o.c. in
One or more
SBS-AA, SB
LWC-35
at max 5 ft spans or
Min. 300 psi, min. 2-Inch thick Mearicrete
B1, B2 or B12
OMG CR BPF
two, equally spaced, staggered rows in the
BP -AA or APP-
structural concrete
field of the sheet
TA
TA or APP=
Min. 22 ga., type B steel
B2 (with poly-
Trufast FM-90 or
7-inch o.c. in a 4-inch lap and 7-Inch o.c. in
One or more
SBS-SA, AP
LWC-36
at max 5 ft spans or
Min. 300 psi, min. 2-Inch thick Mearlcrete
film tosurface)
p
OMG CR BPF
two, equally spaced, staggered rows in the
SBS-SA or
SA, SBS-TA
structural concrete
field of the sheet
APP-TA
or APP-TA
Min. 22 ga., type B steel
61, B2, B3, 87 or
Trufast FM-90 or
7-inch o.c. in a 4-Inch lap and 7-inch o.c. in
One or more
SBS-AA, SB.
LWC-37
at max 5 ft spans or
Min. 300 psi, min. 2-inch thick Mearlcrete
B11
OMG CR BPF
two, equally spaced, staggered rows in the
BP -AA or APP-
structural concrete
field of the sheet
TA
TA or APP=
Min. 22 ga., type B steel
B2 (with poly-
Trufast FM-90 or
7-inch o.c. in a 4-Inch lap and 7-Inch o.c. in
One or more
SBS-SA, API
LWC-38
at max 5 ft spans or
Min. 300 psi, min. 2-Inch thick Mearlcrete
film top surface)
OMG CR BPF
two, equally spaced, staggered rows in the
SBS-SA or
SA, SBS-TA
structural concrete
field of the sheet
APP-TA
or APP-TA
A. Base Sheets options are coded as follows:
Y 131: Polyglass G2 Base; 132: Polyglass Elastobase or Polyglass Elastobase Poly; 133: GAFGLAS N75; 84: GAFGLAS Stratovent Nailable Venting Base Sheet; 85: GAFGLAS Ply 4; 136: GAFGLAS F1exPly 6; 87: JM I
No. 28; 88: JM Vensulation; 139: JM GlasPly IV; B10: JM GlasPly Premier; B11: Tamko Glass -Base; B12: Tamko Vapor -Chan
Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report A42970,10.12-132 for
Certificate of Authorization H9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2:
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, P
TRIN17
TABLE 5A: CEMENTITIOUS WOOD FIBER, DECKS— NEW CONSTRUCTION OR,REROOF (TEAR -OFF)
SYSTEM TYPE A4: BONDED INSULATION;•BONDED ROOF COVER
System
Deck
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 15)
No.
(Note 1)
Type
Attach
Type
Attach
Base Ply
Ply
Cap PI)
Min.1.5-inch ACFoam II,
Min. 0.25-Inch Dens Deck, Dens Deck Prime,
(Optional) One or
CWF-1
Min. 2.5-inch Tectum
ISO H-ShiENRG ld,
DAS or
SECUROCK Gypsum -Fiber Roof Board or min. 0.5-
D-IS or
SBS-AA, SB!
Plank or Tectum LS Plank
Polytherm, ENRGY-3
therm,
OB500
inch Structodek High Density Fiberboard Roof
OB500
BP -AA
more BP -AA or APP
APP-TA
insulation
TA
CWF-2
Min. 2.5-Inch Tectum
Min. 1.5-inch ACFoam II,
ISO 95+GL, h ACF a
D-IS or
Min. 0.25-inch Dens Deck, Dens Deck Prime,
DAS or
SBS-SA or
(Optional) One or
SBS-TA, SB5
Plank or Tectum LS Plank
Polytherm, ENRGY-3
OB500
SECUROCK Gypsum -Fiber Roof Board
OB500
APP-TA
more SBS-SA or
APP-TA, AP
App_Tq
Min.1.5-inch ACFoam 11,
Min, 0.25-inch Dens Deck, Dens Deck Prime,
(Optional) One or
CWF-3
Min. 2.5-inch Tectum
plank or Tectum LS Plank
ISO , H-Shield,
CR-20
SECUROCK Gypsum -Fiber Roof Board or min. 0.5-
inch Structodek High Density Fiberboard Roof
CR 20
BP AA
more BP AA or APP-
SBS-AA, SB5
APP-TA
Polytherm, ENRGY-3
TA
Insulation
CWF-4
Min. 2.5-inch Tectum
Min. 1.5-inch ACFoam II,
ISO 95+GL, H-Shield,
CR-20
Min. 0.25-inch Dens Deck, Dens Deck Prime
SBS-SA or
(Optional) One or
SBS-TA, SBS
Plank or Tectum LS Plank
Polytherm, ENRGY-3
SECUROCK Gypsum -Fiber Roof Board
CR-20
APP TA
more SBS-SA or
APP-TA, API
APP-TA
Exterior Research and Design, U.C. d/b/a Trinity ERD
Certificate of Authorization 119503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485
Evaluation Report A42970.10.12-R2I
Revision
Appendix 1
System
No.
Type
tI)Type
MinlassTecobase,
CWF-5lassor
TPlanobase
Poly,
Polyglass G2 Base
Min.2.5-inch
Polyglass
CWF-6 Tectum Plank
Elastobase,
or or Tectum LS
Plank
Elastobase Poly,
Polyglass G2 Base
Min.2.5-Inch
Polyglass
CWF-7 Tectum Plank
Elastobase,
Polyglass
or Tectum LS
Plank
Elastobase Poly,
Polyglass G2 Base
Min.2.5-Inch
Polyglass
Tectum Plank
Elastobase,
CWF-8 or or Tectum LS
Plank
Elastobase Poly,
Polyglass G2 Base
TABLES.,. CEMENTITIOUS,WOOD FIBER DECKS -NEW CONSTRUCTION ORREROOF TEAR -OFF
SYSTEM TYPE A-2: MECHANICALLYATTACHED.ANCHOR SHEET; BONDED.INSULATION, BONDED ROOF COVER
Anchor Sheet Base insulation
Tyr n
Top Insulation Roof Cover (Note 15)
Fastener Attach Type Attach
Type Attach Base Ply Ply Cap F
9-inch o.c. in 4-inch
Min. 1.5-inch
Min. 0.25-inch Dens Deck, Dens
Trufast
lap and 12-inch o.c.
ACFoam II, ACFoam
Deck Prime, SECUROCK Gypsum-
Inuldek
in two, equally
III, ISO95+GL, H-
Fiber Roof Board, Min. 0.75-inch
Loc-Nall
spaced, staggered
Shield, ENRGY 3, HA
FescoBoard (homogeneous) or HA
BP -AA
center rows
Polytherm or Multi
min. 0.5-inch Structodek High
Max FA3
Density Fiberboard Roof
Insulation
9-Inch o.c. in 4-inch
Min. 1.5-inch
Trufast
lap and 12-inch o.c.
ACFoam 11, ACFoam
ISO95+GL, H-
Min. 0.25-inch Dens Deck, Dens
SBS-SA
Inuldek
Loc-Nail
in two, equally
spaced, staggered
ShieldIII,
HA
, ENRGY 3,
Deck Prime, SECUROCK Gypsum- HA
or APP-
center rows
Polytherm or Multi
Fiber Roof Board
TA
Max FA3
9-Inch o.c. in 4-inch
Min. 1.5-inch
Min. 0.25-Inch Dens Deck, Dens
Trufast
lap and 18-inch o.c.
ACFoam Ii, ACFoam
Deck Prime, SECUROCK Gypsum -
Twin
Twin
in two, equally
ISO95+GL, H-
Fiber Roof Board, Min. 0.75-inch
Loc-Nall
spaced, staggered
Shield, ENRGY 3, HA
FescoBoard (homogeneous) or HA
BP -AA
center rows
Polytherm or Multi
min. 0.5-Inch Structodek High
Max FA3
Density Fiberboard Roof
Insulation
9-inch o.c. in 4-inch
Min. 1.5-inch
Trufast
lap and is -inch o.c.
ACFoam II, ACFoam
IIIIS095+GL, H-
Min. 0.25-Inch Dens Deck, Dens
SBS-SA
Twin
Loc-Nail
in two, equally
spaced, staggered
,
HA
Shield, ENRGY 3,
Deck Prime, SECUROCK G sum- HA
YP
or APP-
center rows
Polytherm or Multi-
Fiber Roof Board
TA
Max FA3
(Optional,
One or more SBS-AA
BP -AA or SBS-TA,
APP-TA APP-TA
(Optional)
SBS-TA,
One or more
SBS-SA,
I
SBS-SA or
APP-TA,
APP-TA
APP-SA
(Optional) SBS-AA,
One or more
BP -AA or SBS-TA,
APP-TA APP-TA
(Optional)
SBS-TA,
One or more
SBS-SA,
SBS-SA or
APP-TA,
APP-TA
APP-SA
Exterior Research and Design, LLC. d/b/a Trinity (ERD
Certificate of Authorization 49503 6T"EDITION (2017) FBC NON-HVHZ EVALUATION Evaluation Report A42970.10.12-R2 for F
l Prepared by: Robert Nleminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Revision 2: C
Appendix 1, Pa
TRINITY:ERD
Certificate of Authorization t9503
January I, 2017
RE: Certification of Independence, Florida F.A.C. Rule 61 G20-3
To Whom It May Concern:
This letter serves to document -the following in accordance with Florida F.A.C. Rule 61 G20-3:
I . Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or
will it acquire, afinancial interest in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is not owned, operated or controlled by any
company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company
manufacturing or distributing products for which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved
in the approval process of the product.
5. Building Code Evaluations issued by Trinity{ERD and Robert Nieminen, P.E. are not, in anyway, to be
construed to mean or imply that TrinitylERD or Robert Nieminen, P.E. are the Designer of Record
for any project on which the Evaluation Report is/was used for permitting or design guidance unless
retained specifically for that purpose on a given project.
Please contact our office with any questions.